ABB COMMANDER 360 User Manual page 72

Profile controller
Table of Contents

Advertisement

...5 CONFIGURATION MODE
...5.6 Level A – Control Configuration
A. 1 3
C. O P1
0. 0
A. . 1 4
M5r2
NONE
A. . 1 5
C. O P2
0. 0
A. 1 6
AM. 5 r
NONE
A. 1 7
COP. 3
0. 0
•1
Digital inputs are active when a volt free contact is closed or a low TTL signal is applied
68
Configured Output 1
The control output value required when manual is selected by manual
mode source 1.
[0 to 100% or LAST (non-heat/cool)]
[–100 to 100% (heat/cool only)]
Manual Mode Selection Source 2
The digital source required to select manual mode and Configured
Output 2.
See Rear Fold-out/ Table D –
Digital Sources.
Configured Output 2
The control output value required when manual is selected by manual
mode source 2.
[0 to 100% or LAST (non-heat/cool)]
[–100 to 100% (heat/cool only)]
Auto/Manual Selection Source
Used with auto/manual station.
The source required to lock into manual mode with Configured Output 3.
Switching from manual to auto is not possible via the front panel.
See Rear Fold-out/ Table D –
Digital Sources.
Configured Output 3
The control output value required when manual mode is selected by the
auto/manual selection source.
[0 to 100% or LAST (non-heat/cool)]
[–100 to 100% (heat/cool only)]
Continued...
Manual with output =
C. O P2
Auto
Manual with output =
C. O P3
Auto
A.13...A.17
•1
•1
Auto