ABB COMMANDER 360 User Manual page 85

Profile controller
Table of Contents

Advertisement

...5.10 Level E – Calibration
FCAL
MAN
•1
E11
Fb. L O
100. 0
•1
E. 1 2
Fb. H I
500. 0
rEF
2700
FCAL
NO
O. C AL
NO
Fb. H I
500
E. 1 3
rEF
2700
E. 1 4
bEtA
3977
•2
E. 1 5
CJ1
25. 2
•2
E. 1 6
CJ3
25. 2
LEV. E
CAL
•1
Only displayed if Motorized Valve with feedback output type is selected – see Section 5.2, Basic Configuration.
•2
Only displayed if corresponding input type is set to 'THC'.
Position Feedback Electrical Range Low
Set the minimum electrical input value.
[0.0 to 999.9]
For resistance input types, no decimal places are displayed. For all other
input types, 1 decimal place is displayed.
Position Feedback Electrical Range High
Set the maximum electrical input value.
[0.0 to 999.9]
Continued in
Cold Junction Reference Value
Cold Junction Reference Value
This value should only be changed if a new CJ sensor is supplied with a CJ
reference value different to 2700.
The resistance (in Ohms) of the CJ sensor at 25°C.
Cold Junction Beta Value
This value should only be changed if a new CJ sensor is supplied with a CJ
Beta value different to 3977.
The beta value of the CJ sensor.
Cold Junction Reading – I/P1 and I/P2
The temperature measured by the cold junction sensor is displayed in °C.
Cold Junction Reading – I/P3
The temperature measured by the cold junction sensor is displayed in °C.
Return to top of Calibration Level.