ABB COMMANDER 360 User Manual page 46

Profile controller
Table of Contents

Advertisement

8
...4 SET UP MODE
...4.2 Level 2 – Tune
2. 1 4
drV2
OFF
2. 1 5
Ab. 1
1. 0
2. 1 6
Ab. 2
1. 0
2. 1 7
rSt. 1
50. 0
2. 1 8
rSt. 2
50. 0
•1
Only displayed if a cascade template is selected – see Section 5.2, Basic Configuration/ Template
Application.
•2
Not displayed if the associated derivative action time is set to OFF.
•3
If manual control is selected and no integral action time is set, the manual reset value is calculated
automatically to give bumpless transfer into auto control.
42
•1
Derivative Action Time 2
[0.1 to 999.9 seconds or 'OFF']
The derivative action time for the slave controller if a cascade template is
selected – see Section 5.2, Basic Configuration/ Template Application.
•2
Approach Band 1
[0.1 to 3.0 proportional bands]
This parameter limits when derivative action time 1 is applied. When the
process variable is outside the approach band, derivative action is not applied.
•1
•2
Approach Band 2
[0.1 to 3.0 proportional bands]
This parameter limits when derivative action time 2 is applied to the slave
control loop when a cascade template is selected.
•3
Manual Reset Value 1
The value applied to bring the master control output to the zero error point
under normal load conditions (integral action disabled) or the offset
applied to the control output (integral action enabled).
[0.0 to 100%]
Note. Manual reset is applied whether integral action is selected
ON or OFF.
•1
•3
Manual Reset Value 2
As
Manual Reset Value 1
[0.0 to 100%]
Note. Manual reset is applied whether or not an integral action time
is set.
Continued on next page.
, but applied to the slave output.
2.14...2.18