ABB COMMANDER 360 User Manual page 60

Profile controller
Table of Contents

Advertisement

...5 CONFIGURATION MODE
... 5.3 Level 7 – Analog Inputs
7. 0 4
EN1. H
1000
7. 0 5
ENI. L
0
7. 0 6
b. S d1
UP
7. 0 7
FLt. 1
0
56
Engineering High (I/P1)
[–999 to 9999]
Note. This parameter defaults to the maximum allowed value when
THC or RTD inputs are selected – see Table 5.1.
THC /RTD Type
Min. Max.
–18 1800
Type B
–100
Type E
Type J
–100
Type K
–100
–100
Type L
–200
Type N
–18 1700
Type R & S
Type T
–250
Pt100
–200
Table 5.1 Engineering Limits, THC & RTD Inputs
Engineering Low (I/P1)
[–999 to 9999]
Note. This parameter defaults to the minimum allowed value when
THC or RTD inputs are selected – see Table 5.1.
Broken Sensor Drive (I/P1)
NONE
– No action. Actual input values remain valid.
UP
– Input driven to the maximum upscale value (999)
dN
– Input driven to the minimum downscale value (–999)
In the event of a fault being detected on the input, the input is driven in the
direction selected.
Input Filter Time Constant (I/P1)
The input values are averaged over the time set.
[0 to 60 seconds]
Continued...
°C
Min. Span
Min.
710
900
45
–148
900
50
–148
65
–148
1300
900
50
–148
1300
90
–328
320
300
60
–418
600
25
–328
7.04...7.07
°F
Max.
Min. Span
0
3272
1278
1652
81
1652
90
2372
117
1652
90
2372
162
0
3092
576
572
108
1112
45