...3 PROFILES
...3.5 Ramp/Soak Profile Program
t. 0 9
EVNt
----
SEG_
x
SEG_
NONE
t. 1 0
rPtS
0
t. 1 1
HYS. r
0
t. 1 2
HYS. S
0
•1
t. . 1 3
P. S rC
OFF
LEVt
P. P rG
•1
A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.
38
Time Events
Up to four time-events can be assigned to the segment currently being
programmed – see Fig. 3.7on page 29.
Press the
key to turn event 1 ON.
Press the
key to turn event 1 OFF.
Press the
key to advance to the next event.
Example. '12-4' indicates time events 1, 2, and 4 are active during this
segment and time event 3 is inactive
Repeat Program Profile
[0 to 99 or INFN]
If 'INFN' (infinity) is selected, the program is repeated until stopped by the
operator.
Guaranteed Ramp Hysteresis
[0.001 and 9999 in engineering units or '0' if no deviation from the profile
is allowed]
Guaranteed Soak Hysteresis
[0.001 and 9999 in engineering units or '0' if no deviation from the profile
is allowed]
Program Source
The program source is leading edge triggered i.e. the active logic state
can be removed after the function is selected.
See Rear Fold-out/Table D,
Digital Sources.
Return to
Select Program
frame.
t.09...t.13
Select Program