...2 OPERATOR LEVEL
...2.2 Single Loop Controller (Template 1)
888
OP1
•1 Adjustment can be disabled in the Profile Control Level
12
•1
70
Time Remaining in Current Segment
[0.0 to 99.9 hours or minutes]
Allows the total segment time to be increased or
decreased by the Time Adjust value set in the Profile
Control Level. If the current segment is a ramp, it will
change the ramp rate.
Time units are set in the Profile Control Level – see
Section 3.4/Profile Control/ Program Time Units.
99.9 is displayed if the time remaining is greater
than 99.9 hours or minutes.
Control Output
[0 to 100% (digital/relay outputs),
–10 to 110% (analog outputs)]
Adjustable in manual mode only. With on/off control
selected, 0% = control output off, 100% = control
output on. In manual mode, intermediate values can
be selected. These use 'time proportioning' with a
60s cycle time, e.g. 25% = 15s on, 45s off.
Note. This frame is displayed automatically
when manual mode is selected from the front panel.