5.8.1 Digital Output 1

tYP1
dIG
•1
C. 0 7
dGI. A
NONE
•2
C. 0 8
dG1. P
POS
AN2. A
NONE
•1
If the output is assigned to a control output by the control type, the setting displayed cannot be changed – see
Section 5.2, Basic Configuration/Control Output Type.
•2
Not applicable if digital output 1 is assigned to a control output.
Digital Output 1 (do1) Assignment Source
Select the source required to activate Digital Output 1
See Rear Fold-out/ Table D – Digital Sources.
Digital Output 1 (do1) Polarity
The output can be set to energize for either an active or inactive digital
signal.
– Output energized when source is active.
POS
– Output energized when source is inactive.
NEG