Error Messages - ABB COMMANDER 360 User Manual

Profile controller
Table of Contents

Advertisement

...1 DISPLAYS AND FUNCTION KEYS

1.5 Error Messages

Display
351 . 5
Err
350. 0
NVx
351 . 5
A-d
350. 0
Err
351 . 5
9999
350. 0
351 . 5
t. E rr
350. 0
351 . 5
CJ. F
350. 0
StK
999
8
Error/Action
Non-volatile Memory Error
x = 1: Processor Board Memory
x = 3: Power Supply Board Memory
Turn mains power off and on again
(if the error persists, check
configuration/setup settings).
A to D Converter Fault
The analog to digital converter is not
communicating correctly.
Input Value Over/Under Range
Auto-tune Error
The number displayed indicates the
1
type of error present – see Table 2.1
on page 19.
Cold Junction Failed
Cold junction sensor is faulty or has
1
not been fitted correctly.
Valve Sticking
Motorized valve not moving at the
speed expected. Valve may be
sticking.
Position Feedback Fail
Input value is over- or under-range.
Only appears if output type set to
'PFb' – motorized valve with feeback.
To clear the display:
Press and hold the
Contact the Customer
Support Organization
Restore valid input
Press and hold the
Check connections or replace
if faulty.
Check that the correct
Regulator Travel Time has
been set – see Section 4.5.
Check the valve.
Restore valid input
key
key