I/O Terminal Connections - Emerson EVH Series Installation Manual

Variable frequency drive
Table of Contents

Advertisement

Factory-Set Control Terminal Functions
I/O Connection
External Wiring Pin
Signal Name
1
+10V
2
AI1+
3
AI1-
i
4
AI2+
5
AI2-
6
GND
7
DIN5
8
DIN6
9
DIN7
10
DIN8
11
CMB
12
GND
13
24Vo
14
DO1
15
24Vo
16
GND
17
AO1+
18
AO2+
19
24Vi
20
DIN1
21
DIN2
22
DIN3
23
DIN4
24
CMA
25
A
26
B
27
R3NO
28
R1NC
29
R1CM
30
R1NO
31
R3CM
32
R2NC
33
R2CM
34
R2NO
Notes
-
The above wiring demonstrates a SINK configuration. It is important that CMA and CMB are wired to
ground (as shown by dashed line). If a SOURCE configuration is desired, wire 24 V to CMA and CMB
and close the inputs to ground. When using the +10 V for AI1, it is important to wire AI1—to ground (as
shown by dashed line). If using +10 V for AI1 or AI2, terminals 3, 5, and 6 need to be jumpered
together.
-
AI1+ and AI2+ block that it can support 10K potentiometer.
Signal
Ref. Output Voltage
Analog Input 1
a
Analog Input 1 Ground
Analog Input 2
a
Analog Input 2 Ground
I/O Signal Ground
Digital Input 5
Digital Input 6
Digital Input 7\TI+
Digital Input 8\TI-
DI5 to DI8 Common
I/O Signal Ground
+24VDC Output
Digital Output 1
+24VDC Output
I/O Signal Ground
Analog Output 1
Analog Output 2
+24VDC Input
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
DI1 to DI4 Common
RS-485 Signal A/+
RS-485 Signal B/-
Relay 3 Normally Open
Relay 1 Normally Closed
Relay 1 Common
Relay 1 Normally Open
Relay 3 Common
Relay 2 Normally Closed
Relay 2 Common
Relay 2 Normally Open
Default Setting
Description
-
10VDC Supply Source
0-10V
Voltage Speed Reference (Programmable to 4-20mA)
-
Analog Input 1 Common (Ground)
4-20mA
Current Speed Reference (Programmable to 0-10V)
-
Analog Input 2 Common (Ground)
-
I/O Ground for Reference and Control
Preset Speed B0
Sets frequency output to Preset Speed 1
Fire Mode
Enables drive into Fire Mode
Bypass Start
Enables drive into Bypass mode waiting for drive start
Force Auto
Input forces drive into Auto Control place
Grounded
Allows source input
-
I/O Ground for Reference and Control
-
Control voltage output (100mA Max)
Ready
Shows the drive is ready to run
-
Control voltage output (100mA Max)
-
I/O Ground for Reference and Control
Output Frequency
Shows Output frequency to motor 0 - 60Hz (4-20mA)
Motor Current
Shows Motor current of motor 0-FLA (4-20mA)
-
External control voltage input
Run Forward
Input starts drive in forward direction (start enable)
Run Reverse
Input starts drive in reverse direction(start enable)
External Fault
Input causes drive to fault
Fault Reset
Input resets active faults
Grounded
Allows source input
-
Fieldbus Communication (Modbus, BACnet)
-
Fieldbus Communication (Modbus, BACnet)
Fault
Relay output 3 shows VFD is Faulted
Bypass Run
Relay output 1 shows VFD is in a bypass run state
Fault
Relay output 3 shows VFD is Faulted
Run
Relay output 2 shows VFD is in a drive run state
32