Condition Code Description:

D1, Indoor unit - (Condition Code)
DRED (Demand Response Electrical Device)
# Compressor off.
D2, Indoor unit - (Condition Code)
DRED (Demand Response Electrical Device)
# Output capacity limited to 50%.
D3, Indoor unit - (Condition Code)
DRED (Demand Response Electrical Device)
# Output capacity limited to 75%.
E2, Indoor Unit - (Condition Code) {Remote Control Access - 3}
Indoor Standby LED, flash 2 times.
Yellow LED, Outdoor unit flashing 3 times.
(Anti-Freeze Protection)
# Check if the filters are blocked on the indoor unit.
# Check the refrigerant charge.
# Check for blockages within the refrigeration system.
# Check the evaporator fan for correct operation.
FH, Indoor Unit - (Condition Code) {Remote Control Access - 3}
Indoor Heating & Cooling LED, flash 2 times.
Red LED, Outdoor unit flashing 4 times.
(Anti-Freeze Limit – Frequency Drop)
# Check if the filters are blocked on the indoor unit.
# Check the refrigerant charge.
# Check for blockages within the refrigeration system.
# Check the evaporator fan for correct operation.
F6, Indoor Unit. - (Condition Code) {Remote Control Access - 3}
Indoor Cooling LED, flash 6 times.
Yellow LED, Outdoor unit flashing 4 times.
(Anti-High Temperature Protection)
# Check the outdoor coil for airflow obstructions.
# Check the outdoor fan motor for correct operation.