H6, Indoor unit. (Indoor Fan Stall)
Indoor Standby LED, flashing 11 times.
# Remove the fan motor plug from the indoor PCB & operate the unit in "Fan only" mode.
# Measure for DC voltage at the following voltage check points located on the indoor PCB :
Between terminals 1 & 2 (280 – 310V-DC)
Between terminals 2 & 3 (15V-DC)
Note: If the above DC voltage checks are not available, replace the main indoor PCB assembly.
Note: If the above DC voltage checks are okay, continue to the next page.
Page 103 KSSSI116
DC voltage check points on indoor fan motor plug.