Communication Fault Continues:
# Disconnect the supply power & check the continuity of the COM-U wire from the following
points:
COM-U terminal point on the indoor PCB.
To the communication terminal points on the indoor terminal block.
To the communication terminal points on the outdoor terminal block.
To the COM-U terminal point on the outdoor PCB.
Note: When checking the continuity between the indoor terminal block & the outdoor terminal
block, disconnect the COM-U & Active wires on the indoor terminal block, and then attach them
together. This will create a circuit that can then be tested between the COM-U & Active terminal
points on the outdoor terminal block.
COM-U terminal point on indoor PCB.
Communication terminal points on outdoor
terminal block.
Communication terminal points on
indoor terminal block.
COM-U terminal point on outdoor main PCB.
Page 70 KSSSI116