L3, Indoor unit. (Outdoor DC Fan Motor Malfunction)

Indoor Standby LED, flashing 23 times.
Yellow-D5 LED, Outdoor unit On.
Orange-D6 LED, Outdoor unit. Off.
Green-D16 LED, Outdoor unit Off.
Red-D30 LED, Outdoor unit Off.
# Check the condenser fan for correct operation. If the fan motor is not operating check the three
pin DC-Motor connector plug for correct termination to the outdoor PCB.
# Remove the three pin DC-Motor connector plug & check the resistance value from the points
illustrated below.
KSV53HRB:
Blue & Orange (54 K ohms)
Blue & Grey (54 K ohms)
Blue & Brown (54 K ohms)
KSV62HRC, KSV70CRC, KSV70HRC & KSV80HRC:
Blue & Orange (41 K ohms)
Blue & Grey (41 K ohms)
Blue & Brown (41 K ohms)
Note: If the resistance values of the fan motor are okay, replace the outdoor PCB.
Note: These resistance values may vary in accordance to capacity & ambient temperatures.
DC-Fan Motor connector plug located under
outdoor PCB.
Page 105 KSSSI116
Three pin connector Plug, outdoor DC
Fan Motor.