H6 fault continues:
# Check the evaporator fan motor for correct operation. If the fan motor is not operating check the
five pin DC-Motor connector plug on the indoor PCB for correct termination.
# Remove the five pin DC-Motor connector plug & check the resistance value from the following
points:
Yellow & White (155 K ohms)
Yellow & Black (100 K ohms)
Note: If the resistance values of the fan motor are okay, replace the indoor PCB.
Note: These resistance values may vary in accordance to capacity & ambient temperatures.
Five pin indoor DC-Motor connector plug, located on
indoor PCB.
Five pin connector Plug, indoor DC Fan
Motor.