Fault Code Description Continues:
E5, Indoor Unit.
Indoor Standby LED, flash 5 times.
(AC Over-Current Protection)
# While the unit is in operation, check the maximum current draw. If it's above the maximum
current rating illustrated on the outdoor rating plate, check operation of the compressor.
E8, Indoor Unit. (Delayed)
Indoor Standby LED, flash 8 times. (Delayed)
Red LED, Outdoor unit flashing 3 times.
(Anti-High Temperature Protection)
# Check the indoor coil for airflow obstructions.
# Check the indoor fan motor for correct operation.
H1, Indoor unit.
Indoor Heating flashing 1 time.
Yellow LED: Outdoor unit, flashing 2 times.
(Defrosting)
PL, Indoor unit.
Yellow LED: Outdoor unit, flashing 12 times.

(Low Voltage Protection)

# Check supply voltage.
PH, Indoor unit.
Yellow LED, Outdoor unit flashing 13 times.
(High Voltage Protection)
# Check supply voltage.
HC, Indoor unit.
Indoor Heating LED, flash 6 times.
(PFC Protection)
# Check supply voltage.
Page 65 KSSSI116