Off; Flashing - Electrolux KSV26HRC Service Manual

Kelvinator inverter split system
Hide thumbs Also See for KSV26HRC:
Table of Contents

Advertisement

Condition Code Continues:
P5, Indoor Unit. (Compressor Current Out of Normal Range)
Indoor Heating LED, flash 15 times. {Remote Control Access - 4}
Indoor Cooling LED, flash 15 times.
Yellow-D5 LED, Outdoor unit Off.
Orange-D6 LED, Outdoor unit Flashing.
Green-D16 LED, Outdoor unit Off.
Red-D30 LED, Outdoor unit Off.
# Check the indoor & outdoor coils for airflow obstructions.
P8, Indoor Unit. (IPM High Temperature Protection)
Indoor Heating LED, flash 19 times. {Remote Control Access - 4}
Yellow-D5 LED, Outdoor unit On.
Orange-D6 LED, Outdoor unit Off.
Green-D16 LED, Outdoor unit Flashing.
Red-D30 LED, Outdoor unit On.
# Check the outdoor coil for airflow obstructions.
# Check operation of outdoor fan motor.
U3, Indoor unit. (Drop in Supply Voltage)
Indoor Heating LED flashing 20 times. {Remote Control Access - 4}
Yellow-D5 LED, Outdoor unit Off.
Orange-D6 LED, Outdoor unit On.
Green-D16 LED, Outdoor unit On.
Red-D30 LED, Outdoor unit On.
# Check supply voltage.