5.4 Pulse Train Input Parameter List

Parameter Number
384 (*1)
Input pulse frequency division ratio
385
Zero-input pulse frequency
386
Maximum-input pulse frequency
*1 Indicates the frequency division ratio for the input pulses. The frequency resolution to the input pulses varies with
the setting.
CAUTION
When the Pr. 384 value is "0" (factory setting), Pr. 385 and Pr. 386 do not function even if their
values have been set.
Note that if you set any value other than 0Hz in Pr. 385, m erely turning on the start signal w ill
start the m otor at the preset frequency w ithout a pulse train input com m and.
Name
Setting Range
CAUTION
55
PULSE TRAIN INPUT—A500(L)
Minimum
Increments
0 to 250
1
0 to 400Hz
0.01Hz
0 to 400Hz
0.01Hz
Factory Setting
0
0
60