Wiring Instructions - Mitsubishi Electric FR-A5AP Instruction Manual

Transistorized inverter
Table of Contents

Advertisement

REMARKS
Pr.300 to Pr.305 settings for the FR-A5AX/FR-V5AH, Pr.400 to Pr.405 settings for the FR-V5AX are made invalid
when the stop position is set to be specified from outside the inverter (externally), with the FR-A5AP (orientation
control option) fitted to the inverter and when orientation control is used.
Pr.300 to Pr.305 of the FR-A5AX/FR-V5AH, Pr.400 to Pr.405 of the FR-V5AX are made valid when the stop position
is not set from outside the inverter.

6.3 Wiring Instructions

(1) Connection with the position detector (encoder).
Use twisted pair shielded cables (0.2mm
(encoder). Cables to terminals 5V and SG should be connected in parallel or be larger in size according
to the cable length table as indicated below.
To protect the cables from noise, run them away from any source of noise (e.g. the main circuit and
power supply voltage).
(2) Cable length.
1)Cable length within 30m.
Cable Length
Within 10m
Within 20m
Within 30m
2
or larger) to connect the FR-A5AP and position detector
Number of Parallel Cables of 0.2mm
At least 2 cables
At least 4 cables
At least 6 cables
61
ORIENTATION CONTROL AT A MACHINE END—V500
2
Larger-Size Cable
Required
0.4mm
0.75mm
1.25mm
2
or larger
2
or larger
2
or larger