Verifying Voltage and Current Connections

Introduction
Displaying the
screen

Single Phase

resistive load

Split phase

Three phase
Shop for Power Metering products online at:
Correct voltage and current connection of single phase, split phase, or polyphase
connections can be verified using phasor diagrams. Phasor diagrams are graphic
representations that show the magnitude and angular relationship of voltage and current
for each phase of a monitored connection. Each connection diagram on the following
pages shows the correct voltage and current phasor diagrams (for resistive loads) for
that circuit.
To display the Voltage and Current Phasor screen, from the Home screen press Phasor.
The following screen depicting Positive Sequence 3 Phase Wye resistive load will
appear.
The touch screen Demo button presents an animated phasor demo rotation for resistive,
capacitive and inductive loads.
A single phase voltage or current phasor is displayed as a single line showing a channel
reference at 0 degrees and a magnitude relative to its measured value. An arrow head
on the line indicates direction.
Split phase vectors are displayed as dual lines showing channel references and
magnitudes and opposite (180 degrees) directions.
Three phase vectors are displayed as three lines, 120 degrees apart in a resistive load
(unity power factor). Phase displacement will occur in a reactive or capacitive load.
PowerMeterStore
www.
APPENDIX E/ Common Circuit Connections
EP241
Continued on next page
.ca
E-5
1.800.561.8187