Connecting to a Potential Transformer
Procedure
Scale factor
E-14
Shop for Power Metering products online at:
Follow these steps to connect voltage probes to a potential transformer.
Step
1
Turn off power to the PT.
2
Connect the colored voltage probes to the channel inputs on the Energy
Platform top panel.
3
Connect the colored voltage probes to the PT's connections in
accordance with the manufacturer's instructions.
4
Turn on power to the PT.
The scale factor of the PT must be accounted for in making accurate voltage
measurements. Because the monitored output voltage of the PT is stepped-down
(divided) from the original voltage, this ratio must be stepped-up (multiplied) by the
Energy Platform when voltage computations are performed. The PT scale factor is
usually mounted on the PT assembly and is entered into the Energy Platform on the
scale factors screen (refer to page 5-10). Refer to the PT manufacturer's literature for
the scale factor for the device you are using.
PowerMeterStore
www.
Action
.ca