DRANFLEX 3000XL/6000XL Current Probes
DRANFLEX 3000XL and 6000XL Current Probes
Guidelines
Specifications
B-12
Shop for Power Metering products online at:
DRANFLEX 3000XL/6000XL current probes allow current measurements in the range
of 0.5 to 3000 A full scale, or 0.5 to 6000 A full scale. Available in three sizes: 24"
probe length - conductor(s) up to 8" diameter; 36" probe length - conductor(s) up to 11"
diameter; 48" probe length - conductor(s) up to 17" diameter.
Range:
30 / 300 A Range: ±1% of reading ± 0.1A
3000 A Range: ±1% of reading ± 1A
60 / 600 A Range: ±1% of reading ± 0.1A
6000 A Range: ±1% of reading ± 1A
Amplitude: 10%-100% of full scale of probe range
Accuracy: 50 to 60Hz:
Note: Overall measurement accuracy is the probe accuracy plus the instrument
accuracy. Refer to the applicable Dranetz instrument user's guide for
measurement accuracy for the instrument you are using
Phase shift (45 to 65 Hz): ±1 degree
Working voltage: 1000 V Maximum
Frequency range: 10 to 10kHz (-1dB)
Output signal:
Ranges 30 / 300 or 3000A: 1.5VRMS
Ranges 60 / 600 or 6000A: 1.5VRMS
Maximum conductor size:
24 inch probe length conductor(s) up to 8 inch diameter
36 inch probe length conductor(s) up to 11 inch diameter
48 inch probe length conductor(s) up to 17 inch diameter
Operating temperature:
-20°C to + 65°C
0-90% Relative Humidity (non-condensing)
Storage temperature: -40 ºC to 75 ºC
Altitude: 2000m (6560ft) maximum
PowerMeterStore
www.
1.800.561.8187
.ca