Dranetz Energy Platform User Manual page 60

Ortable, hand-held, eight-channel demand and energy meter / monitor
Table of Contents

Advertisement

Harmonic Options, continued
Harmonic/
Interharmonic
data plots
(continued)
3-16
Shop for Power Metering products online at:
Harmonic Computation for 60 Hz
The 5 Hz bins adjacent to the harmonic bin are grouped together for the harmonic
magnitude. For example, at 60 Hz, 175+180+185 bins form the 3rd harmonic. All of
the rest of the 5 Hz bins in between such are used to compute the interharmonic
magnitude.
3.0%
2.5%
2.0%
1.5%
1.0%
0.5%
0.0%
... 160 165 170 175 180 185 190 195 200 205 210 215 220 225 230 235 240 245 250
Properties under Graph Units pertain to the way the graph (not the list) is labelled. The
vertical scale can be in Percent or Engineering units, and Scale to Fund (full scale)
can be chosen to be the fundamental at 100% or the largest component. The
engineering unit for voltage is volts and for current is amperes. The horizontal axis can
be in Hz or Harmonic Number.
harmonic data display
measurement scale for
frequency (x axis) and
amplitude (y axis) of
harmonics
full scale graph relative to
fundamental frequency
www.
3rd harmonic
+
2 adjacent
interharmonics
PowerMeterStore
...
4th harmonic
+
2 adjacent
interharmonics
MARK236
1.800.561.8187
.ca

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ep1

Table of Contents