Phasor Measurement Unit One-Shot - GE D60 Instruction Manual

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

COMMANDS MENU
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are
activated by changing a command setting to "Yes" and pressing the
reverts to "No." The service command is activated by entering a numerical code and pressing the
Not all commands display in the software; use the front panel when required.
PERFORM LAMP TEST
PERFORM LCD TEST
graphical front panel. RED/GREEN/BLUE is to display the solid background color in the whole screen. WHITE & TEXT
PATTERN shows the white background and black texts. BLACK & TEXT PATTERN shows the black background and white
texts. TV TEST PATTERN displays a standard television test pattern (SMPTE color bars). The test screen can be cancelled by
pressing any pushbutton or after 30 seconds of inactivity.
PERFORM PUSHBUTTON TEST
corresponding pushbutton according to the prompt text. A failure message is given if the expected action is not detected
in one minute. Holding the ESCAPE button for five seconds to interrupt the test sequence. The designated function of a
specific pushbutton is bypassed in the test.
UPDATE ORDER CODE
order code to match. If an update occurs, the following message displays.
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message displays.
— Restarts the relay so that changes to configuration settings can take effect. In most cases, if changes are
REBOOT RELAY
made to the configuration settings these changes do not take effect unless the relay is rebooted.
With the CyberSentry option, the Administrator and Operator roles can initiate the Reboot Relay command.
SERVICE COMMAND
"20511" returns all settings to their factory default value. Code "101" is used to clear factory diagnostic information stored
7
in the non-volatile memory. If a code other than these two is entered, the command is ignored and no action is taken.
Various self-checking diagnostics are performed in the background while the D60 is running, and diagnostic information is
stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic
information is cleared before the D60 is shipped from the factory, the user can want to clear the diagnostic information for
themselves under certain circumstances. For example, you clear diagnostic information after replacement of hardware.
Once the diagnostic information is cleared, all self-checking variables are reset to their initial state and diagnostics restart
from scratch.
SAVE VOLATILE DATA
recent as possible instead of relying on the periodic timer to save the data.

7.1.5 Phasor Measurement Unit one-shot

COMMANDS  PMU ONE-SHOT
 COMMANDS
 PMU ONE-SHOT
7-4
SERVICE COMMAND
0
SAVE VOLATILE DATA?
No
— Turns on all front panel LEDs and display pixels for a short duration.
— This command detects either stuck-ON or stuck-OFF pixels (dead pixels) in the display screen on the
— This command tests the pushbuttons on the graphical front panel. During testing, press the
— This command causes the relay to scan the backplane for the hardware modules and update the
UPDATING...
PLEASE WAIT
— Performs specific D60 service actions. Presently, there are two service actions available. Code
— Saves this data to compact flash memory prior to shutdown. This allows the saved data to be as
PMU ONE-SHOT
FUNCTION: Disabled
PMU ONE-SHOT
FRACTIONAL SEC: 0
CHAPTER 7: COMMANDS AND TARGETS
Range: 0, 101
Range: No, Yes
key. The command setting then automatically
ENTER
Range: Enabled, Disabled
Range: 0 to 99 in steps of 1
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
key.
ENTER

Advertisement

Table of Contents
loading