GE D60 Instruction Manual page 588

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

CONTROL ELEMENTS
This scheme uses an under-reaching zone 1 distance element to key a transfer trip signal(s) to the remote terminal(s)
where it is supervised by an over-reaching zone 2 distance element. For proper operation, the zone 1 and 2 phase and
ground distance elements must be enabled, configured, and set per rules of distance relaying.
In single-pole tripping applications, the scheme uses local fault type identification provided by the phase selector together
with information received from the remote terminal(s). The scheme generates output operands
that are used to transmit the signal to the remote end(s). Choices of communications channel include remote inputs/
outputs and telecommunications interfaces. When used with telecommunications facilities, assign the output operands to
operate output contacts connected to assert the individual bits at the interface.
To make the scheme a fully operational stand-alone feature, the scheme output operands must be configured to interface
with other relay functions, output contacts in particular. Typically, you program the output operands to initiate a trip,
breaker fail, and autoreclose, and drive a user-programmable LED as per user application. When used in conjunction with
the Trip Output element, the scheme is pre-configured to initiate trip, breaker fail and single-pole autoreclose actions.
PUTT SCHEME BLOCK
from a pilot cut-out switch are typically used for this purpose.
5
PUTT RX PICKUP DELAY
longest spurious TX signal that can be received simultaneously with the zone 1 pickup. The selected delay increases the
response time of the scheme.
PUTT SEAL-IN DELAY
time delay is applied to this operand for coping with noisy communication channels such as a power line carrier. The
is a minimum guaranteed duration of the
SEAL-IN DELAY
scheme, the trip operands
PUTT NO OF COMM BITS
scheme. The transmit codes and trip table of the PUTT scheme are identical as those for the direct under-reaching transfer
trip scheme.
through
PUTT RX1
PUTT RX4
signals for the scheme. Typically input contacts interfacing with a signaling system are used. In single-bit applications,
must be used. In two-bit applications,
PUTT RX1
,
PUTT RX2
PUTT RX3
remote terminals through OR gates in the FlexLogic, and configure the resulting signals as the
5-374
PUTT RX3:
Off
PUTT RX4:
Off
PUTT SCHEME TARGET:
Self-Reset
PUTT SCHEME EVENT:
Disabled
— This setting allows the user to assign any FlexLogic operand to block the scheme. Contact inputs
— This setting enables the relay to cope with spurious receive signals. Set this delay longer than the
— The output FlexLogic operand
A, B, C, and
PUTT TRIP
3P
— This setting specifies the number of bits of the communications channel available for the
— These settings allow the user to select the FlexLogic operands that represent the receive
PUTT RX1
, and
must be used. In multi-terminal applications, connect the
PUTT RX4
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
(PUTT
OP) is produced according to the PUTT scheme logic. A seal-in
pulse. As this operand activates the trip table of the PUTT
PUTT OP
are sealed-in for the same period of time.
and
must be used. In four-bit applications,
PUTT RX2
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
(PUTT TX1
through
PUTT
TX4)
PUTT
,
PUTT RX1
signals from two or more
RX
inputs.
PUTT RX

Advertisement

Table of Contents
loading

Table of Contents