Phasor Measurement Unit One-Shot - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 11: METERING

Phasor measurement unit one-shot

Phasor measurement unit one-shot settings
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
PDC Control
Range: Enabled, Disabled
Default: Disabled
The synchrophasor standard allows for user-defined controls originating at the PDC, to
be executed on the phasor measurement unit. The control is accomplished via an
extended command frame. The relay decodes the first word of the extended field,
EXTFRAME, to drive 16 dedicated FlexLogic™ operands:
least significant bit) to
PDC NETWORK CNTRL 16
if any, in the EXTFRAME are ignored. The operands are asserted for 5 seconds following
reception of the command frame. If the new command frame arrives within the 5
second period, the FlexLogic™ operands are updated, and the 5 second timer is re-
started.
This setting enables or disables the control. When enabled, all 16 operands are active;
when disabled, all 16 operands remain reset.
TCP Port Number
Range: 1 to 65535 in steps of 1
Default: 4712
This setting selects the TCP port number that will be used for network reporting.
UDP Port Number
Range: 1 to 65535 in steps of 1
Default: 4713
This setting selects the UDP port number that will be used for network reporting.
The phasor measurement unit one-shot feature allows pre-scheduling a phasor
measurement unit measurement at a specific point in time. This functionality can be used
to test for accuracy of the phasor measurement unit, and for manual collection of
synchronized measurements through the system.
Select the Settings > Metering > Phasor Measurement Unit > One-Shot menu item to
open the phasor measurement unit one-shot window.
Figure 483: Phasor measurement unit one-shot configuration settings
The following settings are available for each phasor measurement unit.
PHASOR MEASUREMENT UNIT
PDC NETWORK CNTRL 1
(from the most significant bit). Other words,
(from the
535