GE D60 Instruction Manual page 433

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
5.7.4.2 Phase distance (ANSI 21P, IEC PDIS)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  DISTANCE  PHASE DISTANCE Z1(Z5)
 PHASE DISTANCE Z1
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-112: Memory voltage logic
PHS DIST Z1
FUNCTION: Disabled
PHS DIST Z1 DIR:
Forward
PHS DIST Z1
SHAPE: Mho
PHS DIST Z1 XFMR VOL
CONNECTION: None
PHS DIST Z1 XFMR CUR
CONNECTION: None
PHS DIST Z1
REACH: 2.00 Ω
PHS DIST Z1
RCA: 85°
PHS DIST Z1 REV
REACH: 2.00 Ω
PHS DIST Z1 REV
REACH RCA: 85°
PHS DIST Z1
COMP LIMIT: 90°
PHS DIST Z1
DIR RCA: 85°
PHS DIST Z1
DIR COMP LIMIT: 90°
PHS DIST Z1 QUAD
RGT BLD: 10.00 Ω
PHS DIST Z1 QUAD
RGT BLD RCA: 85°
PHS DIST Z1 QUAD
LFT BLD: 10.00 Ω
PHS DIST Z1 QUAD
LFT BLD RCA: 85°
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: Forward, Reverse, Non-directional
Range: Mho, Quad
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1,
Yd3, Yd5, Yd7, Yd9, Yd11
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1,
Yd3, Yd5, Yd7, Yd9, Yd11
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 60 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 60 to 90° in steps of 1
5
5-219