FLEXLOGIC

5.6.2 FlexLogic rules

When forming a FlexLogic equation, the sequence in the linear array of parameters must follow these general rules:
1.
Operands must precede the operator that uses the operands as inputs.
2.
Operators have only one output. The output of an operator must be used to create a virtual output if it is to be used as
an input to two or more operators.
3.
Assigning the output of an operator to a virtual output terminates the equation.
4.
A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") can be used once
only. If this rule is broken, a syntax error is declared.

5.6.3 FlexLogic evaluation

Each equation is evaluated in the ascending order in which the parameters have been entered.
FlexLogic provides built-in latches that by definition have a memory action, remaining in the set state after the set
input has been asserted. These built-in latches are reset dominant, meaning that if logical "1" is applied to both set
and reset entries simultaneously, then the output of the latch is logical "0." However, they are volatile, meaning that
they reset upon removal of control power.
When making changes to FlexLogic entries in the settings, all FlexLogic equations are re-compiled whenever any
new FlexLogic entry value is entered, and as a result of the re-compile all latches are reset automatically.
To implement FlexLogic using a graphical user interface, see the FlexLogic Design and Monitoring using Engineer
section in the previous chapter.
5

5.6.4 FlexLogic example

This section provides an example of logic implementation for a typical application. The sequence of steps is important to
minimize the work to develop the relay settings. Note that the example in the following figure demonstrates the procedure,
not to solve a specific application situation.
Note that there is also a graphical interface with which to draw logic and populate FlexLogic equation entries. See the
Engineer content at the end of the previous chapter.
In the example, it is assumed that logic has already been programmed to produce virtual outputs 1 and 2, and is only a
part of the full set of equations used. When using FlexLogic, it is important to make a note of each virtual output used; a
virtual output designation (1 to 96) can be assigned only once.
1.
Inspect the example logic diagram to determine if the required logic can be implemented with the FlexLogic
operators. If this is not possible, the logic must be altered until this condition is satisfied. Once done, count the inputs
to each gate to verify that the number of inputs does not exceed the FlexLogic limits, which is unlikely but possible. If
5-202
Figure 5-100: Logic example
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS