Advertisement

GROUPED ELEMENTS

5.7.2 Setting group 1

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)
 SETTING GROUP 1
5
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.

5.7.3 Line pickup

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  LINE PICKUP
 LINE PICKUP
5-214
 LINE PICKUP
 DISTANCE
 POWER SWING
 DETECT
 LOAD ENCROACHMENT
 PHASE CURRENT
 NEUTRAL CURRENT
 WATTMETRIC
 GROUND FAULT
 GROUND CURRENT
 NEGATIVE SEQUENCE
 CURRENT
 BREAKER FAILURE
 VOLTAGE ELEMENTS
 POWER
LINE PICKUP
FUNCTION: Disabled
LINE PICKUP SIGNAL
SOURCE: SRC 1
PHASE IOC LINE
PICKUP: 1.000 pu
LINE PICKUP UV PKP:
0.700 pu
LINE END OPEN PICKUP
DELAY: 0.150 s
LINE END OPEN RESET
DELAY: 0.090 s
See below
See page 5-217
See page 5-238
See page 5-247
See page 5-248
See page 5-260
See page 5-268
See page 5-272
See page 5-275
See page 5-281
See page 5-291
See page 5-300
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.020 to 30.000 pu in steps of 0.001
Range: 0.004 to 3.000 pu in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS