GE D60 Instruction Manual page 728

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

SINGLE-POLE TRIPPING
Table 9-26: Permissive scheme transmit codes for four-bit channels
Phase selector determination of
fault type
AG
BG
CG
AB, ABG, BC, BCG, CA, CAG, 3P,
Unrecognized
Table 9-27: Blocking scheme transmit codes for four-bit channels
Phase selector determination
of fault type
AG
BG
CG
AB, ABG, BC, BCG, CA, CAG, 3P,
Unrecognized
Table 9-28: Unblocking scheme transmit codes for four-bit channels
Phase selector determination of
fault type
AG
BG
CG
AB, ABG, BC, BCG, CA, CAG, 3P,
Unrecognized
The action output is generated per the following tables.
Table 9-29: Permissive scheme trip table for four-bit channels
Remote data
Bit pattern received
RX1
RX2
0
0
0
1
0
0
1
0
0
1
1
0
0
0
0
0
9
0
0
1
0
0
1
0
0
9-32
Bit pattern transmitted
TX1
1
0
0
0
Bit pattern transmitted
TX1
TX2
0
1
1
0
1
1
1
1
Bit pattern transmitted
TX1
1
0
0
0
Remote
determination of
RX3
RX4
fault type
0
1
MULTI-P
0
0
BG
1
0
CG
0
0
AG
0
0
BG
0
0
AG
1
0
CG
0
1
MULTI-P
1
0
CG
0
0
AG
0
0
BG
0
1
MULTI-P
TX2
TX3
0
0
1
0
0
1
0
0
FlexLogic operands asserted
TX3
TX4
TX1 STOP
1
1
1
1
1
0
0
1
0
1
0
0
TX2
TX3
0
0
1
0
0
1
0
0
Local data
Local determination of fault
type
AG
AG
AG
AG, AB, ABG, CA, CAG, 3P,
Unrecognized
BG, AB, ABG, BC, BCG, 3P,
Unrecognized
BG
BG
BG
CG, BC, BCG, CA, CAG, 3P,
Unrecognized
CG
CG
CG
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 9: THEORY OF OPERATION
TX4
0
0
0
1
TX2 STOP
TX3 STOP
TX4 STOP
0
0
0
1
0
0
0
1
0
0
0
1
TX4
0
0
0
1
Trip output
Trip Phase A
Trip Phase B
Trip Phase C

Advertisement

Table of Contents
loading

Table of Contents