CONTROL ELEMENTS
The signal used to initiate the autoreclose scheme is the trip output from protection. This signal can be single pole tripping
for single phase faults and three phase tripping for multi-phase faults. The autoreclose scheme has five operating states.
Table 5-42: Autoreclose states
State
Enabled
Disabled
Reset
Reclose in progress
Lockout
Autoreclose programs
The autorecloser provides four programs that can cause from one to four reclose attempts (shots). After the first shot, all
subsequent recloses are always three-pole. If the maximum number of shots selected is "1" (only one reclose attempt) and
the fault is persistent, after the first reclose the scheme goes to lockout upon another Initiate signal.
For the three-pole reclose programs (modes 3 and 4), an
connection with the tripping logic to cause a three-pole trip for single-phase faults.
Table 5-43: Autoreclose programs
Mode
Autoreclose
mode
1
1 & 3 Pole
5
2
1 Pole
3
3 Pole-A
4
3 Pole-B
The four autoreclose modes are described as follows:
1 & 3 Pole — In this mode, the autorecloser starts the
single-phase initiated, the
timer if the autoreclose is three-phase time delay initiated. If two or more shots are enabled, the second, third, and
fourth shots are always three-pole and start the
1 Pole — In this mode, the autorecloser starts the
fault is three-phase or a three-pole trip on the breaker occurred during the single-pole initiation, the scheme goes to
lockout without reclosing. If two or more shots are enabled, the second, third, and fourth shots are always three-pole
and start the
3 Pole-A — In this mode, the autorecloser is initiated only for single phase faults, although the trip is three pole. The
autorecloser uses the
scheme goes to Lockout without reclosing. If two or more shots are enabled, the second, third, and fourth shots are
always three-phase and start the
3 Pole-B — In this mode, the autorecloser is initiated for any type of fault and starts the
shot. If the initiating signal is
are enabled, the second, third, and fourth shots are always three-phase and start the
Basic reclosing operation
Reclosing operation is determined primarily by the
started by the initiate inputs. A reclose initiate signal sends the scheme into the reclose-in-progress (RIP) state, asserting
the
FlexLogic operand. The scheme is latched into the RIP state and resets only when an
AR RIP
breaker 1) or
AR CLS BKR 2
5-330
Characteristic
Scheme is permitted to operate
Scheme is not permitted to operate
Scheme is permitted to operate and shot count is reset to 0
Scheme has been initiated but the reclose cycle is not finished (successful or not)
Scheme is not permitted to operate until reset received
First shot
Single-
Multi-phase
phase fault
fault
1 Pole
3 Pole
1 Pole
Lockout
3 Pole
Lockout
3 Pole
3 Pole
AR 3-P DEAD TIME 1
timers.
AR 3-P DEAD TIME 2(4)
for the first shot if the fault is single phase. If the fault is multi phase the
AR 3-P DEAD TIME 1
AR 3-P DEAD TIME 2(4)
the scheme starts
AR 3P TD INIT
(autoreclose breaker 2) operand is generated or the scheme goes to the Lockout state.
FlexLogic operand is set. This operand can be used in
AR FORCE 3-P
Second shot
Third shot
Single-
Multi-phase
Single-
phase fault
fault
phase fault
3 Pole or
3 Pole or
3 Pole or
Lockout
Lockout
Lockout
3 Pole or
3 Pole or
3 Pole or
Lockout
Lockout
Lockout
3 Pole or
Lockout
3 Pole or
Lockout
Lockout
3 Pole or
3 Pole or
3 Pole or
Lockout
Lockout
Lockout
timer for the first shot if the autoreclose is
AR 1-P DEAD TIME
timer if the autoreclose is three-pole initiated, and the
timers.
AR 3-P DEAD TIME 2(4)
for the first shot if the fault is single phase. If the
AR 1-P DEAD TIME
timers.
AR 3-P DEAD TIME 2
and
AR MODE
AR BKR SEQUENCE
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Fourth shot
Multi-phase
Single-
Multi-phase
fault
phase fault
fault
3 Pole or
3 Pole or
3 Pole or
Lockout
Lockout
Lockout
3 Pole or
3 Pole or
3 Pole or
Lockout
Lockout
Lockout
Lockout
3 Pole or
Lockout
Lockout
3 Pole or
3 Pole or
3 Pole or
Lockout
Lockout
Lockout
AR 3-P DEAD TIME 2
for the first
AR 3-P DEAD TIME 1
for the first shot. If two or more shots
timers.
AR 3-P DEAD TIME 2(4)
settings. The reclosing sequences are
(autoreclose
AR CLS BKR 1