CHAPTER 9: THEORY OF OPERATION
Operand
Description
PHASE SELECT CG
Asserted when a phase C to ground fault is detected
PHASE SELECT AB
Asserted when a phase A to B fault is detected
PHASE SELECT BC
Asserted when a phase B to C fault is detected
PHASE SELECT CA
Asserted when a phase C to A fault is detected
PHASE SELECT ABG
Asserted when a phase A to B to ground fault is detected
PHASE SELECT BCG
Asserted when a phase B to C to ground fault is detected
PHASE SELECT CAG
Asserted when a phase C to A to ground fault is detected
If none of the fault types outlined in the table is determined, then three-phase fault conditions are checked to detect the
presence of positive-sequence current and the absence of both zero-sequence and negative-sequence current. If these
conditions are met, then the
PHASE SELECT 3P
asserted, indicating that the phase selector failed to identify the fault type.
Finally, the states of the following additional FlexLogic operands are determined.
Table 9-13: FlexLogic operands asserted
Operand
Description
PHASE SELECT SLG
Asserted if any of
PHASE SELECT MULTI-P
Asserted if neither the
The phase selector operands are reset a half cycle after the
defined by the
PHASE SELECTOR RESET
operated.
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
FlexLogic operand is asserted; otherwise, the
PHASE SELECT
AG,
PHASE SELECT
nor
PHASE SELECT SLG
PHASE SELECT VOID
OPEN POLE OP
setting (in the Trip Output element) once the disturbance detector (50DD) initially
Figure 9-11: Phase selector logic
PHASE SELECT VOID
BG, or
operands is active
PHASE SELECT CG
operands are being asserted
FlexLogic operand is asserted or after delay
SINGLE-POLE TRIPPING
operand is
9-27
9