GROUPED ELEMENTS
COMPENSATED OV STG1 PKP
for each of the three stages. If any stage is set with no intentional time delay, then set the pickup setting 15% above the
anticipated steady state overvoltage to prevent an operation during line energization. A stage that is not used can be set
to its maximum setting value (3.000 pu) to effectively disable it.
COMPENSATED OV STG1 DELAY
delay for each of the three stages in seconds.
5

5.7.14 Sensitive directional power

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  POWER  SENSITIVE DIRECTIONAL POWER 
DIRECTIONAL POWER 1(2)
 DIRECTIONAL
 POWER 1
5-300
,
,
COMPENSATED OV STG2 PKP
COMPENSATED OV STG3 PKP
,
COMPENSATED OV STG2 DELAY
Figure 5-173: Compensated overvoltage logic
DIR POWER 1
FUNCTION: Disabled
DIR POWER 1
SOURCE: SRC 1
DIR POWER 1
RCA: 0°
DIR POWER 1
CALIBRATION: 0.00°
DIR POWER 1 STG1
SMIN: 0.100 pu
DIR POWER 1 STG1
DELAY: 0.50 s
DIR POWER 1 STG2
SMIN: 0.100 pu
DIR POWER 1 STG2
DELAY: 20.00 s
— These settings specify the pickup level
,
COMPENSATED OV STG3 DELAY
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0 to 359° in steps of 1
Range: 0 to 0.95° in steps of 0.05
Range: –1.200 to 1.200 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: –1.200 to 1.200 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
— These settings specify the time