GE D60 Instruction Manual page 470

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

GROUPED ELEMENTS
— Specifies a multiple of the base curve shape specified by the
TD MULTIPLIER
zero results in an instantaneous response to all current levels above pickup.
— The "Instantaneous" reset method is intended for applications with other relays, such as most static relays, which
RESET
set the energy capacity directly to zero when the current falls below the reset threshold. The "Timed" reset method can be
used where the relay must coordinate with electromechanical relays.
VOLTAGE RESTRAINT
— Assertion of the operand assigned to this setting blocks phase A of the phase time overcurrent element.
BLOCK A
— Enables and disables the logging of phase time overcurrent events in the sequence of events recorder.
EVENTS
5
5.7.7.4 Phase instantaneous overcurrent (ANSI 50P, IEC PIOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE IOC 1(12)
 PHASE IOC 1
5-256
— Enables and disables the phase time overcurrent voltage restraint feature.
Figure 5-142: Phase time overcurrent 1 logic
PHASE IOC1
FUNCTION: Disabled
PHASE IOC1 SIGNAL
SOURCE: SRC 1
PHASE IOC1
PICKUP: 1.000 pu
PHASE IOC1 PICKUP
DELAY: 0.00 s
PHASE IOC1 RESET
DELAY: 0.00 s
setting. Programming this value to
CURVE
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.005 to 30.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL