GE T60 Instruction Manual

GE T60 Instruction Manual

Ur series transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

Quick Links

GE
Grid Solutions
GE Grid Solutions
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEGridSolutions.com
*1601-0090-AA5*
T60 Transformer Protection System
UR Series Instruction Manual
Manual P/N: 1601-0090-AA5 (GEK-119568D)
IND.CONT. EQ.
T60 Revision: 7.2x
828743A2.CDR
E83849
LISTED
52TL
GE Multilin's Quality Management
System is registered to ISO
9001:2008
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading

Summary of Contents for GE T60

  • Page 1 Grid Solutions T60 Transformer Protection System UR Series Instruction Manual T60 Revision: 7.2x Manual P/N: 1601-0090-AA5 (GEK-119568D) 828743A2.CDR E83849 GE Grid Solutions LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1 System is registered to ISO...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3 ADDENDUM This addendum outlines items not included in the instruction manual for the T60. PHASE DISTANCE FAULT TYPE CHARACTERISTICS Phase distance fault type characteristics were slightly changed between minor version 7.21 and 7.24 firmware releases to allow phase distance operation during some unusual cases, where spurious I_0 can be present during fault. This adden- dum explains the difference in the firmware implementation for the following minor releases.
  • Page 4 ADDENDUM SLG= (VA_LOW & NOT VB_LOW & NOT VC_LOW) OR (NOT VA_LOW & VB_LOW & NOT VC_LOW) OR (NOT VA_LOW & NOT VB_LOW & VC_LOW) where √ VA_LOW = |V_A + V_0| < 0.98 *VBC/ 3, similarly for B and C phases Additionally multi-phase fault is determined if at least 2 phases are below 85% of the nominal: M-PH= (VA <...
  • Page 5 ADDENDUM Table 0–1: DIRECTIONAL MHO PHASE DISTANCE FUNCTIONS CHARACTERISTIC COMPARATOR INPUTS LIMIT ANGLE Variable mho I × Z – V V_1M COMP LIMIT I × Z – V I × Z Reactance COMP LIMIT I × Z Directional V_1M DIR COMP LIMIT Fault type NOT SLG Removed during open pole conditions...
  • Page 6 TABLE OF CONTENTS T60 Transformer Protection System GE Multilin...
  • Page 7: Table Of Contents

    1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 SYSTEM REQUIREMENTS ................1-5 1.3.2 INSTALLATION....................1-5 1.3.3 CONFIGURING THE T60 FOR SOFTWARE ACCESS ........1-6 1.3.4 USING THE QUICK CONNECT FEATURE............1-9 1.3.5 CONNECTING TO THE T60 RELAY ............... 1-14 1.3.6 SETTING UP CYBERSENTRY AND CHANGING DEFAULT PASSWORD ... 1-15 1.4 UR HARDWARE...
  • Page 8 REAL TIME CLOCK ..................5-66 5.2.7 USER-PROGRAMMABLE FAULT REPORT............5-71 5.2.8 OSCILLOGRAPHY ...................5-72 5.2.9 DATA LOGGER ....................5-75 5.2.10 DEMAND ......................5-76 5.2.11 USER-PROGRAMMABLE LEDS ..............5-77 5.2.12 USER-PROGRAMMABLE SELF TESTS ............5-81 5.2.13 CONTROL PUSHBUTTONS ................5-81 5.2.14 USER-PROGRAMMABLE PUSHBUTTONS............5-84 viii T60 Transformer Protection System GE Multilin...
  • Page 9 REMOTE DOUBLE-POINT STATUS INPUTS ..........5-319 5.8.8 REMOTE OUTPUTS..................5-320 5.8.9 RESETTING....................5-320 5.8.10 DIRECT INPUTS AND OUTPUTS ..............5-321 5.8.11 TELEPROTECTION INPUTS AND OUTPUTS..........5-324 5.8.12 IEC 61850 GOOSE ANALOGS..............5-326 5.8.13 IEC 61850 GOOSE INTEGERS..............5-327 GE Multilin T60 Transformer Protection System...
  • Page 10 USER-PROGRAMMABLE FAULT REPORTS ..........6-28 6.4.2 EVENT RECORDS ...................6-28 6.4.3 OSCILLOGRAPHY ...................6-28 6.4.4 DATA LOGGER ....................6-29 6.4.5 PHASOR MEASUREMENT UNIT RECORDS ..........6-29 6.4.6 BREAKER MAINTENANCE ................6-30 6.5 PRODUCT INFORMATION 6.5.1 MODEL INFORMATION ...................6-31 6.5.2 FIRMWARE REVISIONS..................6-31 T60 Transformer Protection System GE Multilin...
  • Page 11 DISPOSE OF BATTERY.................. 10-5 10.3 UNINSTALL AND CLEAR FILES AND DATA 10.3.1 UNINSTALL AND CLEAR FILES AND DATA..........10-8 10.4 REPAIRS 10.4.1 REPAIRS ......................10-9 10.5 STORAGE 10.5.1 STORAGE...................... 10-10 10.6 DISPOSAL 10.6.1 DISPOSAL ..................... 10-11 GE Multilin T60 Transformer Protection System...
  • Page 12 C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP C.5.1 OVERVIEW ..................... C-12 C.5.2 CONFIGURING IEC 61850 SETTINGS ............C-13 C.5.3 ABOUT ICD FILES ..................C-14 C.5.4 CREATING AN ICD FILE WITH ENERVISTA UR SETUP......C-18 T60 Transformer Protection System GE Multilin...
  • Page 13 G.1 RADIUS SERVER CONFIGURATION G.1.1 RADIUS SERVER CONFIGURATION.............. G-1 H. MISCELLANEOUS H.1 CHANGE NOTES H.1.1 REVISION HISTORY ..................H-1 H.1.2 CHANGES TO THE T60 MANUAL ..............H-2 H.2 ABBREVIATIONS H.2.1 STANDARD ABBREVIATIONS .................H-7 H.3 WARRANTY H.3.1 GE MULTILIN WARRANTY ................H-10 INDEX GE Multilin...
  • Page 14 TABLE OF CONTENTS T60 Transformer Protection System GE Multilin...
  • Page 15: Getting Started

    1.1 IMPORTANT PROCEDURES 1 GETTING STARTED 1.1IMPORTANT PROCEDURES Use this chapter for initial setup of your new T60 Transformer Protection System. 1.1.1 CAUTIONS AND WARNINGS Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime.
  • Page 16: Inspection Procedure

    • GE EnerVista™ DVD (includes the EnerVista UR Setup software and manuals in PDF format) • Mounting screws If there is any noticeable physical damage, or any of the contents listed are missing, contact GE Grid Solutions as fol- lows.
  • Page 17: Ur Overview

    1.2UR OVERVIEW 1.2.1 INTRODUCTION TO THE UR The GE Universal Relay (UR) series is a new generation of digital, modular, and multifunction equipment that is easily incorporated into automation systems, at both the station and enterprise levels. 1.2.2 HARDWARE ARCHITECTURE...
  • Page 18: Software Architecture

    Employing OOD/OOP in the software architecture of the T60 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functional classes.
  • Page 19: Enervista Ur Setup Software

    Ethernet port of the same type as one of the UR CPU ports or a LAN connection to the UR • Internet access or a DVD drive The following qualified modems have been tested to be compatible with the T60 and the EnerVista UR Setup software: • US Robotics external 56K FaxModem 5686 •...
  • Page 20: Configuring The T60 For Software Access

    To configure the T60 for remote access via the rear Ethernet port, see the Configuring Ethernet Communications sec- tion. • To configure the T60 for local access with a computer through either the front RS232 port or rear Ethernet port, see the Using the Quick Connect Feature section. T60 Transformer Protection System...
  • Page 21 CONFIGURING SERIAL COMMUNICATIONS A computer with an RS232 port and a serial cable is required. To use the RS485 port at the back of the relay, a GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
  • Page 22 MODBUS PROTOCOL 21. Click the Read Order Code button to connect to the T60 device and upload the order code. If an communications error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting values.
  • Page 23: Using The Quick Connect Feature

    USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the T60 from a computer through Ethernet, first assign an IP address to the relay from the front panel keyboard. Press the MENU key until the SETTINGS menu displays.
  • Page 24 Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button. Click the “Use the following IP address” box. 1-10 T60 Transformer Protection System GE Multilin...
  • Page 25 1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE Enter an IP address with the first three numbers the same as the IP address of the T60 relay and the last number dif- ferent (in this example, 1.1.1.2). Enter a subnet mask equal to the one set in the T60 (in this example, 255.0.0.0).
  • Page 26 Ensure that the “Use a proxy server for your LAN” box is not checked. If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been discon- nected from the T60 relay. Start the Internet Explorer software.
  • Page 27 Click the Quick Connect button to open the Quick Connect dialog box. Select the Ethernet interface and enter the IP address assigned to the T60, then click the Connect button. The EnerV- ista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Con- nect”...
  • Page 28: Connecting To The T60 Relay

    The EnerVista UR Setup software has several quick action buttons to provide instant access to several functions that are often performed when using T60 relays. From the online window, users can select the relay to interrogate from a pull-down window, then click the button for the action they want to perform. The following quick action functions are available: •...
  • Page 29: Setting Up Cybersentry And Changing Default Password

    If using EnerVista, navigate to Settings > Product Setup > Security. Change the Local Administrator Password, for example. It is strongly recommended that the password for the Administrator be changed from the default. Changing the passwords for the other three roles is optional. GE Multilin T60 Transformer Protection System 1-15...
  • Page 30: Ur Hardware

    This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the T60 rear communications port. The converter terminals (+, –, GND) are connected to the T60 communication module (+, –, COM) terminals. See the CPU Communica- tion Ports section in chapter 3 for details.
  • Page 31: Using The Relay

    MESSAGE LEFT key from a setting value or actual value display returns to the header display. HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE)  SETTINGS  SECURITY ACCESS LEVEL:  PRODUCT SETUP  Restricted  SETTINGS  SYSTEM SETUP GE Multilin T60 Transformer Protection System 1-17...
  • Page 32: Relay Activation

    For more information, see the CyberSentry content in the Security section of the next chapter. 1.5.6 FLEXLOGIC CUSTOMIZATION FlexLogic equation editing is required for setting user-defined logic for customizing the relay operations. See the FlexLogic section in Chapter 5. 1-18 T60 Transformer Protection System GE Multilin...
  • Page 33: Commissioning

    The T60 performs a number of continual self-tests and takes the necessary action in case of any major errors (see the Relay Self-tests section in chapter 7). However, it is recommended that T60 maintenance be scheduled with other system maintenance.
  • Page 34 1.5 USING THE RELAY 1 GETTING STARTED 1-20 T60 Transformer Protection System GE Multilin...
  • Page 35: Product Description

    Ethernet port supports IEC 61850, IEC 61850-90-5, Modbus/TCP, and TFTP protocols, PTP (according to IEEE Std. 1588- 2008 or IEC 61588), and allows access to the relay via any standard web browser (T60 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when purchased as an option.
  • Page 36 2.1 INTRODUCTION 2 PRODUCT DESCRIPTION Table 2–1: ANSI DEVICE NUMBERS AND FUNCTIONS DEVICE FUNCTION DEVICE FUNCTION NUMBER NUMBER Phase instantaneous overcurrent 87RGF Restricted ground fault Ground time overcurrent Transformer differential Neutral time overcurrent T60 Transformer Protection System GE Multilin...
  • Page 37 2 PRODUCT DESCRIPTION 2.1 INTRODUCTION Figure 2–1: SINGLE LINE DIAGRAM GE Multilin T60 Transformer Protection System...
  • Page 38: Security

    Two levels of password security are provided: command and setting. The following operations are under command password supervision: • Changing the state of virtual inputs • Clearing the event records • Clearing the oscillography records • Changing the date and time T60 Transformer Protection System GE Multilin...
  • Page 39 When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the T60, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password applies.
  • Page 40 User programmable |--------------- Pushbuttons |--------------- Flex states User definable dis- |--------------- plays |--------------- Direct I/O |--------------- Tele-protection |--------------- Installation |------------ System Setup |------------ FlexLogic |------------ Grouped Elements |------------ Control Elements |------------ Inputs / Outputs T60 Transformer Protection System GE Multilin...
  • Page 41 |------------ Transducer I/O |------------ Records |------------ Product Info Maintenance |------------ Modbus Analyzer |------------ Change Front Panel |------------ Update Firmware |------------ Retrieve File Table Notes: RW = read and write access R = read access GE Multilin T60 Transformer Protection System...
  • Page 42: Iec 870-5-103 Protocol

    103 communication messages. The UR implementation of IEC 60870-5-103 consists of the following functions: • Report binary inputs • Report analog values (measurands) • Commands • Time synchronization The RS485 port supports IEC 60870-5-103. T60 Transformer Protection System GE Multilin...
  • Page 43: Order Codes

    2.2ORDER CODES 2.2.1 OVERVIEW The T60 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod- ules: power supply, CPU, CT/VT, contact input and output, transducer input and output, and inter-relay communications.
  • Page 44 2.2 ORDER CODES 2 PRODUCT DESCRIPTION Table 2–4: T60 ORDER CODES (HORIZONTAL UNITS) * - F - W/X Full Size Horizontal Mount BASE UNIT Base Unit IEEE 1588, PRP, IEC 61850, and Synchrocheck IEEE 1588, PRP, and six windings IEEE 1588, PRP, six windings, and Ethernet Global Data...
  • Page 45 RS422, 1 Channel RS422, 2 Channels The order codes for the reduced size vertical mount units are shown below. Table 2–5: T60 ORDER CODES (REDUCED SIZE VERTICAL UNITS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below)
  • Page 46 2.2 ORDER CODES 2 PRODUCT DESCRIPTION Table 2–5: T60 ORDER CODES (REDUCED SIZE VERTICAL UNITS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below) IEEE 1588 and Phasor Measurement Unit (PMU) and synchrocheck IEEE 1588 and IEC 61850 and Phasor Measurement Unit (PMU) and synchrocheck...
  • Page 47: Order Codes With Process Bus Modules

    RS422, 2 Channels 2.2.3 ORDER CODES WITH PROCESS BUS MODULES The order codes for the horizontal mount units with the process bus module are shown below. Table 2–6: T60 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS) * - F - W/X...
  • Page 48 2.2 ORDER CODES 2 PRODUCT DESCRIPTION Table 2–6: T60 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS) * - F - W/X Full Size Horizontal Mount BASE UNIT Base Unit CyberSentry Lvl 1 and IEC 61850 and Phasor Measurement Unit (PMU)
  • Page 49 RS422, 2 Channels The order codes for the reduced size vertical mount units with the process bus module are shown below. Table 2–7: T60 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below)
  • Page 50 2.2 ORDER CODES 2 PRODUCT DESCRIPTION Table 2–7: T60 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below) Phasor Measurement Unit (PMU) and synchrocheck Phasor Measurement Unit (PMU), IEC 61850 protocol, and synchrocheck...
  • Page 51 2 PRODUCT DESCRIPTION 2.2 ORDER CODES Table 2–7: T60 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below) IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + EGD...
  • Page 52: Replacement Modules

    Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the serial number of your existing unit. Not all replacement modules may be applicable to the T60 relay. Only the modules specified in the order codes are available as replacement modules.
  • Page 53 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed) 4 DCmA inputs, 4 RTD inputs 8 DCmA inputs GE Multilin T60 Transformer Protection System 2-19...
  • Page 54: Signal Processing

    The sampling rate is dynamically adjusted to the actual system frequency by an accurate and fast frequency tracking system. The A/D converter has the following ranges of AC signals: Voltages: ± ⋅ 260 V (EQ 2.1) Currents: 2-20 T60 Transformer Protection System GE Multilin...
  • Page 55 Other advanced UR order code options are available to support IEC 61850 Ed2.0 (including fast GOOSE, MMS server, 61850 services, ICD/CID/IID files, and so on), IEEE 1588 (IEEE C37.238 power profile) based time synchronization, Cyber- Sentry (advanced cyber security), the Parallel Redundancy Protocol (PRP), IEC 60870-5-103, and so on. GE Multilin T60 Transformer Protection System 2-21...
  • Page 56: Specifications

    CT location: all delta-wye and wye-delta transformers Voltage supervision pickup (series compensation applications): 0 to 5.000 pu in steps of 0.001 Operation time: 1 to 1.5 cycles (typical) Reset time: 1 power cycle (typical) 2-22 T60 Transformer Protection System GE Multilin...
  • Page 57 IEEE Moderately/Very/Extremely Limit angle: 30 to 90° in steps of 1 Inverse; IEC (and BS) A/B/C and Short Zero-sequence compensation Inverse; GE IAC Inverse, Short/Very/ Z0/Z1 magnitude: 0.00 to 10.00 in steps of 0.01 Extremely Inverse; I t; FlexCurves™ Z0/Z1 angle: –90 to 90°...
  • Page 58 ±0.5% of reading from 10 to 208 V seq.: phase A (V ), phase B (V Curve shapes: GE IAV Inverse, Definite Time phase C (V Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01 Polarizing voltage threshold: 0.000 to 3.000 pu in steps of 0.001 Curve timing accuracy Current sensitivity threshold: 0.05 pu...
  • Page 59 (whichever is greater) 95% settling time for df/dt: <24 cycles typically 9.5 cycles at 2 × pickup Operate time: typically 8.5 cycles at 3 × pickup typically 6.5 cycles at 5 × pickup GE Multilin T60 Transformer Protection System 2-25...
  • Page 60: User-Programmable Elements

    Type: set-dominant or reset-dominant Time delay: 0 to 65535 ms in steps of 1 Number: 16 (individually programmed) Output: stored in non-volatile memory Execution sequence: as input prior to protection, control, and FlexLogic 2-26 T60 Transformer Protection System GE Multilin...
  • Page 61: Monitoring

    16 channels for NN days output change of state; self-test events ↓ Data storage: in non-volatile memory 60-minute rate: 01 channel for NN days 16 channels for NN days GE Multilin T60 Transformer Protection System 2-27...
  • Page 62: Metering

    Parameters: three-phase only DEMAND Update rate: 50 ms Measurements: Phases A, B, and C present and maxi- mum measured currents 3-Phase Power (P, Q, and S) present and maximum measured currents Accuracy: ±2.0% 2-28 T60 Transformer Protection System GE Multilin...
  • Page 63: Inputs

    1 to 1000 in steps of 1 Unreturned message alarm: Responding to: Rate of unreturned messages in the ring configuration Monitoring message count: 10 to 10000 in steps of 1 Alarm threshold: 1 to 1000 in steps of 1 GE Multilin T60 Transformer Protection System 2-29...
  • Page 64: Power Supply

    24 V 48 V 1.6 A 125 V 0.4 A 250 V 0.2 A Operate time: < 4 ms Contact material: silver alloy Control: separate operate and reset inputs Control mode: operate-dominant or reset-dominant 2-30 T60 Transformer Protection System GE Multilin...
  • Page 65 L/R = 10 ms (0 to 250 V 1.6 A 10 A 10 A L/R = 20 ms L/R = 40 ms L/R = 40 ms 0.8 A L/R = 40 ms GE Multilin T60 Transformer Protection System 2-31...
  • Page 66: Communication Protocols

    1200 m G.703 100 m RS422 distance is based on transmitter power and does not take into consideration the clock source NOTE provided by the user. LINK POWER BUDGET AND MAXIMUM OPTICAL INPUT POWER 2-32 T60 Transformer Protection System GE Multilin...
  • Page 67 1300 nm ELED, 9/125 μm 11.4 km 20 km single mode 1300 nm Laser, 9/125 μm 64 km 65 km single mode 1550 nm Laser, 9/125 μm 105 km 125 km single mode GE Multilin T60 Transformer Protection System 2-33...
  • Page 68: Environmental

    – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Noise: 0 dB Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days). 2-34 T60 Transformer Protection System GE Multilin...
  • Page 69: Type Tests

    NKCR Safety IEC 60255-27 Insulation: class 1, Pollution degree: 2, Over voltage cat II 2.4.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. GE Multilin T60 Transformer Protection System 2-35...
  • Page 70: Approvals

    Normally, cleaning is not required; but for situations where dust has accumulated on the faceplate display, a dry cloth can be used. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. 2-36 T60 Transformer Protection System GE Multilin...
  • Page 71: Hardware

    HORIZONTAL UNITS The T60 Transformer Protection System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 72 VERTICAL UNITS The T60 Transformer Protection System is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 73 3 HARDWARE 3.1 DESCRIPTION Figure 3–4: T60 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin T60 Transformer Protection System...
  • Page 74 3.1 DESCRIPTION 3 HARDWARE Figure 3–5: T60 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For side mounting T60 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Grid Solutions website: • GEK-113180: UR-Series UR-V Side-Mounting Front Panel Assembly Instructions •...
  • Page 75 3 HARDWARE 3.1 DESCRIPTION Figure 3–6: T60 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin T60 Transformer Protection System...
  • Page 76 3.1 DESCRIPTION 3 HARDWARE Figure 3–7: T60 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL) T60 Transformer Protection System GE Multilin...
  • Page 77: Rear Terminal Layout

    (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments. Figure 3–9: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin T60 Transformer Protection System...
  • Page 78 (rows 1 to 8), use a minimum of 17 inch-pounds. During manufacturing, the power supply and CPU modules are installed in slots B and D of the chassis with 13 inch-pounds of torque on the screws at the top and bottom of the modules. T60 Transformer Protection System GE Multilin...
  • Page 79: Wiring

    3 HARDWARE 3.2 WIRING 3.2WIRING 3.2.1 TYPICAL WIRING Figure 3–10: TYPICAL WIRING DIAGRAM (T MODULE SHOWN FOR CPU) GE Multilin T60 Transformer Protection System...
  • Page 80: Dielectric Strength

    (see the Self-test Errors section in chapter 7) or control power is lost, the relay is de-energize. For high reliability systems, the T60 has a redundant option in which two T60 power supplies are placed in parallel on the bus.
  • Page 81: Ct/Vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown as follows. Twisted-pair cabling on the zero-sequence CT is recommended. GE Multilin T60 Transformer Protection System 3-11...
  • Page 82 Substitute the tilde “~” symbol with the slot position of the module in the following figure. NOTE Current inputs Voltage inputs 8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs) Current inputs 8H, 8J, 8N, and 8R modules (8 CTs) 842766A3.CDR Figure 3–13: CT/VT MODULE WIRING 3-12 T60 Transformer Protection System GE Multilin...
  • Page 83: Process Bus Modules

    3.2.5 PROCESS BUS MODULES The T60 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bidirectional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
  • Page 84 Logic operand driving the contact output should be given a reset delay of 10 ms to prevent damage of the output contact (in situations when the element initiating the contact output is bouncing, at val- ues in the region of the pickup value). 3-14 T60 Transformer Protection System GE Multilin...
  • Page 85 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs GE Multilin T60 Transformer Protection System 3-15...
  • Page 86 Not Used ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used 3-16 T60 Transformer Protection System GE Multilin...
  • Page 87 3 HARDWARE 3.2 WIRING Figure 3–15: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) GE Multilin T60 Transformer Protection System 3-17...
  • Page 88 3.2 WIRING 3 HARDWARE Figure 3–16: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output con- nections. 3-18 T60 Transformer Protection System GE Multilin...
  • Page 89 T60 input even when the output is open, if there is a substantial distributed capacitance (represented by C1) present in the wiring between the output and the T60 input and the debounce time setting in the T60 relay is low enough.
  • Page 90 This operation of contact inputs also can be prevented by using the Auto-Burnish contact inputs or contact inputs with active impedance. Figure 3–19: CONTACT INPUT CONNECTED TO A CONTACT OUTPUT WITH RESISTOR (R2) ACROSS THE INPUT 3-20 T60 Transformer Protection System GE Multilin...
  • Page 91 (EQ 3.2) The 2 mA current is used in case the contact input is connected across the GE Form A contact output with voltage monitoring. Otherwise use the amperage of the active circuit connected to the contact input when its contact output is open and the voltage across the contact input is third trigger threshold to calculate the resistor value.
  • Page 92 Vresistor < contact input threshold (84 V) (EQ 3.5) In conclusion, in this example, the contact input does NOT operate falsely with the Burden Resistor across its input AND when a battery ground is present. 3-22 T60 Transformer Protection System GE Multilin...
  • Page 93 CONTACT INPUT 2 AUTO-BURNISH = OFF CONTACT INPUT 1 AUTO-BURNISH = OFF CONTACT INPUT 2 AUTO-BURNISH = ON CONTACT INPUT 1 AUTO-BURNISH = ON CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–21: AUTO-BURNISH DIP SWITCHES GE Multilin T60 Transformer Protection System 3-23...
  • Page 94 Contact inputs susceptible to parasitic capacitance caused by long cable runs affected by switching surges from external circuits can result in inadvertent activation of contact inputs with the external contact open. In this case, GE recommends using the digital I/O module with active impedance circuit.
  • Page 95: Transducer Inputs/Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE GE Multilin T60 Transformer Protection System 3-25...
  • Page 96 3.2 WIRING 3 HARDWARE Figure 3–23: TRANSDUCER INPUT/OUTPUT MODULE WIRING The following figure show how to connect RTDs. 3-26 T60 Transformer Protection System GE Multilin...
  • Page 97: Rs232 Faceplate Port

    3.2.8 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the T60 faceplate for programming with a computer. All that is required to use this interface is a computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
  • Page 98: Cpu Communication Ports

    This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the T60 COM terminal (#3); others function cor- rectly only if the common wire is connected to the T60 COM terminal, but insulated from the shield.
  • Page 99 The fiber optic communication ports allow for fast and efficient communications between relays at 100 Mbps. Optical fiber can be connected to the relay supporting a wavelength of 1310 nm in multi-mode. GE Multilin T60 Transformer Protection System 3-29...
  • Page 100: Irig-B

    IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the T60 operates an internal oscillator with 1 µs resolution and accuracy.
  • Page 101: Direct Input/Output Communications

    Loop Timing Mode. If there is no MUX, then UR1 and UR3 can be in Internal Timing Mode and UR2 and UR4 can be in Loop Timing Mode. That is, connected channels must have opposite timing modes. Figure 3–30: RING CONFIGURATION FOR C37.94 MODULE (CONCEPT ALSO APPLIES TO G.703) GE Multilin T60 Transformer Protection System 3-31...
  • Page 102 Those that apply depend on options purchased. The options are outlined in the Inter-Relay Communications section of the Order Code tables in Chapter 2. All of the fiber modules use ST type connectors. 3-32 T60 Transformer Protection System GE Multilin...
  • Page 103: Fiber: Led And Eled Transmitters

    The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules. Figure 3–33: LED AND ELED FIBER MODULES 3.3.3 FIBER-LASER TRANSMITTERS The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser modules. Figure 3–34: 7X LASER FIBER MODULES GE Multilin T60 Transformer Protection System 3-33...
  • Page 104: Interface

    X6a is used to ground the shield at one end, do not ground the shield at the other end. This interface module is protected by surge suppression devices. Figure 3–36: G.703 INTERFACE CONFIGURATION 3-34 T60 Transformer Protection System GE Multilin...
  • Page 105 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. GE Multilin T60 Transformer Protection System 3-35...
  • Page 106 For connection to a higher order system (UR- to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). 3-36 T60 Transformer Protection System GE Multilin...
  • Page 107 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–40: G.703 DUAL LOOPBACK MODE GE Multilin T60 Transformer Protection System 3-37...
  • Page 108: Rs422 Interface

    UR–RS422 channels is synchronized via the send timing leads on data module 1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. 3-38 T60 Transformer Protection System GE Multilin...
  • Page 109 Figure 3–43: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, THREE-TERMINAL APPLICATION Data module 1 provides timing to the T60 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they vary by manufacturer.
  • Page 110: Rs422 And Fiber Interface

    G.703 and fiber interfaces. When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver. Figure 3–46: G.703 AND FIBER INTERFACE CONNECTION 3-40 T60 Transformer Protection System GE Multilin...
  • Page 111: Ieee C37.94 Interface

    5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of T60 communication for two and three terminal applications.
  • Page 112 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. 3-42 T60 Transformer Protection System GE Multilin...
  • Page 113 Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow- ing figure. Figure 3–48: STATUS LEDS The clock configuration LED status is as follows: • Flashing green — loop timing mode while receiving a valid data packet GE Multilin T60 Transformer Protection System 3-43...
  • Page 114: C37.94Sm Interface

    5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of T60 communi- cation for two and three terminal applications.
  • Page 115 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. GE Multilin T60 Transformer Protection System 3-45...
  • Page 116 Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow- ing figure. Figure 3–50: STATUS LEDS The clock configuration LED status is as follows: • Flashing green — loop timing mode while receiving a valid data packet 3-46 T60 Transformer Protection System GE Multilin...
  • Page 117 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid GE Multilin T60 Transformer Protection System 3-47...
  • Page 118 3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS 3 HARDWARE 3-48 T60 Transformer Protection System GE Multilin...
  • Page 119: Human Interfaces

    The EnerVista UR Setup software is provided with every T60 relay and runs on Microsoft Windows XP, 7, and Server 2008. This chapter provides a summary of the basic EnerVista UR Setup software interface features. The EnerVista UR Setup Help File provides details for getting started and using the EnerVista UR Setup software interface.
  • Page 120 Site List window are automatically sent to the online communicating device. g) FIRMWARE UPGRADES The firmware of a T60 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
  • Page 121: Enervista Ur Setup Main Window

    Device data view windows, with common tool bar Settings file data view windows, with common tool bar Workspace area with data view tabs Status bar 10. Quick action hot links 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW GE Multilin T60 Transformer Protection System...
  • Page 122: Extended Enervista Ur Setup Features

    Right-click the device or file and select the Template Mode > Edit Template option to place the device in template editing mode. If prompted, enter the template password then click OK. Open the relevant settings window that contains settings to be specified as viewable. T60 Transformer Protection System GE Multilin...
  • Page 123 ADDING PASSWORD PROTECTION TO A TEMPLATE GE recommends that templates be saved with password protection to maximize security. When templates are created for online settings, the password is added during the initial template creation step. It does not need to be added after the template is created.
  • Page 124 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND T60 Transformer Protection System GE Multilin...
  • Page 125 Once a settings template is removed, it cannot be reapplied and a new settings template needs to be defined before use. Right-click the device in the Online or Offline Window area and select the Template Mode > Remove Template option. Enter the template password and click OK to continue. GE Multilin T60 Transformer Protection System...
  • Page 126: Securing And Locking Flexlogic Equations

    Select the Template Mode > View In Template Mode option to view the template. Optionally apply a password to the template by right-clicking the device and selecting the Template Mode > Pass- word Protect Template option. T60 Transformer Protection System GE Multilin...
  • Page 127 A serial number is viewable under Actual Values > Product Info > Model Information, the inside front panel, and the rear of the device. GE Multilin T60 Transformer Protection System...
  • Page 128: Settings File Traceability

    When a settings file is transferred to a T60 device, the date, time, and serial number of the T60 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the T60 actual values at any later date to determine if security has been compromised.
  • Page 129 With respect to the above diagram, the traceability feature is used as follows. The transfer date of a setting file written to a T60 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 130 ONLINE DEVICE TRACEABILITY INFORMATION The T60 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 131: Faceplate Interface

    The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over the faceplate that must be removed in order to access the keypad panel. The following figure shows the horizontal arrange- ment of the faceplate panels. Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS GE Multilin T60 Transformer Protection System 4-13...
  • Page 132: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. 4-14 T60 Transformer Protection System GE Multilin...
  • Page 133 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack- age of every T60, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
  • Page 134 User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program the operation of the LEDs on these panels. 4-16 T60 Transformer Protection System GE Multilin...
  • Page 135: Custom Labeling Of Leds

    EnerVista UR Setup software is installed and operational • The T60 settings have been saved to a settings file • The T60 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://www.gegridsolutions.com/products/support/ur/URLEDenhanced.doc and printed •...
  • Page 136 Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the T60 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
  • Page 137 4.3 FACEPLATE INTERFACE Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the T60 enhanced front panel and insert the custom labels. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay.
  • Page 138 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the T60 enhanced front panel and insert the custom labels.
  • Page 139 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This attaches the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. GE Multilin T60 Transformer Protection System 4-21...
  • Page 140: Display

    INTRODUCTION The T60 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, that can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic operand.
  • Page 141: Menus

    Press the MENU key to select a header display page (top-level menu). The header title appears momentarily followed by a header display page menu item. Each press of the MENU key advances through the following main heading pages: • Actual values • Settings GE Multilin T60 Transformer Protection System 4-23...
  • Page 142 Pressing the MESSAGE DOWN key displays the second setting sub-header associ-  PROPERTIES ated with the Product Setup header.  Press the MESSAGE RIGHT key once more to display the first setting for Display FLASH MESSAGE Properties. TIME: 1.0 s 4-24 T60 Transformer Protection System GE Multilin...
  • Page 143: Changing Settings

    ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length, but user-defined in character. They can be upper case letters, lower case letters, numerals, and a selection of special characters. GE Multilin T60 Transformer Protection System 4-25...
  • Page 144: Settings

    The information in this section refers to password security. For information on how to set or change CyberSentry pass- words, see the Settings > Product Setup > Security > CyberSentry section in the next chapter. 4-26 T60 Transformer Protection System GE Multilin...
  • Page 145 By default, when an incorrect Command or Setting password has been entered via the faceplate interface three times within three minutes, the FlexLogic operand is set to “On” and the T60 does not allow settings or LOCAL ACCESS DENIED command level access via the faceplate interface for the next five minutes.
  • Page 146 4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4-28 T60 Transformer Protection System GE Multilin...
  • Page 147: Overview

    See page 5–91.   TELEPROTECTION See page 5–99.   INSTALLATION See page 5–100.   SETTINGS  AC INPUTS See page 5–102.  SYSTEM SETUP   POWER SYSTEM See page 5–104.  GE Multilin T60 Transformer Protection System...
  • Page 148  SELECTOR SWITCH See page 5–273.   UNDERFREQUENCY See page 5–279.   OVERFREQUENCY See page 5–280.   FREQUENCY RATE See page 5–281.  OF CHANGE  SYNCHROCHECK See page 5–283.  T60 Transformer Protection System GE Multilin...
  • Page 149  IEC 61850 See page 5-327.  GOOSE UINTEGERS  SETTINGS  DCMA INPUTS See page 5–329.  TRANSDUCER I/O   RTD INPUTS See page 5–330.   RRTD INPUTS See page 5-331.  GE Multilin T60 Transformer Protection System...
  • Page 150: Introduction To Elements

    For example, on a system with a 13.8 kV nominal primary voltage, the base quantity is 13800 V. With 14400:120 V delta- connected VTs, the secondary base quantity and secondary voltage setting is: 13800 --------------- - × 115 V (EQ 5.1) 14400 T60 Transformer Protection System GE Multilin...
  • Page 151: Introduction To Ac Sources

    UR products.) In this application, the current flows as shown by the arrows. Some current flows through the upper bus bar to some other location or power GE Multilin T60 Transformer Protection System...
  • Page 152 “bank,” and all four are either current or voltage, as are channels 5, 6, 7, and 8. Channels 1, 2, 3 and 5, 6, 7 are arranged as phase A, B and C respectively. Channels 4 and 8 are either another current or voltage. T60 Transformer Protection System GE Multilin...
  • Page 153 Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and will display them in the appropriate section in the sequence of the banks (as described above) as follows for a maximum configuration: F1, F5, M1, M5, U1, and U5. GE Multilin T60 Transformer Protection System...
  • Page 154: Product Setup

    To reset the unit after a lost password: Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email account. Customer service provides a code to reset the relay to the factory defaults.
  • Page 155 When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the T60, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 156 INVALID ATTEMPTS BEFORE LOCKOUT The T60 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.
  • Page 157 When this occurs, local access is permitted and the timer pro- grammed with the setting value is started. When this timer expires, local setting access is ACCESS AUTH TIMEOUT GE Multilin T60 Transformer Protection System 5-11...
  • Page 158 It is disabled by default to allow the administrator direct access to the EnerVista software immediately after installation. When security is disabled, all users have administrator access. GE recommends enabling the EnerVista security before placing the device in service.
  • Page 159 Enter a username in the User field. The username must be 4 to 20 characters in length. Select the user access rights by enabling the check box of one or more of the fields. GE Multilin T60 Transformer Protection System 5-13...
  • Page 160 Deletes the user account when exiting the user management window Actual Values Allows the user to read actual values Settings Allows the user to read setting values Commands Allows the user to execute commands 5-14 T60 Transformer Protection System GE Multilin...
  • Page 161 Note that other protocols (DNP, 101, 103, 104, EGD) are not encrypted, and they are good communications options for SCADA systems when CyberSentry is enabled. CYBERSENTRY SETTINGS THROUGH ENERVISTA CyberSentry security settings are configured under Device > Settings > Product Setup > Security. GE Multilin T60 Transformer Protection System 5-15...
  • Page 162 Authentication method used by RADIUS EAP-TTLS EAP-TTLS EAP-TTLS Administrator Authentication server. Currently fixed to EAP-TTLS. Method Timeout Timeout in seconds between re- 9999 Administrator transmission requests Retries Number of retries before giving up 9999 Administrator 5-16 T60 Transformer Protection System GE Multilin...
  • Page 163 See the Change Text The specified role password-protected. All RADIUS users are Password following Me1# and Administrator, password-protected. Requirement password except for s section section for Supervisor, where requireme it is only itself GE Multilin T60 Transformer Protection System 5-17...
  • Page 164 This role can also be disabled, but only through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role. 5-18 T60 Transformer Protection System GE Multilin...
  • Page 165 LOAD FACTORY DEFAULTS: This setting is used to reset all the settings, communication and security passwords. An Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it. GE Multilin T60 Transformer Protection System 5-19...
  • Page 166 Administrator if the Supervisor role is disabled. The Supervisor role enables this setting for the relay to start accepting setting changes or command changes or firmware upgrade. After all the setting changes are applied or com- mands executed, the Supervisor disables to lock setting changes. 5-20 T60 Transformer Protection System GE Multilin...
  • Page 167 Observer). When using a serial connection, only device authentication is supported. When server authentication is required, characteristics for communication with a RADIUS server must be configured. This is possible only in the EnerV- GE Multilin T60 Transformer Protection System 5-21...
  • Page 168 Event Number — Event identification number (index) Date & Timestamp — UTC date and time Username — 255 chars maximum, but in the security log it is truncated to 20 characters IP address — Device IP address 5-22 T60 Transformer Protection System GE Multilin...
  • Page 169 Notice (5) Clear energy command was issued RESET_UNAUTH_ACCESS Warning (4) Reset Unauthorized access command was issued CLEAR_TELEPROTECTION_CNT Notice (5) Clear teleprotection counters command was issued CLEAR_ALL_RECS Warning (4) Clear all records command was issued GE Multilin T60 Transformer Protection System 5-23...
  • Page 170: Display Properties

    Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The T60 applies a cut- off value to the magnitudes and angles of the measured currents.
  • Page 171: Clear Relay Records

    CLEAR EVENT RECORDS: MESSAGE Range: FlexLogic operand CLEAR OSCILLOGRAPHY? MESSAGE Range: FlexLogic operand CLEAR DATA LOGGER: MESSAGE Range: FlexLogic operand CLEAR ARC AMPS 1: MESSAGE Range: FlexLogic operand CLEAR ARC AMPS 2: MESSAGE GE Multilin T60 Transformer Protection System 5-25...
  • Page 172 Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programma- ble pushbuttons to clear specific records are typical applications for these commands. Since the T60 responds to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
  • Page 173: Communications

    SERIAL PORTS The T60 is equipped with up to two independent serial communication ports. The faceplate RS232 port is intended for local use and is fixed at 19200 baud and no parity. The rear COM2 port be used for either RS485 or RRTD communications.
  • Page 174 ETHERNET NETWORK TOPOLOGY The T60 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND oper- ation performed between their respective IP address and mask produces a different result.
  • Page 175 EnerVista, and access to the public network shared on the same LAN. No redundancy is provided. Figure 5–4: NETWORK CONFIGURATION FOR SINGLE LAN Public Network SCADA EnerVista Software LAN1 ML3000 IP1/ MAC1 859708A2.vsd GE Multilin T60 Transformer Protection System 5-29...
  • Page 176 LAN3, to which port 3 (P3) is connected. There is no redundancy. Figure 5–6: MULTIPLE LANS, NO REDUNDANCY Public Network SCADA EnerVista Software LAN1 LAN2 LAN3 ML3000 ML3000 ML3000 IP1/ IP2/ IP3/ MAC2 MAC3 MAC1 859710A2.vsd 5-30 T60 Transformer Protection System GE Multilin...
  • Page 177 IP addresses and mask. Configure the network IP and subnet settings before configuring the rout- ing settings. To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiating information, such as the serial number and order code of your device.
  • Page 178 2 is performed. The delay in switching back ensures that rebooted switching devices connected to the T60, which signal their ports as active prior to being completely functional, have time to completely initialize themselves and become active. Once port 2 is active again, port 3 returns to standby mode.
  • Page 179 The default route is used as the last choice when no other route towards a given destination is found. Range: Standard IPV4 unicast address format  IPV4 DEFAULT ROUTE GATEWAY ADDRESS  127.0.0.1 GE Multilin T60 Transformer Protection System 5-33...
  • Page 180 (RtGwy & Prt1Mask) == (Prt1IP & Prt1Mask) || (RtGwy & Prt2Mask) == (Prt2IP & Prt2Mask) || (RtGwy & Prt3Mask) == (Prt3IP & Prt3Mask) where & is the bitwise-AND operator == is the equality operator || is the logical OR operator 5-34 T60 Transformer Protection System GE Multilin...
  • Page 181 PRT2 IP ADDRESS = 10.1.2.2 PRT2 SUBNET IP MASK = 255.255.255.0 IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1 STATIC NETWORK ROUTE 1: RT1 DESTINATION = 10.1.3.0/24; RT1 NET MASK = 255.255.255.0; and RT1 GATE- WAY = 10.1.2.1 GE Multilin T60 Transformer Protection System 5-35...
  • Page 182 This allows the EnerVista UR Setup software to be used on the port. The UR operates as a Modbus slave device only. When using Modbus protocol on the RS232 port, the T60 responds regardless of the pro- MODBUS SLAVE ADDRESS grammed.
  • Page 183 Modbus, IEC 61850 Channel 2: RS485 Channel 1: RS485 Modbus Modbus, IEC 61850 Channel 2: none IEC 104 Modbus Modbus IEC 104, Modbus, IEC 61850 IEC 103 Modbus IEC 103 Modbus, IEC 61850 GE Multilin T60 Transformer Protection System 5-37...
  • Page 184 DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP OTHER DEFAULT MESSAGE DEADBAND: 30000 Range: 1 to 10080 min. in steps of 1 DNP TIME SYNC IIN MESSAGE PERIOD: 1440 min 5-38 T60 Transformer Protection System GE Multilin...
  • Page 185 PROTOCOL nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the T60 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the T60 at one time.
  • Page 186 DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the T60 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.
  • Page 187 (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP master can operate a single point for both trip and close, or raise and lower, operations. The T60 can be configured to sup- port paired control points, with each paired control point operating two virtual inputs.
  • Page 188 The T60 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over Ethernet. The T60 operates as an IEC 61850 server. The Remote Inputs and Out- puts section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
  • Page 189 IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In T60 releases previous to 5.0x, this name string was repre- sented by the setting.
  • Page 190 DESTINATION MAC address; the least significant bit of the first byte must be set. In T60 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the T60) and setting the multicast bit.
  • Page 191 The T60 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 192 Configure the transmission dataset. Configure the GOOSE service settings. Configure the data. The general steps required for reception configuration are: Configure the reception dataset. Configure the GOOSE service settings. Configure the data. 5-46 T60 Transformer Protection System GE Multilin...
  • Page 193 MMXU1 HZ DEADBAND change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency. The T60 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. Configure the reception dataset by making the following changes in the ...
  • Page 194 IEC61850 GOOSE ANALOG INPUT 1 UNITS The GOOSE analog input 1 can now be used as a FlexAnalog value in a FlexElement or in other settings. The T60 must be rebooted (control power removed and re-applied) before these settings take effect.
  • Page 195 DNA and UserSt bit pairs that are included in GSSE messages. To set up a T60 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and “GGIO3.ST.Ind2.stVal”.
  • Page 196 CPU resources. When server scanning is disabled, there is no updating of the IEC 61850 logical node status values in the T60. Clients are still able to connect to the server (T60 relay), but most data values are not updated. This set- ting does not affect GOOSE/GSSE operation.
  • Page 197 (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard. Changes to the logical node prefixes will not take effect until the T60 is restarted. The main menu for the IEC 61850 MMXU deadbands is shown below.
  • Page 198 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the T60 virtual inputs.
  • Page 199 GGIO1 (binary status values). The settings allow the selection of FlexInteger values for each GGIO5 integer value point. It is intended that clients use GGIO5 to access generic integer values from the T60. Additional settings are provided to allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger values to the GGIO5 integer inputs.
  • Page 200 ITEM 64 attributes supported by the T60. Changes to the dataset will only take effect when the T60 is restarted. It is recommended to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1, GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
  • Page 201 XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation can result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1. GE Multilin T60 Transformer Protection System 5-55...
  • Page 202 Since GSSE/GOOSE messages are multicast Ethernet by specification, they are not usually be forwarded by net- work routers. However, GOOSE messages may be forwarded by routers if the router has been configured for VLAN functionality. NOTE 5-56 T60 Transformer Protection System GE Multilin...
  • Page 203 Menu”. Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the UR and a computer to an Ethernet network, then enter the IP address of the T60 Ethernet port employed into the “Address”...
  • Page 204 PROTOCOL connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the T60 maintains two sets of IEC 60870-5-104 data change buffers, no more than two masters should actively communicate with the T60 at one time.
  • Page 205 MESSAGE 0.0.0.0 The T60 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to which the T60 can connect. A maximum of two simultaneous connections are supported at any given time.
  • Page 206 MESSAGE (Modbus register address range) Fast exchanges (50 to 1000 ms) are generally used in control schemes. The T60 has one fast exchange (exchange 1) and two slow exchanges (exchange 2 and 3). The settings menu for the slow EGD exchanges is shown below: ...
  • Page 207 SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs and none of IRIG-B, PTP, or SNTP is active, the T60 sets the invalid bit in the time stamp of a time-tagged message.
  • Page 208 Spontaneous transmission occurs as a response to cyclic Class 2 requests. If the T60 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the con- trol field of the response).
  • Page 209 ASDU 4 ANALOG 9 MESSAGE Range: 0.000 to 65.535 in steps of 0.001 ASDU 4 ANALOG 9 MESSAGE FACTOR: 1.000 Range: -32768 to 32767 in steps of 1 ASDU 4 ANALOG 9 MESSAGE OFFSET: 0 GE Multilin T60 Transformer Protection System 5-63...
  • Page 210 FlexAnalog operands. The measurands sent are voltage, current, power, power fac- tor, and frequency. If any other FlexAnalog is chosen, the T60 sends 0 instead of its value. Note that the power is transmit- ted in KW, not W.
  • Page 211 ASDU command comes. A list of available mappings is provided on the T60. This includes 64 virtual inputs (see the following table). The ON and OFF for the same ASDU command can be mapped to different virtual inputs.
  • Page 212: Modbus User Map

    Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchroniz- ing time delivered to the relay. While the RTC is not synchronized via PTP or IRIG-B, or the relay determines than it has an 5-66 T60 Transformer Protection System GE Multilin...
  • Page 213  PROTOCOL (1588) Disabled Range: 0 to 255 PTP DOMAIN NUMBER MESSAGE Range: 0 to 7 PTP VLAN PRIORITY MESSAGE Range: 0 to 4095 PTP VLAN ID MESSAGE  PTP PORT 1 MESSAGE  GE Multilin T60 Transformer Protection System 5-67...
  • Page 214 Should a clock on starting up discover it is “better” that the present grandmaster, it assumes the grandmaster role and the previous grandmaster reverts to slave. The T60 qualification mechanism accepts a potential mas- ter clock as a new grandmaster, when in a four-second interval it has received three announce messages from it, all better than the present grandmaster clock and better than any other announce in this interval.
  • Page 215 Ethernet switch it is connected to is 9 000 ns and the that the delay from the switch to the relay is 11 000 ns, then the mean delay is 10 000 ns, and the path delay asymmetry is 11000 - 10000 = +1000 ns. GE Multilin T60 Transformer Protection System 5-69...
  • Page 216 T60 clock is closely synchronized with the SNTP/NTP server. It takes up to two minutes for the T60 to signal an SNTP self-test error if the server is offline.
  • Page 217: User-Programmable Fault Report

    The user programmable record contains the following information: the user-programmed relay name, detailed firmware revision (7.2x, for example) and relay model (T60), the date and time of trigger, the name of pre-fault trigger (a specific FlexLogic operand), the name of fault trigger (a specific FlexLogic operand), the active setting group at pre-fault trigger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger), and fault values of all programmed analog channels (at the fault trigger).
  • Page 218: Oscillography

    ACTUAL VALUES  menu to view the number of cycles captured per record. The following table provides sam- RECORDS OSCILLOGRAPHY ple configurations with corresponding cycles/record. The minimum number of oscillographic records is three. 5-72 T60 Transformer Protection System GE Multilin...
  • Page 219 FlexLogic operand state recorded in an oscillography trace. The length of each DIGITAL 1(63) CHANNEL oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. Upon startup, the relay will automatically prepare the parameter list. GE Multilin T60 Transformer Protection System 5-73...
  • Page 220 2nd to 25th harmonics in the relay as follows: NOTE Analog channel 0 ↔ 2nd harmonic Analog channel 1 ↔ 3rd harmonic Analog channel 23 ↔ 25th harmonic 5-74 T60 Transformer Protection System GE Multilin...
  • Page 221: Data Logger

    490920 s 436380 s 254460 s 3600000 ms 2727.5 235645200 s 340.9 29455200 s 26182800 s Changing any setting affecting data logger operation will clear any data that is currently in the log. NOTE GE Multilin T60 Transformer Protection System 5-75...
  • Page 222: Demand

    D 1 e (EQ 5.6) – where: d = demand value after applying input quantity for time t (in minutes) D = input quantity (constant), and k = 2.3 / thermal 90% response time. 5-76 T60 Transformer Protection System GE Multilin...
  • Page 223: User-Programmable Leds

    See below  LEDS   TRIP & ALARM MESSAGE See page 5–80.  LEDS  USER-PROGRAMMABLE MESSAGE See page 5–80.  LED1  USER-PROGRAMMABLE MESSAGE  LED2 ↓  USER-PROGRAMMABLE MESSAGE  LED48 GE Multilin T60 Transformer Protection System 5-77...
  • Page 224 The test responds to the position and rising edges of the control input defined by the set- LED TEST CONTROL ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed. 5-78 T60 Transformer Protection System GE Multilin...
  • Page 225 2. Once stage 2 has started, the pushbutton can be released. When stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton. GE Multilin T60 Transformer Protection System 5-79...
  • Page 226 LED 19 operand LED 8 operand LED 20 operand LED 9 operand LED 21 operand LED 10 operand LED 22 operand LED 11 operand LED 23 operand LED 12 operand LED 24 operand 5-80 T60 Transformer Protection System GE Multilin...
  • Page 227: User-Programmable Self Tests

    There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front panels. These are user-programmable and can be used for various applications such as performing an LED test, switching setting groups, and invoking and scrolling though user-programmable displays. GE Multilin T60 Transformer Protection System 5-81...
  • Page 228 The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–11: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the T60 is ordered with the 12 user-pro- grammable pushbutton option. STATUS EVENT CAUSE...
  • Page 229 SYSTEM SETUP/ BREAKERS/BREAKER 1/ BREAKER 1 PUSHBUTTON CONTROL Enabled=1 TIMER FLEXLOGIC OPERAND SYSTEM SETUP/ BREAKERS/BREAKER 2/ CONTROL PUSHBTN 1 ON 100 msec BREAKER 2 PUSHBUTTON CONTROL 842010A2.CDR Enabled=1 Figure 5–13: CONTROL PUSHBUTTON LOGIC GE Multilin T60 Transformer Protection System 5-83...
  • Page 230 MESSAGE EVENTS: Disabled The T60 is provided with this optional feature, specified as an option at the time of ordering. Using the order code for your device, see the order codes in chapter 2 for details. User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The number depends on the front panel ordered.
  • Page 231: User-Programmable Pushbuttons

    FlexLogic, the pulse duration is specified by the only. The time the operand remains PUSHBTN 1 DROP-OUT TIME assigned to the setting remains On has no effect on the pulse duration. PUSHBTN 1 SET GE Multilin T60 Transformer Protection System 5-85...
  • Page 232 PUSHBTN 1 LED CTL: This setting assigns the FlexLogic operand serving to drive the front panel pushbutton LED. If this setting is “Off”, then LED operation is directly linked to the operand. PUSHBUTTON 1 ON 5-86 T60 Transformer Protection System GE Multilin...
  • Page 233 PUSHBUTTON 1 EVENTS: If this setting is enabled, each user-programmable pushbutton state change is logged as an event into the event recorder. The figures show the user-programmable pushbutton logic. Figure 5–16: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) GE Multilin T60 Transformer Protection System 5-87...
  • Page 234: Flex State Parameters

    PATH: SETTINGS PRODUCT SETUP FLEX STATE PARAMETERS Range: FlexLogic operand  FLEX STATE PARAMETER  PARAMETERS Range: FlexLogic operand PARAMETER MESSAGE Range: FlexLogic operand PARAMETER MESSAGE ↓ Range: FlexLogic operand PARAMETER 256: MESSAGE 5-88 T60 Transformer Protection System GE Multilin...
  • Page 235: User-Definable Displays

    INVOKE AND SCROLL play, not at the first user-defined display. The pulses must last for at least 250 ms to take effect. INVOKE AND SCROLL GE Multilin T60 Transformer Protection System 5-89...
  • Page 236 While viewing a user display, press the ENTER key and then select the ‘Yes” option to remove the display from the user display list. Use the MENU key again to exit the user displays menu. 5-90 T60 Transformer Protection System GE Multilin...
  • Page 237: Direct Inputs And Outputs

    See page 5–97.   CRC ALARM CH2 MESSAGE See page 5–97.   UNRETURNED MESSAGE See page 5–98.  MESSAGES ALARM CH1  UNRETURNED MESSAGE See page 5–98.  MESSAGES ALARM CH2 GE Multilin T60 Transformer Protection System 5-91...
  • Page 238 Delivery time for direct input and output messages is approximately 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’. 5-92 T60 Transformer Protection System GE Multilin...
  • Page 239 The following application examples illustrate the basic concepts for direct input and output configuration. See the Inputs and Outputs section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged. GE Multilin T60 Transformer Protection System 5-93...
  • Page 240 UR IED 1 BLOCK UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–19: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application. 5-94 T60 Transformer Protection System GE Multilin...
  • Page 241 The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. GE Multilin T60 Transformer Protection System 5-95...
  • Page 242 Inputs and Outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This is accomplished using a dual-ring configuration as shown here. 5-96 T60 Transformer Protection System GE Multilin...
  • Page 243 EVENTS: Disabled The T60 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
  • Page 244 MESSAGE EVENTS: Disabled The T60 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre- turned messages.
  • Page 245: Teleprotection

    On two- terminals two-channel systems, the same is transmitted over LOCAL RELAY ID NUMBER both channels; as such, only the has to be programmed on the receiving end. TERMINAL 1 ID NUMBER GE Multilin T60 Transformer Protection System 5-99...
  • Page 246: Installation

    "Programmed" state. UNIT NOT PROGRAMMED setting allows the user to uniquely identify a relay. This name will appear on generated reports. RELAY NAME 5-100 T60 Transformer Protection System GE Multilin...
  • Page 247: Remote Resources Configuration

    Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the T60 process card and specific Brick. The relay is then configured to measure spe- cific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 248: System Setup

    1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). 5-102 T60 Transformer Protection System GE Multilin...
  • Page 249 = 66.4. On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the voltage value entered would be 120; that is, 14400 / 120. GE Multilin T60 Transformer Protection System 5-103...
  • Page 250: Power System

    FREQUENCY TRACKING frequency applications. NOTE The frequency tracking feature functions only when the T60 is in the “Programmed” mode. If the T60 is “Not Pro- grammed”, then metering values are available but can exhibit significant errors. NOTE Systems with an ACB phase sequence require special consideration. Refer to the Phase relationships of three- phase transformers sub-section of chapter 5.
  • Page 251: Signal Sources

    CT wiring problem. A disturbance detector is provided for each source. The 50DD function responds to the changes in magnitude of the sequence currents. The disturbance detector scheme logic is as follows: GE Multilin T60 Transformer Protection System 5-105...
  • Page 252 This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys- tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and the CT/VT inputs that are used to provide the data. 5-106 T60 Transformer Protection System GE Multilin...
  • Page 253: Transformer

     TRANSFORMER  GENERAL See page 5–108.    WINDING 1 MESSAGE See page 5–110.   WINDING 2 MESSAGE See page 5–110.   WINDING 3 MESSAGE See page 5–110.  GE Multilin T60 Transformer Protection System 5-107...
  • Page 254 See page 5–119.  The T60 Transformer Protection System has been designed to provide primary protection for medium to high voltage power transformers. It is able to perform this function on 2 to 5 winding transformers in a variety of system configurations.
  • Page 255 C = 0.02 × (weight of core and aluminum coils from the nameplate) • WINDING THERMAL TIME CONSTANT: Required for insulation aging calculation. If this value is not available from the transformer data, select “2 min.”. GE Multilin T60 Transformer Protection System 5-109...
  • Page 256 CTs and tapped relay windings with some combination of CT connections. The T60 simplifies these configuration issues. All CTs at the transformer are connected wye (polarity markings pointing away from the transformer). User-entered settings in the relay characterizing the transformer being protected and allow the relay to automatically perform all necessary magnitude, phase angle, and zero-sequence compensation.
  • Page 257 The reason the source phase sequence must be stated when describing the winding phase relationships is that these rela- tionships change when the phase sequence changes. The example shown below shows why this happens, using a trans- former described in IEC nomenclature as a type “Yd1” or in GE Multilin nomenclature as a “Y/d30.” 828716A1.CDR Figure 5–27: EXAMPLE TRANSFORMER...
  • Page 258 Note that the delta winding currents leads the wye winding currents by 30°, (which is a type Yd11 in IEC nomenclature and a type Y/d330 in GE Multilin nomenclature) which is in disagreement with the transformer nameplate. This is because the physical connections and hence the equations used to calculate current for the delta winding have not changed.
  • Page 259 5 SETTINGS 5.4 SYSTEM SETUP The T60 automatically corrects for CT mismatch errors. All currents are magnitude compensated to be in units of the CTs of one winding before the calculation of differential and restraint quantities. The reference winding (w ) is the winding to which all currents are referred.
  • Page 260 The T60 performs this phase angle compensation and zero sequence removal automatically, based on the settings entered for the transformer. All CTs are connected Wye (polarity markings pointing away from the transformer). All currents are phase and zero sequence compensated internally before the calculation of differential and restraint quantities.
  • Page 261 ------ - I – – ------ - I ------ - I ------ - I ------ - I – – ------ - I ------ - I ------ - I ------ - I – – GE Multilin T60 Transformer Protection System 5-115...
  • Page 262 = magnitude, phase and zero sequence compensated winding w phase currents = magnitude compensation factor for winding w (see previous sections) [ ] I , and = phase and zero sequence compensated winding w phase currents (see earlier) 5-116 T60 Transformer Protection System GE Multilin...
  • Page 263 SYSTEM SETUP SIGNAL  settings menu. SOURCES SOURCE 1(4) “WDG 1X” SOURCE 1 NAME: “F1” SOURCE 1 PHASE CT: “None” SOURCE 1 GROUND CT: “None” SOURCE 1 PHASE VT: “None” SOURCE 1 AUX VT: GE Multilin T60 Transformer Protection System 5-117...
  • Page 264 SYSTEM SETUP SIGNAL  settings menu. SOURCES SOURCE n “WDG 2" SOURCE 2 NAME: “M1” SOURCE 2 PHASE CT: “M1” SOURCE 2 GROUND CT: “None” SOURCE 2 PHASE VT: “None” SOURCE 2 AUX VT: 5-118 T60 Transformer Protection System GE Multilin...
  • Page 265 Range: –60 to 60°C in steps of 1 FEBRUARY AVERAGE: MESSAGE –30°C Range: –60 to 60°C in steps of 1 MARCH AVERAGE: MESSAGE –10°C ↓ Range: –60 to 60°C in steps of 1 DECEMBER AVERAGE: MESSAGE –10°C GE Multilin T60 Transformer Protection System 5-119...
  • Page 266: Breakers

    Range: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled 5-120 T60 Transformer Protection System GE Multilin...
  • Page 267 1. The number of breaker control elements is dependent on the number of CT/VT modules specified with the T60. The follow- ing settings are available for each breaker control element.
  • Page 268 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–30: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the T60 is in “Programmed” mode and not in the local control mode. NOTE 5-122 T60 Transformer Protection System...
  • Page 269 Note that IEC 61850 commands are event-driven and dwell time for these is one protection pass only. If you want to main- tain the close/open command for a certain time, do so either on the contact outputs using the "Seal-in" setting or in Flex- Logic. GE Multilin T60 Transformer Protection System 5-123...
  • Page 270: Disconnect Switches

    SWITCH 1 FUNCTION: This setting enables and disables the operation of the disconnect switch element. • SWITCH 1 NAME: Assign a user-defined name (up to six characters) to the disconnect switch. This name will be used in flash messages related to disconnect switch 1. 5-124 T60 Transformer Protection System GE Multilin...
  • Page 271 This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the T60 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin...
  • Page 272 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–32: DISCONNECT SWITCH SCHEME LOGIC 5-126 T60 Transformer Protection System GE Multilin...
  • Page 273: Flexcurves

    0.86 15.0 0.48 0.88 15.5 0.50 0.90 16.0 0.52 0.91 16.5 0.54 0.92 17.0 0.56 0.93 17.5 0.58 0.94 18.0 0.60 0.95 18.5 0.62 0.96 19.0 0.64 0.97 19.5 0.66 0.98 10.0 20.0 GE Multilin T60 Transformer Protection System 5-127...
  • Page 274 The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE 5-128 T60 Transformer Protection System GE Multilin...
  • Page 275 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the T60 are displayed in the following graphs. GE Multilin T60 Transformer Protection System...
  • Page 276 CURRENT (multiple of pickup) 842723A1.CDR Figure 5–36: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–37: RECLOSER CURVES GE113, GE120, GE138 AND GE142 5-130 T60 Transformer Protection System GE Multilin...
  • Page 277 Figure 5–38: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–39: RECLOSER CURVES GE131, GE141, GE152, AND GE200 GE Multilin T60 Transformer Protection System 5-131...
  • Page 278 Figure 5–40: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–41: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 5-132 T60 Transformer Protection System GE Multilin...
  • Page 279 Figure 5–42: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–43: RECLOSER CURVES GE119, GE135, AND GE202 GE Multilin T60 Transformer Protection System 5-133...
  • Page 280: Phasor Measurement Unit

    See page 5-154.  CONFIGURATION The T60 is provided with an optional phasor measurement unit feature. This feature is specified as a soft- ware option at the time of ordering. The number of phasor measurement units available can also depend on this option.
  • Page 281 NONE, which within the standard is classified as PRES OR UNKNOWN under the Calculation Method - ClcMth. Each Logical Device PMU supports one MxxMMXU, MxxMSQI, PxxxMMXU , PxxxMSQI, NxxMMXU, and one NxxMSQI logical node. Figure 5–46: LOGICAL NODES SUPPORTED IN EACH LOGICAL DEVICE GE Multilin T60 Transformer Protection System 5-135...
  • Page 282 C37.118 STN and IDCode is to be mapped as a concatenated value in the (d)escription field of LPL CDC of the NamPlt DO in LLN0. The mapping is implemented as STN-IDCode (text string). 5-136 T60 Transformer Protection System GE Multilin...
  • Page 283 The aggregators allow the aggregation of phasors from multiple PMUs (with the same reporting rate) into a single custom data set to optimize bandwidth when streaming. Figure 5–48: EXAMPLE OF AGGREGATOR DATA SETS GE Multilin T60 Transformer Protection System 5-137...
  • Page 284 CONFIGURATION EXAMPLE: CFG-2 BASED CONFIGURATION (USING IEC 61850-90-5) The T60 is expected to send the CFG-2 file (IEEE C37.118 config. file) upon request from the upstream synchrophasor devices (for example, P30) without stopping R-SV multicasting, as shown in the figure below. The primary domain control- ler (PDC) does not need to use a stop/start data stream command if the UR protocol is set to IEC 61850-90-5 prior to requesting the configuration via CFG-2 (IEEE C37.118 config.
  • Page 285 Range: 1 to 65534 in steps of 1 PMU 1 IDCODE: MESSAGE Range: 32-character ASCII string truncated to 16 PMU 1 STN: MESSAGE characters if mapped into C37.118 Default: GE-UR-PMU GE-UR-PMU Range: Available signal sources PMU 1 SIGNAL SOURCE: MESSAGE SRC 1...
  • Page 286 For a system frequency of 60 Hz (50 Hz), the T60 generates a reporting mismatch message if the selected rate is not set as 10 Hz, 12 Hz, 15 Hz, 20 Hz, 30 Hz, 60 Hz, or 120 Hz (or 10 Hz, 25 Hz, 50 Hz or 100 Hz when the system frequency is 50 Hz) when entered via the keypad or software;...
  • Page 287 This setting complies with bit-1 of the FORMAT field of the IEEE C37.118 configuration frame. This setting applies to synchrophasors only; the user-selectable FlexAnalog channels are always transmitted as 16-bit integer values. GE Multilin T60 Transformer Protection System 5-141...
  • Page 288 As per IEC 61850-6 standard specification, the PMU LD Name is the concatenated combination (to total 64 charac- ters) of IED Name (specified in IEC 61850 Server Settings) appended with PMU X LDINST string. NOTE 5-142 T60 Transformer Protection System GE Multilin...
  • Page 289 VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the true signal. GE Multilin T60 Transformer Protection System 5-143...
  • Page 290 When receiving synchrophasor data at multiple locations, with possibly different reference nodes, it can be more beneficial to allow the central locations to perform the compensation of sequence voltages. This setting applies to PMU data only. The T60 calculates symmetrical voltages independently for protection and control purposes without applying this correction.
  • Page 291 DPO TIME: 1.00 s Range: FlexLogic operand PMU 1 FREQ TRIG BLK: MESSAGE Range: Self-Reset, Latched, Disabled PMU 1 FREQ TRIGGER MESSAGE TARGET: Self-Reset Range: Enabled, Disabled PMU 1 FREQ TRIGGER MESSAGE EVENTS: Disabled GE Multilin T60 Transformer Protection System 5-145...
  • Page 292 T60 standards. This element requires that the frequency be above the minimum measurable value. If the frequency is below this value, such as when the circuit is de-energized, the trigger drops out.
  • Page 293 This element responds to elevated current. The trigger responds to the phase current signal of the phasor measurement unit (PMU) source. All current channel (A, B, and C) are processed independently and could trigger the recorder. GE Multilin T60 Transformer Protection System 5-147...
  • Page 294 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase power. The comparator applies a 3% hysteresis. 5-148 T60 Transformer Protection System GE Multilin...
  • Page 295 DPO TIME: 1.00 s Range: FlexLogic operand PMU 1 df/dt TRG BLK: MESSAGE Range: Self-Reset, Latched, Disabled PMU 1 df/dt TRIGGER MESSAGE TARGET: Self-Reset Range: Enabled, Disabled PMU 1 df/dt TRIGGER MESSAGE EVENTS: Disabled GE Multilin T60 Transformer Protection System 5-149...
  • Page 296 PMU 1 df/dt TRIGGER DPO TIME: This setting can be used to extend the trigger after the situation returned to nor- mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig- gering condition is asserted). 5-150 T60 Transformer Protection System GE Multilin...
  • Page 297 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–55: RATE OF CHANGE OF FREQUENCY TRIGGER SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-151...
  • Page 298  37.118 AGGR 1 PMU AGGREGATOR 1  CONFIGURATION TCP PORT: 4712 Range: 1 to 65534 PMU AGGREGATOR 1 MESSAGE UDP PORT: 4713 Range: Disabled, Enabled PMU AGGREGATOR 1 MESSAGE PDC CONTROL: Disabled 5-152 T60 Transformer Protection System GE Multilin...
  • Page 299 AGTR1 PDC CNTRL 3 Phasor data concentrator asserts control bit 3 as received via the network. ↓ as above AGTR1 PDC CNTRL 16 Phasor data concentrator asserts control bit 16, as received via the network. GE Multilin T60 Transformer Protection System 5-153...
  • Page 300 Range: 0 to 7 MSVCB 1 PRIORITY: MESSAGE Range: 0 to 252 MSVCB 1 IP CLASS: MESSAGE Range: 0 to 4095 MSVCB 1 VID: MESSAGE Range: 0 to 16383 MSVCB 1 APPID: MESSAGE 5-154 T60 Transformer Protection System GE Multilin...
  • Page 301 MSVCB 1 Security: This setting selects the level of security and authentication used, as outlined in the following table, and is in the form of an enumeration as per standard. The range is 0 to 2. Shaded settings in the table are not supported in firmware 7.0. ENUMERATION AUTHENTICATION ENCRYPTION NOTE GE Multilin T60 Transformer Protection System 5-155...
  • Page 302 5.4 SYSTEM SETUP 5 SETTINGS ENUMERATION AUTHENTICATION ENCRYPTION 5-156 T60 Transformer Protection System GE Multilin...
  • Page 303: Flexlogic

    Figure 5–57: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the T60 are represented by flags (or FlexLogic operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an ele- ment from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output.
  • Page 304 Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper- ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 5–19: T60 FLEXLOGIC OPERAND TYPES OPERAND TYPE STATE...
  • Page 305 5 SETTINGS 5.5 FLEXLOGIC The operands available for this relay are listed alphabetically by types in the following table. Table 5–20: T60 FLEXLOGIC OPERANDS (Sheet 1 of 9) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed...
  • Page 306 5.5 FLEXLOGIC 5 SETTINGS Table 5–20: T60 FLEXLOGIC OPERANDS (Sheet 2 of 9) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT BRK RESTRIKE 1 OP Breaker restrike detected in any phase of the breaker control 1 element Breaker restrike BRK RESTRIKE 1 OP A...
  • Page 307 5 SETTINGS 5.5 FLEXLOGIC Table 5–20: T60 FLEXLOGIC OPERANDS (Sheet 3 of 9) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: GND DIST Z1 PKP Ground distance zone 1 has picked up Ground distance GND DIST Z1 OP Ground distance zone 1 has operated...
  • Page 308 5.5 FLEXLOGIC 5 SETTINGS Table 5–20: T60 FLEXLOGIC OPERANDS (Sheet 4 of 9) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: PH DIST Z1 PKP Phase distance zone 1 has picked up Phase distance PH DIST Z1 OP Phase distance zone 1 has operated...
  • Page 309 5 SETTINGS 5.5 FLEXLOGIC Table 5–20: T60 FLEXLOGIC OPERANDS (Sheet 5 of 9) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: PMU Agg 1 SvEng On SvEng data item in associated control block is on Synchrophasor PMU 1 CURR TRIGGER Overcurrent trigger of phasor measurement unit 1 has operated...
  • Page 310 5.5 FLEXLOGIC 5 SETTINGS Table 5–20: T60 FLEXLOGIC OPERANDS (Sheet 6 of 9) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: SRC1 VT FF OP Source 1 VT fuse failure detector has operated VTFF (Voltage SRC1 VT FF DPO Source 1 VT fuse failure detector has dropped out...
  • Page 311 5 SETTINGS 5.5 FLEXLOGIC Table 5–20: T60 FLEXLOGIC OPERANDS (Sheet 7 of 9) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: UNDERFREQ 1 PKP Underfrequency 1 has picked up Underfrequency UNDERFREQ 1 OP Underfrequency 1 has operated UNDERFREQ 1 DPO Underfrequency 1 has dropped out...
  • Page 312 5.5 FLEXLOGIC 5 SETTINGS Table 5–20: T60 FLEXLOGIC OPERANDS (Sheet 8 of 9) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION INPUTS/OUTPUTS: Virt Ip 1 Flag is set, logic=1 Virtual inputs Virt Ip 2 Flag is set, logic=1 Virt Ip 3 Flag is set, logic=1 ↓...
  • Page 313 5 SETTINGS 5.5 FLEXLOGIC Table 5–20: T60 FLEXLOGIC OPERANDS (Sheet 9 of 9) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION SELF- ANY MAJOR ERROR Any of the major self-test errors generated (major error) DIAGNOSTICS ANY MINOR ERROR Any of the minor self-test errors generated (minor error)
  • Page 314: Flexlogic Rules

    When making changes to FlexLogic entries in the settings, all FlexLogic equations are re-compiled whenever any new FlexLogic entry value is entered, and as a result of the re-compile all latches are reset automatically. 5-168 T60 Transformer Protection System GE Multilin...
  • Page 315: Flexlogic Example

    DIGITAL ELEMENT 1 on Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–59: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS GE Multilin T60 Transformer Protection System 5-169...
  • Page 316 Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." 5-170 T60 Transformer Protection System GE Multilin...
  • Page 317 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". GE Multilin T60 Transformer Protection System 5-171...
  • Page 318 In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) 5-172 T60 Transformer Protection System GE Multilin...
  • Page 319: Flexlogic Equation Editor

    TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". GE Multilin T60 Transformer Protection System 5-173...
  • Page 320: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. 5-174 T60 Transformer Protection System GE Multilin...
  • Page 321 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS GE Multilin T60 Transformer Protection System 5-175...
  • Page 322 Figure 5–66: FLEXELEMENT DIRECTION, PICKUP, AND HYSTERESIS In conjunction with the setting the element could be programmed to provide two extra charac- FLEXELEMENT 1 INPUT MODE teristics as shown in the figure below. 5-176 T60 Transformer Protection System GE Multilin...
  • Page 323 DELTA TIME BASE = 1 µs FREQUENCY = 1 Hz BASE FREQUENCY RATE OF CHANGE df/dt = 1 Hz/s BASE PHASE ANGLE ϕ = 360 degrees (see the UR angle referencing convention) BASE GE Multilin T60 Transformer Protection System 5-177...
  • Page 324 “Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. 5-178 T60 Transformer Protection System GE Multilin...
  • Page 325: Non-Volatile Latches

    LATCH N LATCH N LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–68: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC GE Multilin T60 Transformer Protection System 5-179...
  • Page 326: Grouped Elements

    (see the Control elements section for additional details). If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.25, 7.31, or later to cor- rect this issue. 5-180 T60 Transformer Protection System GE Multilin...
  • Page 327 Keeping the memory in effect for too long may eventually lead to incorrect operation of the distance functions. GE Multilin T60 Transformer Protection System 5-181...
  • Page 328 In firmware 7.20, when the fast distance algorithm is applied, the HardFiber brick is not supported. The fast dis- tance algorithm is supported by the T60. It is not supported by the HardFiber, which maintains the original distance element timing.
  • Page 329 SETTINGS GROUPED   ELEMENTS SETTING GROUP 1(6) DISTANCE setting (common for the distance elements of all zones as entered under  MEMORY DURATION SETTINGS   GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE GE Multilin T60 Transformer Protection System 5-183...
  • Page 330 The selection is available on a per-zone basis. The two characteristics and their possible varia- tions are shown in the following figures. COMP LIMIT DIR COMP LIMIT DIR COMP LIMIT DIR RCA 837720A1.CDR Figure 5–70: DIRECTIONAL MHO DISTANCE CHARACTERISTIC 5-184 T60 Transformer Protection System GE Multilin...
  • Page 331 Figure 5–71: NON-DIRECTIONAL MHO DISTANCE CHARACTERISTIC COMP LIMIT COMP LIMIT DIR COMP LIMIT DIR COMP LIMIT DIR RCA LFT BLD RCA RGT BLD RCA -LFT BLD RGT BLD 837721A1.CDR Figure 5–72: DIRECTIONAL QUADRILATERAL PHASE DISTANCE CHARACTERISTIC GE Multilin T60 Transformer Protection System 5-185...
  • Page 332 COMP LIMIT = 90 COMP LIMIT = 60 DIR RCA = 45 DIR RCA = 80 DIR COMP LIMIT = 90 DIR COMP LIMIT = 60 837722A1.CDR Figure 5–74: MHO DISTANCE CHARACTERISTIC SAMPLE SHAPES 5-186 T60 Transformer Protection System GE Multilin...
  • Page 333 CTs are located at the same side as the read point. Therefore, the Z3 setting shall be set to “None”. See the Theory of operation chapter for more details, and the Application of settings chapter for information on calcu- lating distance reach settings in applications involving power transformers. GE Multilin T60 Transformer Protection System 5-187...
  • Page 334 If the mho shape is selected, the same limit angle applies to both the mho and supervising reactance compara- tors. In conjunction with the mho shape selection, the setting improves loadability of the protected line. In conjunction 5-188 T60 Transformer Protection System GE Multilin...
  • Page 335 • PHS DIST Z1 BLK: This setting enables the user to select a FlexLogic operand to block a given distance element. VT fuse fail detection is one of the applications for this setting. GE Multilin T60 Transformer Protection System 5-189...
  • Page 336 2 operation when the fault evolves from one type to another or migrates from the initial zone to zone 2. Desired zones in the trip output function should be assigned to accomplish NOTE this functionality. 5-190 T60 Transformer Protection System GE Multilin...
  • Page 337 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–79: PHASE DISTANCE ZONES 3 AND HIGHER OP SCHEME Figure 5–80: PHASE DISTANCE SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-191...
  • Page 338 Range: 60 to 90° in steps of 1 GND DIST Z1 QUAD MESSAGE LFT BLD RCA: 85° Range: 0.050 to 30.000 pu in steps of 0.001 GND DIST Z1 MESSAGE SUPV: 0.200 pu 5-192 T60 Transformer Protection System GE Multilin...
  • Page 339 GND DIST Z1 REV REACH RCA • GND DIST Z1 SHAPE: This setting selects the shape of the ground distance characteristic between the mho and quadrilateral characteristics. The selection is available on a per-zone basis. GE Multilin T60 Transformer Protection System 5-193...
  • Page 340 (3I_0) measured in the direction of the zone being compensated must be connected to the ground input CT of the CT bank configured under the . This setting specifies the ratio between the magnitudes of the mutual DISTANCE SOURCE 5-194 T60 Transformer Protection System GE Multilin...
  • Page 341 GND DIST Z1 DIR RCA: Selects the characteristic angle (or ‘maximum torque angle’) of the directional supervising function. If the mho shape is applied, the directional function is an extra supervising function, as the dynamic mho GE Multilin T60 Transformer Protection System 5-195...
  • Page 342 • GND DIST Z1 BLK: This setting enables the user to select a FlexLogic operand to block the given distance element. VT fuse fail detection is one of the applications for this setting. 5-196 T60 Transformer Protection System GE Multilin...
  • Page 343 2 operation if the fault evolves from one type to another or migrates from zone 3 or 4 to zone 2. The desired zones should be assigned in the trip output element to accomplish this NOTE functionality. GE Multilin T60 Transformer Protection System 5-197...
  • Page 344 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–85: GROUND DISTANCE ZONES 3 AND HIGHER OP SCHEME 5-198 T60 Transformer Protection System GE Multilin...
  • Page 345 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–86: GROUND DISTANCE ZONE 1 SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-199...
  • Page 346 The supervision is biased toward operation in order to avoid compromising the sensitivity of ground distance elements at low signal levels. Otherwise, the reverse fault condition that generates concern will have high polarizing levels so that a cor- rect reverse fault decision can be reliably made. 5-200 T60 Transformer Protection System GE Multilin...
  • Page 347 REACH MID: 60.00 Ω Range: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING QUAD REV MESSAGE REACH OUT: 70.00 Ω Range: 40 to 90° in steps of 1 POWER SWING REV MESSAGE RCA: 75° GE Multilin T60 Transformer Protection System 5-201...
  • Page 348 – faults in particular – that may occur during power swings. Operation of this dedicated disturbance detector is signaled via the operand. POWER SWING 50DD 5-202 T60 Transformer Protection System GE Multilin...
  • Page 349 The element can be set to use either lens (mho) or rectangular (quadrilateral) characteristics as illustrated below. When set to “Mho”, the element applies the right and left blinders as well. If the blinders are not required, their settings should be set high enough to effectively disable the blinders. GE Multilin T60 Transformer Protection System 5-203...
  • Page 350 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–89: POWER SWING DETECT MHO OPERATING CHARACTERISTICS Figure 5–90: EFFECTS OF BLINDERS ON THE MHO CHARACTERISTICS 5-204 T60 Transformer Protection System GE Multilin...
  • Page 351 POWER SWING SHAPE: This setting selects the shapes (either “Mho” or “Quad”) of the outer, middle and, inner char- acteristics of the power swing detect element. The operating principle is not affected. The “Mho” characteristics use the left and right blinders. GE Multilin T60 Transformer Protection System 5-205...
  • Page 352 POWER SWING INNER LIMIT ANGLE: This setting defines the inner power swing detect characteristic. The inner characteristic is used by the out-of-step tripping function: beyond the inner characteristic out-of-step trip action is defi- 5-206 T60 Transformer Protection System GE Multilin...
  • Page 353 The blocking signal resets the output operand but does not stop the out-of-step tripping sequence. POWER SWING TRIP GE Multilin T60 Transformer Protection System 5-207...
  • Page 354 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–92: POWER SWING DETECT SCHEME LOGIC (1 of 3) 5-208 T60 Transformer Protection System GE Multilin...
  • Page 355 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–93: POWER SWING DETECT SCHEME LOGIC (2 of 3) GE Multilin T60 Transformer Protection System 5-209...
  • Page 356 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–94: POWER SWING DETECT SCHEME LOGIC (3 of 3) 5-210 T60 Transformer Protection System GE Multilin...
  • Page 357: Load Encroachment

    The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be used to block selected protection elements such as distance or phase overcurrent. The following figure shows an effect of the load encroachment characteristics used to block the quadrilateral distance element. GE Multilin T60 Transformer Protection System 5-211...
  • Page 358 If the voltage is below this threshold a blocking signal will not be asserted by the element. When selecting this setting one must remember that the T60 measures the phase-to-ground sequence voltages regardless of the VT connection.
  • Page 359: Transformer Elements

    IEEE standards C57.91-1995: “IEEE Guide for Loading Mineral-Oil-Immersed Transformers” and C57.96-1989: “IEEE Guide for Loading Dry-Type Distribution Transformers”. The computations are based on transformer loading conditions, ambient temperature, and the entered transformer data. GE Multilin T60 Transformer Protection System 5-213...
  • Page 360 > K, where PKP represents a percent differential pickup setting and K is a restraint factor defined by the relays settings Slope 1, Slope 2, and a transition area between breakpoint 1 and breakpoint 2 settings. 5-214 T60 Transformer Protection System GE Multilin...
  • Page 361 Figure 5–98: PERCENT DIFFERENTIAL CALCULATIONS The T60 percent differential element is based on a configurable dual-breakpoint / dual-slope differential restraint character- istic. The purpose of the preset characteristic is to define the differential restraint ratio for the transformer winding currents at different loading conditions and distinguish between external and internal faults.
  • Page 362 2nd harmonic ratios during inrush conditions. This may result undesired tripping of the pro- tected transformer. Reducing the 2nd harmonic inhibit threshold may jeopardize dependability and speed of protection. 5-216 T60 Transformer Protection System GE Multilin...
  • Page 363 The relay produces three FlexLogic operands that may be used for testing or for special applications such as building cus- tom logic (1-out-of-3) or supervising some protection functions (ground time overcurrent, for example) from the 2nd har- monic inhibit. GE Multilin T60 Transformer Protection System 5-217...
  • Page 364 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–100: PERCENT DIFFERENTIAL SCHEME LOGIC 5-218 T60 Transformer Protection System GE Multilin...
  • Page 365 MESSAGE 140°C Range: 0 to 30000 min. in steps of 1 XFMR HST DELAY: MESSAGE 1 min. Range: FlexLogic operand XFMR HST BLOCK: MESSAGE Range: Self-reset, Latched, Disabled XFMR HST TARGET: MESSAGE Self-Reset GE Multilin T60 Transformer Protection System 5-219...
  • Page 366 • AGING FACTOR PICKUP: Enter a value above which the aging factor element will operate. Enter a setting greater than the maximum permissible aging factor under emergency loading conditions and maximum ambient temperature. 5-220 T60 Transformer Protection System GE Multilin...
  • Page 367 LOSS OF LIFE PICKUP: Enter the expended life, in hours, required for operation of the element. This setting should be above the total transformer life set as a reference based on nominal loading conditions and a 30°C ambient temper- ature, as outlined in the IEEE standards. GE Multilin T60 Transformer Protection System 5-221...
  • Page 368 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–104: TRANSFORMER LOSS OF LIFE LOGIC 5-222 T60 Transformer Protection System GE Multilin...
  • Page 369: Phase Current

    INVERSE TOC CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 370 5.041 4.827 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 5-224 T60 Transformer Protection System GE Multilin...
  • Page 371 0.60 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 GE Multilin T60 Transformer Protection System 5-225...
  • Page 372 = characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–29: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
  • Page 373 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The T60 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurve section in this chapter for details. GE Multilin...
  • Page 374 (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic curve (see the figure below); the pickup level is calculated as ‘Mvr’ times the setting. If the voltage restraint feature PHASE TOC1 PICKUP is disabled, the pickup level always remains at the setting value. 5-228 T60 Transformer Protection System GE Multilin...
  • Page 375 5 SETTINGS 5.6 GROUPED ELEMENTS Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage 818784A4.CDR Figure 5–105: PHASE TIME OVERCURRENT VOLTAGE RESTRAINT CHARACTERISTIC Figure 5–106: PHASE TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-229...
  • Page 376 The input current is the fundamental phasor magnitude. For timing curves, see the publication Instan- taneous Overcurrent Element Response to Saturated Waveforms in UR-Series Relays (GET-8400A). Figure 5–107: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC 5-230 T60 Transformer Protection System GE Multilin...
  • Page 377 30° +90° Phasors for Phase A Polarization: × VPol = VBC (1/_ECA) = polarizing voltage IA = operating current ECA = Element Characteristic Angle at 30° 827800A2.CDR Figure 5–108: PHASE A DIRECTIONAL POLARIZATION GE Multilin T60 Transformer Protection System 5-231...
  • Page 378 When set to "Yes", the directional element blocks the operation of any phase overcurrent element under directional control, when voltage memory expires; when set to "No", the directional element allows tripping of phase overcurrent elements under directional control. 5-232 T60 Transformer Protection System GE Multilin...
  • Page 379 If current reversal is of a concern, a longer delay – in the order of 20 ms – may be needed. Figure 5–109: PHASE DIRECTIONAL SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-233...
  • Page 380: Neutral Current

    MESSAGE   NEUTRAL IOC1 MESSAGE See page 5–236.   NEUTRAL IOC2 MESSAGE See page 5–236.  ↓  NEUTRAL IOC12 MESSAGE   NEUTRAL MESSAGE See page 5–237.  DIRECTIONAL OC1 5-234 T60 Transformer Protection System GE Multilin...
  • Page 381 NEUTRAL TOC 1 SETTING RESET: NEUTRAL TOC1 PKP NEUTRAL TOC1 NEUTRAL TOC1 DPO PICKUP SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A4.VSD Figure 5–110: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-235...
  • Page 382 The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of pickup). The operating quantity depends on how test currents are injected into the relay (single-phase injection): -- - × (EQ 5.38) – injected 5-236 T60 Transformer Protection System GE Multilin...
  • Page 383 NEUTRAL DIR OC1 REV MESSAGE PICKUP: 0.050 pu Range: FlexLogic operand NEUTRAL DIR OC1 BLK: MESSAGE Range: Self-reset, Latched, Disabled NEUTRAL DIR OC1 MESSAGE TARGET: Self-reset Range: Disabled, Enabled NEUTRAL DIR OC1 MESSAGE EVENTS: Disabled GE Multilin T60 Transformer Protection System 5-237...
  • Page 384 Table 5–33: QUANTITIES FOR "MEASURED IG" CONFIGURATION DIRECTIONAL UNIT OVERCURRENT UNIT POLARIZING MODE DIRECTION COMPARED PHASORS Forward –V_0 + Z_offset × IG/3 IG × 1∠ECA = |IG| Voltage Reverse –V_0 + Z_offset × IG/3 –IG × 1∠ECA 5-238 T60 Transformer Protection System GE Multilin...
  • Page 385 SYSTEM SETUP AC INPUTS VOLTAGE BANK  is set to “Vn” and the auxiliary voltage is connected to a zero-sequence voltage AUXILIARY VT CONNECTION source (such as broken delta connected secondary of VTs). GE Multilin T60 Transformer Protection System 5-239...
  • Page 386 180°. • NEUTRAL DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit angle for the forward direction. 5-240 T60 Transformer Protection System GE Multilin...
  • Page 387 When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique for the “Calculated 3I0” mode of operation. Figure 5–113: NEUTRAL DIRECTIONAL OVERCURRENT LOGIC GE Multilin T60 Transformer Protection System 5-241...
  • Page 388: Ground Current

     RESTRICTED GROUND MESSAGE See page 5–245.  FAULT 1 ↓  RESTRICTED GROUND MESSAGE  FAULT 6 For information on the Ground Time Overcurrent curves, see Inverse TOC Characteristics on page 5–223. 5-242 T60 Transformer Protection System GE Multilin...
  • Page 389 0.02 to 46 times the CT rating. NOTE This channel may be also equipped with a sensitive input. The conversion range of a sensitive channel is from 0.002 to 4.6 times the CT rating. NOTE GE Multilin T60 Transformer Protection System 5-243...
  • Page 390 0.02 to 46 times the CT rating. NOTE This channel may be equipped with a standard or sensitive input. The conversion range of a sensitive channel is from 0.002 to 4.6 times the CT rating. NOTE 5-244 T60 Transformer Protection System GE Multilin...
  • Page 391 MESSAGE EVENTS: Disabled As of T60 firmware revision 3.20, the definition of the restraining signal has been significantly changed compared to previous versions. The restraint during external faults is generally not lower, and often much higher, compared to the previous definition of the restraining signal (enhanced security). The restraint on...
  • Page 392 This is similar to a single infeed situation and may be mistaken for an internal fault. Similar difficulties occur in a breaker-and-a-half application of the restricted ground fault, where any through fault with a weak infeed from the winding itself may cause problems. 5-246 T60 Transformer Protection System GE Multilin...
  • Page 393 50% each 15.5 power system cycles. Having the differential and restraining signals developed, the element applies a single slope differential characteristic with a minimum pickup as shown in the logic diagram below. GE Multilin T60 Transformer Protection System 5-247...
  • Page 394 Igd = abs(3 × 0.0333 + 0.05) = 0.15 pu, IR0 = abs(3 × 0.033 – (0.05)) = 0.05 pu, IR2 = 3 × 0.033 = 0.10 pu, IR1 = 1.033 / 8 = 0.1292 pu, and Igr = 0.1292 pu Despite very low fault current level the differential current is above 100% of the restraining current. 5-248 T60 Transformer Protection System GE Multilin...
  • Page 395: Breaker Failure (Ansi 50Bf)

    BF1 TIMER 1 PICKUP MESSAGE DELAY: 0.000 s Range: Yes, No BF1 USE TIMER 2: MESSAGE Range: 0.000 to 65.535 s in steps of 0.001 BF1 TIMER 2 PICKUP MESSAGE DELAY: 0.000 s GE Multilin T60 Transformer Protection System 5-249...
  • Page 396 Because breaker failure can result in tripping a large number of breakers and this affects system safety and stability, a very high level of security is required. 5-250 T60 Transformer Protection System GE Multilin...
  • Page 397 FlexLogic operands that initiate tripping required to clear the faulted zone. The trip output can be sealed-in for an adjustable period. • Target message indicating a failed breaker has been declared • Illumination of the faceplate Trip LED (and the Phase A, B or C LED, if applicable) GE Multilin T60 Transformer Protection System 5-251...
  • Page 398 BF1 TIMER 1 PICKUP DELAY: Timer 1 is set to the shortest time required for breaker auxiliary contact Status-1 to open, from the time the initial trip signal is applied to the breaker trip circuit, plus a safety margin. 5-252 T60 Transformer Protection System GE Multilin...
  • Page 399 In microprocessor relays this time is not significant. In T60 relays, which use a Fourier transform, the calculated current magnitude will ramp-down to zero one power frequency cycle after the current is interrupted, and this lag should be included in the overall margin duration, as it occurs after current interruption.
  • Page 400 Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command should be given via output operand BKR FAIL 1 TRIP OP 5-254 T60 Transformer Protection System GE Multilin...
  • Page 401 5 SETTINGS 5.6 GROUPED ELEMENTS SINGLE-POLE BREAKER FAILURE, INITIATE Figure 5–121: SINGLE-POLE BREAKER FAILURE, TIMERS GE Multilin T60 Transformer Protection System 5-255...
  • Page 402 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–122: THREE-POLE BREAKER FAILURE, INITIATE 5-256 T60 Transformer Protection System GE Multilin...
  • Page 403 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–123: THREE-POLE BREAKER FAILURE, TIMERS GE Multilin T60 Transformer Protection System 5-257...
  • Page 404: Voltage Elements

    The undervoltage feature may also be used to block the functioning of other elements through the block feature of those elements. 5-258 T60 Transformer Protection System GE Multilin...
  • Page 405 V = secondary voltage applied to the relay = pickup level pickup % of voltage pickup 842788A1.CDR Figure 5–124: INVERSE TIME UNDERVOLTAGE CURVES At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting. NOTE GE Multilin T60 Transformer Protection System 5-259...
  • Page 406 The minimum voltage setting selects the operating voltage below which the element is blocked (a setting of “0” will allow a dead source to be considered a fault condition). Figure 5–125: PHASE UNDERVOLTAGE1 SCHEME LOGIC 5-260 T60 Transformer Protection System GE Multilin...
  • Page 407 Figure 5–126: PHASE OVERVOLTAGE SCHEME LOGIC > × If the source VT is wye-connected, then the phase overvoltage pickup condition is Pickup for V and V NOTE GE Multilin T60 Transformer Protection System 5-261...
  • Page 408 “Definite time”. The source assigned to this element must be configured for a phase VT. NEUTRAL OV1 CURVE VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to be wye-connected. Figure 5–127: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC 5-262 T60 Transformer Protection System GE Multilin...
  • Page 409 AUX UV1 EVENTS: MESSAGE Disabled The T60 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt- age conditions of the auxiliary voltage. The selects the voltage level at which the time undervoltage ele- AUX UV1 PICKUP ment starts timing.
  • Page 410 AUX OV1 EVENTS: MESSAGE Disabled The T60 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM ...
  • Page 411 “Phase-ground”, then the operating quantity for this element will be the phase-to-ground nominal volt- age. It is beneficial to use the phase-to-phase voltage mode for this element when the T60 device is applied on an iso- lated or resistance-grounded system.
  • Page 412 T = Operating Time TDM = Time Delay Multiplier (delay in seconds) V = fundamental RMS value of voltage (pu) F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) 5-266 T60 Transformer Protection System GE Multilin...
  • Page 413 F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) The volts/hertz inverse B curves are shown below. Time delay setting Multiples of volts per hertz pickup 830739A1.CDR Figure 5–132: VOLTS-PER-HERTZ CURVES, INVERSE CURVE B GE Multilin T60 Transformer Protection System 5-267...
  • Page 414 F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) The volts/hertz inverse C curves are shown below. Time delay setting Multiples of volts per hertz pickup 830740A1.CDR Figure 5–133: VOLTS-PER-HERTZ CURVES, INVERSE CURVE C 5-268 T60 Transformer Protection System GE Multilin...
  • Page 415: Control Elements

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. GE Multilin T60 Transformer Protection System 5-269...
  • Page 416 TRIP BUS 1 RESET: The trip bus output is reset when the operand assigned to this setting is asserted. Note that the operand is pre-wired to the reset gate of the latch, As such, a reset command the front panel interface or via RESET OP communications will reset the trip bus output. 5-270 T60 Transformer Protection System GE Multilin...
  • Page 417: Setting Groups

    GROUP 1 NAME: MESSAGE Range: up to 16 alphanumeric characters GROUP 2 NAME: MESSAGE ↓ Range: up to 16 alphanumeric characters GROUP 6 NAME: MESSAGE Range: Disabled, Enabled SETTING GROUP MESSAGE EVENTS: Disabled GE Multilin T60 Transformer Protection System 5-271...
  • Page 418 The assigned operand is used to control the “On” state of a particular settings group. VIRTUAL OUTPUT 1 5-272 T60 Transformer Protection System GE Multilin...
  • Page 419: Selector Switch

    Range: FlexLogic operand SELECTOR 1 3BIT ACK: MESSAGE Range: Restore, Synchronize, Sync/Restore SELECTOR 1 POWER-UP MESSAGE MODE: Restore Range: Self-reset, Latched, Disabled SELECTOR 1 TARGETS: MESSAGE Self-reset Range: Disabled, Enabled SELECTOR 1 EVENTS: MESSAGE Disabled GE Multilin T60 Transformer Protection System 5-273...
  • Page 420 • SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con- trol word pre-selects the position using the following encoding convention: POSITION rest 5-274 T60 Transformer Protection System GE Multilin...
  • Page 421 The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. GE Multilin T60 Transformer Protection System 5-275...
  • Page 422 3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–137: TIME-OUT MODE 5-276 T60 Transformer Protection System GE Multilin...
  • Page 423 Make the following changes to selector switch element in the    SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 GE Multilin T60 Transformer Protection System 5-277...
  • Page 424 3-bit acknowledge SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–139: SELECTOR SWITCH LOGIC 5-278 T60 Transformer Protection System GE Multilin...
  • Page 425: Underfrequency (Ansi 81U)

    For example, UNDERFREQ 1 PICKUP if the system frequency is 60 Hz and the load shedding is required at 59.5 Hz, the setting will be 59.50 Hz. Figure 5–140: UNDERFREQUENCY SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-279...
  • Page 426: Overfrequency (Ansi 81O)

    The setting selects OVERFREQ 1 SOURCE OVERFREQ 1 PICKUP the level at which the overfrequency element is to pickup. Figure 5–141: OVERFREQUENCY SCHEME LOGIC 5-280 T60 Transformer Protection System GE Multilin...
  • Page 427: Frequency Rate Of Change (Ansi 81R)

    FREQ RATE 1 OC SUPV PICKUP: This setting defines minimum current level required for operation of the element. The supervising function responds to the positive-sequence current. Typical application includes load shedding. Set the pickup threshold to zero if no overcurrent supervision is required. GE Multilin T60 Transformer Protection System 5-281...
  • Page 428 SETTINGS FREQ RATE 1 PKP FREQ RATE 1 MIN FREQUENCY: FREQ RATE 1 MAX FREQUENCY: F > MIN & F < MAX Calculate df/dt 832023A2.CDR Figure 5–142: FREQUENCY RATE OF CHANGE SCHEME LOGIC 5-282 T60 Transformer Protection System GE Multilin...
  • Page 429: Synchrocheck (Ansi 25)

    MESSAGE Disabled The T60 Transformer Protection System is provided with an optional synchrocheck element. This element is specified as a software option (select “10” or “11”) at the time of ordering. Refer to the Ordering section of chapter 2 for additional details.
  • Page 430 SYNCHK1 LIVE V2 MIN VOLT: This setting establishes a minimum voltage magnitude for V2 in ‘pu’. Above this mag- nitude, the V2 voltage input used for synchrocheck will be considered “Live” or energized. 5-284 T60 Transformer Protection System GE Multilin...
  • Page 431 The relay will use the phase channel of a three-phase set of voltages if pro- grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as part of the Source and a three-phase set is not. GE Multilin T60 Transformer Protection System 5-285...
  • Page 432 5.7 CONTROL ELEMENTS 5 SETTINGS Figure 5–143: SYNCHROCHECK SCHEME LOGIC 5-286 T60 Transformer Protection System GE Multilin...
  • Page 433: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”. • DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to “Disabled”, the operation of the pickup LED is blocked. GE Multilin T60 Transformer Protection System 5-287...
  • Page 434 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5–145: TRIP CIRCUIT EXAMPLE 1 5-288 T60 Transformer Protection System GE Multilin...
  • Page 435 In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). Figure 5–146: TRIP CIRCUIT EXAMPLE 2 GE Multilin T60 Transformer Protection System 5-289...
  • Page 436: Digital Counters

    –2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic operand for blocking the counting operation. All counter operands are blocked. 5-290 T60 Transformer Protection System GE Multilin...
  • Page 437 COUNTER 1 RESET: COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A2.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–147: DIGITAL COUNTER SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-291...
  • Page 438: Monitoring Elements

    See page 5–304.  DETECTOR  VT FUSE FAILURE 1 MESSAGE See page 5–306.   VT FUSE FAILURE 2 MESSAGE See page 5–306.   VT FUSE FAILURE 3 MESSAGE See page 5–306.  5-292 T60 Transformer Protection System GE Multilin...
  • Page 439 In three-pole tripping applications, the same operand should be configured to initiate arcing current calculations for poles A, B and C of the breaker. In single-pole tripping applications, per-pole tripping operands should be configured to initiate the calculations for the poles that are actually tripped. GE Multilin T60 Transformer Protection System 5-293...
  • Page 440 BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set. Breaker Contacts Initiate Extinguished Part Total Area = Breaker Arcing Current (kA·cycle) Programmable 100 ms Start Delay Start Stop Integration Integration Figure 5–148: ARCING CURRENT MEASUREMENT 5-294 T60 Transformer Protection System GE Multilin...
  • Page 441 5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–149: BREAKER ARCING CURRENT SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-295...
  • Page 442 Breaker open, Voltage difference drop, and Measured flashover current through the breaker. Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available across the breaker. 5-296 T60 Transformer Protection System GE Multilin...
  • Page 443 This application does not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than setting. However, monitoring the breaker contact will ensure scheme stability. BRK 1 FLSHOVR DIFF V PKP GE Multilin T60 Transformer Protection System 5-297...
  • Page 444 Depending on the flashover protection application, the flashover current can vary from levels of the charging current when the line is de-energized (all line breakers open), to well above the maximum line (feeder) load (line/feeder con- nected to load). 5-298 T60 Transformer Protection System GE Multilin...
  • Page 445 A six-cycle time delay applies after the selected FlexLogic operand resets. • BRK FLSHOVR PKP DELAY: This setting specifies the time delay to operate after a pickup condition is detected. GE Multilin T60 Transformer Protection System 5-299...
  • Page 446 5.7 CONTROL ELEMENTS 5 SETTINGS Figure 5–150: BREAKER FLASHOVER SCHEME LOGIC 5-300 T60 Transformer Protection System GE Multilin...
  • Page 447 BRK RESTRIKE 1 OP user can add counters and other logic to facilitate the decision making process as to the appropriate actions upon detecting a single restrike or a series of consecutive restrikes. GE Multilin T60 Transformer Protection System 5-301...
  • Page 448 FlexLogic operand will be picked up for only 1/8th of the power cycle. • BREAKER RESTRIKE 1 HF DETECT: This setting enables/disables high-frequency (HF) pattern detection when breaker restrike occurs. High-frequency pattern is typical for capacitor bank, cables, and long transmission line appli- cations. 5-302 T60 Transformer Protection System GE Multilin...
  • Page 449 “1” when breaker is opened, either manually or from protection logic. • BRK RSTR 1 CLS CMD: This setting assigns a FlexLogic operand indicating a breaker close command. It must be logic “1” when breaker is closed. Figure 5–153: BREAKER RESTRIKE SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-303...
  • Page 450 CT core of the same CT. If 3I_0 does not exist at source 2, then a CT failure is declared. • CT FAIL 1 3I0 INPUT 2 PICKUP: This setting selects the 3I_0 pickup value for input 2 (different CT input) of the relay. 5-304 T60 Transformer Protection System GE Multilin...
  • Page 451 CT FAIL 1 3V0 INPUT PICKUP: This setting specifies the pickup value for the 3V_0 source. • CT FAIL 1 PICKUP DELAY: This setting specifies the pickup delay of the CT failure element. Figure 5–154: CT FAILURE DETECTOR SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-305...
  • Page 452 VT is connected in Delta, do not enabled this function because there is no neutral wire for Delta connected VT. setting specifies the pickup level of 3rd harmonic of 3V0 signal for the VT NEU VT NEU WIRE OPEN 1 3 HRAM PKP WIRE OPEN detection logic to pick up. 5-306 T60 Transformer Protection System GE Multilin...
  • Page 453 827093AQ.CDR Figure 5–155: VT FUSE FAIL SCHEME LOGIC Base voltage for this element is PHASE VT SECONDARY setting in the case of WYE VTs and (PHASE VT SECONDARY)/ in case of DELTA VTs. GE Multilin T60 Transformer Protection System 5-307...
  • Page 454 = thermal protection trip time constant • I = measured overload RMS current • = measured load RMS current before overload occurs • k= IEC 255-8 k-factor applied to I , defining maximum permissible current above nominal current 5-308 T60 Transformer Protection System GE Multilin...
  • Page 455 The thermal overload protection element estimates accumulated thermal energy E using the following equations calculated each power cycle. When current is greater than the pickup level, I > k × I , element starts increasing the thermal energy: GE Multilin T60 Transformer Protection System 5-309...
  • Page 456 30 minutes Busbar 60 minutes 20 minutes Underground cable 20 to 60 minutes 60 minutes The logic for the thermal overload protection element is shown below. Figure 5–157: THERMAL OVERLOAD PROTECTION SCHEME LOGIC 5-310 T60 Transformer Protection System GE Multilin...
  • Page 457: Inputs And Outputs

    The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the T60 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
  • Page 458 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. 5-312 T60 Transformer Protection System GE Multilin...
  • Page 459: Virtual Inputs

    FlexLogic equation, it will likely have to be lengthened NOTE in time. A FlexLogic timer with a delayed reset can perform this function. Figure 5–159: VIRTUAL INPUTS SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-313...
  • Page 460: Contact Outputs

     PATH: SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS CONTACT OUTPUT H1a Range: Up to 12 alphanumeric characters  CONTACT OUTPUT H1a OUTPUT H1a ID  L-Cont Op 1 Range: FlexLogic operand OUTPUT H1a OPERATE: MESSAGE 5-314 T60 Transformer Protection System GE Multilin...
  • Page 461 PRODUCT SETUP USER-PROGRAMMABLE PUSHBUT-  menus: TONS USER PUSHBUTTON 1 USER PUSHBUTTON 2 “Self-reset” “Self-reset” PUSHBUTTON 1 FUNCTION: PUSHBUTTON 2 FUNCTION: “0.00 s” “0.00 s” PUSHBTN 1 DROP-OUT TIME: PUSHBTN 2 DROP-OUT TIME: GE Multilin T60 Transformer Protection System 5-315...
  • Page 462 Write the following FlexLogic equation (EnerVista UR Setup example shown): Program the Latching Outputs by making the following changes in the   SETTINGS INPUTS/OUTPUTS CONTACT OUT-  menu (assuming an H4L module): PUTS CONTACT OUTPUT H1a 5-316 T60 Transformer Protection System GE Multilin...
  • Page 463: Virtual Outputs

    32 “DNA” bit pairs that represent the state of two pre-defined events and 30 user-defined events. All remaining bit pairs are “UserSt” bit pairs, which are status bits representing user-definable events. The T60 implementation provides 32 of the 96 available UserSt bit pairs.
  • Page 464: Remote Inputs

    5 SETTINGS b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES In a T60 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the ...
  • Page 465: Remote Double-Point Status Inputs

    The remote double point status is recovered from the received IEC 61850 dataset and is available as through the RemDPS , and FlexLogic operands. These operands can then be Ip 1 BAD RemDPS Ip 1 INTERM RemDPS Ip 1 OFF RemDPS Ip 1 ON used in breaker or disconnect control schemes. GE Multilin T60 Transformer Protection System 5-319...
  • Page 466: Remote Outputs

    Each of these three operands generates an event in the event record when AND) activated. The setting shown above selects the operand that activates the operand. RESET OP (OPERAND) 5-320 T60 Transformer Protection System GE Multilin...
  • Page 467: Direct Inputs And Outputs

    FlexLogic operand that determines the state of this direct output. c) APPLICATION EXAMPLES The examples introduced in the earlier Direct Inputs and Outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. GE Multilin T60 Transformer Protection System 5-321...
  • Page 468 5.8 INPUTS AND OUTPUTS 5 SETTINGS EXAMPLE 1: EXTENDING INPUT/OUTPUT CAPABILITIES OF A T60 RELAY Consider an application that requires additional quantities of contact inputs or output contacts or lines of programmable logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements.
  • Page 469 "3" (effectively, this is a message from IED 1) DIRECT INPUT 6 BIT NUMBER: UR IED 2: "1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "3" DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: GE Multilin T60 Transformer Protection System 5-323...
  • Page 470: Teleprotection Inputs And Outputs

    Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-1 MESSAGE DEFAULT: Off Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-2 MESSAGE DEFAULT: Off ↓ Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-16 MESSAGE DEFAULT: Off 5-324 T60 Transformer Protection System GE Multilin...
  • Page 471 (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel failure between any pair of relays. GE Multilin T60 Transformer Protection System 5-325...
  • Page 472: Iec 61850 Goose Analogs

    GOOSE analog input value. GOOSE Analogs are floating-point values, with no units. The GOOSE UNIT and PU base settings allow the user to configure GOOSE Analog, so that it can be used in a FlexElement. 5-326 T60 Transformer Protection System GE Multilin...
  • Page 473: Iec 61850 Goose Integers

    GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log values in other T60 features, such as FlexElements. The base factor is applied to the GOOSE analog input FlexAn- alog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
  • Page 474 “Default Value”, then the value of the GOOSE uinteger input is defined by the setting. UINTEGER 1 DEFAULT The GOOSE integer input FlexInteger values are available for use in other T60 functions that use FlexInteger values. 5-328 T60 Transformer Protection System...
  • Page 475: Transducer Inputs And Outputs

    –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT F1 MIN VALUE DCMA INPUT F1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE GE Multilin T60 Transformer Protection System 5-329...
  • Page 476: Rtd Inputs

    1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. 5-330 T60 Transformer Protection System GE Multilin...
  • Page 477: Rrtd Inputs

     RRTD See page 5-332.    RRTD MESSAGE See page 5-332.  ↓  RRTD 12 MESSAGE See page 5-332.  Menus are available to configure each of the remote RTDs. GE Multilin T60 Transformer Protection System 5-331...
  • Page 478 5 SETTINGS It is recommended to use the T60 to configure the RRTD parameters. If the RRTDPC software is used to change the RRTD settings directly (the application and type settings), then one of the following two operations is required for changes to be reflected in the T60.
  • Page 479 ” If the RRTD communication link with the T60 is broken, then the last temperature actual values are retained until the RRTD communication failure is detected. When this occurs, a RRTD COMM FAILURE self-test alarm and target message is gen- erated, and an event is logged in the event recorder and the temperature actual values reset to 0.
  • Page 480 RTD group. All remote RTDs programmed to “Stator” are used for RTD biasing of the T60 thermal model. Common groups are provided for rotating machines applications such as ambient, bearing, group 1, or group 2. If the setting value is “Group”, then it is allowed to issue a trip if N –...
  • Page 481: Dcma Outputs

    . The follow- MIN VAL MAX VAL RANGE ing equation is applied: < if x  MIN VAL  if x >  MAX VAL (EQ 5.55)  otherwise  – MIN VAL GE Multilin T60 Transformer Protection System 5-335...
  • Page 482 20% overload compared to the nominal. The nominal three-phase power is: × × × 13.8 kV 0.8 kA 17.21 MW (EQ 5.57) The three-phase power with 20% overload margin is: × 1.2 17.21 MW 20.65 MW (EQ 5.58) 5-336 T60 Transformer Protection System GE Multilin...
  • Page 483 400 kV 400 kV × ------------------ - × ------------------ - 161.66 kV, 254.03 kV (EQ 5.64) The base unit for voltage (refer to the FlexElements section in this chapter for additional details) is: GE Multilin T60 Transformer Protection System 5-337...
  • Page 484 254.03 kV 1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. 5-338 T60 Transformer Protection System GE Multilin...
  • Page 485: Testing

    TEST MODE FORCING: MESSAGE The T60 provides a test facility to verify the functionality of contact inputs and outputs, some communication functions and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.
  • Page 486: Force Contact Inputs

    Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a T60 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.
  • Page 487: Force Contact Outputs

    PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu:   SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin T60 Transformer Protection System 5-341...
  • Page 488: Phasor Measurement Unit Test Values

    The relay must be in test mode to use the PMU test mode. That is, the  setting must be TESTING TEST MODE FUNCTION “Enabled” and the  initiating signal must be “On”. TESTING TEST MODE INITIATE 5-342 T60 Transformer Protection System GE Multilin...
  • Page 489 In test mode, the following actions take place: a. The Data Invalid / Test Mode bit (bit 15 in the STAT word) is set. b. The Sim bit in all output datasets is set. GE Multilin T60 Transformer Protection System 5-343...
  • Page 490 5.10 TESTING 5 SETTINGS 5-344 T60 Transformer Protection System GE Multilin...
  • Page 491: Actual Values

     GOOSE UINTEGERS  EGD PROTOCOL See page 6-10.  STATUS  TELEPROT CH TESTS See page 6-11.   COMM STATUS See page 6-11.  REMAINING CONNECT  PRP See page 6–12.  GE Multilin T60 Transformer Protection System...
  • Page 492 See page 6-26.  DCMA INPUTS  TRANSDUCER I/O See page 6-26.  RTD INPUTS  DISTANCE See page 6-26.   ACTUAL VALUES  USER-PROGRAMMABLE See page 6–28.  RECORDS  FAULT REPORTS T60 Transformer Protection System GE Multilin...
  • Page 493   PMU See page 6-29.  RECORDS  MAINTENANCE See page 6-30.   ACTUAL VALUES  MODEL INFORMATION See page 6-31.  PRODUCT INFO   FIRMWARE REVISIONS See page 6-31.  GE Multilin T60 Transformer Protection System...
  • Page 494: Contact Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. T60 Transformer Protection System GE Multilin...
  • Page 495: Teleprotection Inputs

    For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn. For form-C contact outputs, the state is displayed as Off or On. NOTE GE Multilin T60 Transformer Protection System...
  • Page 496: Virtual Outputs

    GSSE/GOOSE message, without a state change, is sent. When the GSSE/GOOSE message trasmits a state change, the resets to 0. This number rolls over to zero when a count of 4,294,967,295 is incre- SQNUM mented. T60 Transformer Protection System GE Multilin...
  • Page 497: Digital Counters

    PATH: ACTUAL VALUES STATUS ETHERNET Range: Fail, OK  ETHERNET ETHERNET PRI LINK  STATUS: Fail Range: Fail, OK ETHERNET SEC LINK MESSAGE STATUS: Fail Range: Fail, OK ETHERNET TRD LINK MESSAGE STATUS: Fail GE Multilin T60 Transformer Protection System...
  • Page 498: Real Time Clock Synchronizing

    PTP-— IRIG-B DELTA being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-B time. T60 Transformer Protection System GE Multilin...
  • Page 499: Direct Inputs

     STATUS STATUS: Offline Range: Offline, Online DIRECT DEVICE 2 MESSAGE STATUS: Offline ↓ Range: Offline, Online DIRECT DEVICE 16 MESSAGE STATUS: Offline These actual values represent the state of direct devices 1 through 16. GE Multilin T60 Transformer Protection System...
  • Page 500: Iec 61850 Goose Integers

    UINT INPUT 16 MESSAGE The T60 Transformer Protection System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chap- ter 2 for details.
  • Page 501: Teleprotection Channel Tests

    UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP status shows 4. — The number of IEC 61850 connections remaining. MMS TCP GE Multilin T60 Transformer Protection System 6-11...
  • Page 502: Parallel Redundancy Protocol (Prp)

    Mismatches Port B: MESSAGE The T60 Transformer Protection System is provided with optional PRP capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details. is a counter for total messages received (either from DANPs or from SANs) on Port A.
  • Page 503: Metering Conventions

    PF = Lag WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS GE Multilin T60 Transformer Protection System 6-13...
  • Page 504 ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. 6-14 T60 Transformer Protection System GE Multilin...
  • Page 505 The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a relative matter. It is important to remember that the T60 displays are always referenced as specified under SETTINGS ...
  • Page 506: Transformer

    THERMAL ELEMENTS    PATH: ACTUAL VALUES METERING TRANSFORMER THERMAL ELEMENTS  THERMAL TOP OIL °C:  ELEMENTS 70°C HOTTEST-SPOT °C: MESSAGE 130° AGING FACTOR: MESSAGE DAILY RATE LOL: MESSAGE 15 hrs 6-16 T60 Transformer Protection System GE Multilin...
  • Page 507: Sources

    SRC 1 RMS Ia: 0.000  SRC 1 b: 0.000 c: 0.000 SRC 1 RMS Ia: MESSAGE 0.000 SRC 1 RMS Ib: MESSAGE 0.000 SRC 1 RMS Ic: MESSAGE 0.000 SRC 1 RMS In: MESSAGE 0.000 GE Multilin T60 Transformer Protection System 6-17...
  • Page 508 SRC 1 RMS Vcg: MESSAGE 0.00 SRC 1 PHASOR Vag: MESSAGE 0.000 0.0° SRC 1 PHASOR Vbg: MESSAGE 0.000 0.0° SRC 1 PHASOR Vcg: MESSAGE 0.000 0.0° SRC 1 RMS Vab: MESSAGE 0.00 6-18 T60 Transformer Protection System GE Multilin...
  • Page 509 REAL POWER MESSAGE φb: 0.000 SRC 1 REAL POWER MESSAGE φc: 0.000 SRC 1 REACTIVE PWR MESSAGE 3φ: 0.000 SRC 1 REACTIVE PWR MESSAGE φa: 0.000 SRC 1 REACTIVE PWR MESSAGE φb: 0.000 GE Multilin T60 Transformer Protection System 6-19...
  • Page 510 S = V x Î x Î x Î (EQ 6.1) When VTs are configured in delta, the T60 does not calculate power in each phase and three-phase power is measured as S = V x Î x Î (EQ 6.2)
  • Page 511 These parameters can be monitored to reduce supplier demand penalties or for statistical metering purposes. Demand calculations are based on the measurement type selected in the  SETTINGS PRODUCT SETUP GE Multilin T60 Transformer Protection System 6-21...
  • Page 512: Synchrocheck

    If a synchrocheck function setting is "Disabled", the corresponding actual values menu item is not displayed. 6.3.5 TRACKING FREQUENCY   PATH: ACTUAL VALUES METERING TRACKING FREQUENCY  TRACKING FREQUENCY TRACKING FREQUENCY:  60.00 Hz 6-22 T60 Transformer Protection System GE Multilin...
  • Page 513: Frequency Rate Of Change

    XFMR DIFFERENTIAL CURRENT = maximum primary RMS value of the +IN and -IN inputs BASE (Xfmr Iad, Ibd, and Icd Mag) (CT primary for source currents, and transformer reference primary current for transformer differential currents) GE Multilin T60 Transformer Protection System 6-23...
  • Page 514: Iec 61580 Goose Analog Values

    ANALOG INPUT 32 MESSAGE 0.000 The T60 Transformer Protection System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chap- ter 2 for details.
  • Page 515: Pmu Aggregator 1

      PATH: ACTUAL VALUES METERING VOLTS PER HERTZ 1(2)  VOLTS PER HERTZ 1 VOLTS PER HERTZ 1:  0.000 pu The volts per hertz actual values are displayed in this menu. GE Multilin T60 Transformer Protection System 6-25...
  • Page 516: Restricted Ground Fault

    BC LOOP REACTANCE MESSAGE XBC: 0.00 Ohms BC LOOP IMPEDANCE MESSAGE ZBC: 0.00 Ohms BC LOOP IMPEDANCE MESSAGE ANGLE: 0.00 DEG CA LOOP RESISTANCE MESSAGE RCA: 0.00 Ohms CA LOOP REACTANCE MESSAGE XCA: 0.00 Ohms 6-26 T60 Transformer Protection System GE Multilin...
  • Page 517 (ZAG, ZBG, and ZCG) are reset to zero, including magnitude and angle. Note that VTs of the distance source must be connected in Wye if the ground distance element is enabled. GE Multilin T60 Transformer Protection System 6-27...
  • Page 518: Records

    This menu allows the user to view the number of triggers involved and number of oscillography traces available. The value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog- CYCLES PER RECORD raphy section of chapter 5 for additional details. 6-28 T60 Transformer Protection System GE Multilin...
  • Page 519: Data Logger

    PUM 1 AVAILABLE MESSAGE RECORDS: 0 Range: 0 to 6553.5 in steps of 0.1 PUM 1 SECONDS MESSAGE PER RECORD: 0.0 Range: date and time in format shown PUM 1 LAST CLEARED: MESSAGE 2013/07/14 15:40:16 GE Multilin T60 Transformer Protection System 6-29...
  • Page 520: Breaker Maintenance

    BKR 1 ARCING AMP  menu for clearing breaker arcing current records. The COMMANDS CLEAR RECORDS BREAKER OPERATING TIME defined as the slowest operating time of breaker poles that were initiated to open. 6-30 T60 Transformer Protection System GE Multilin...
  • Page 521: Product Information

    6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION   PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE order code format;  MODEL INFORMATION ORDER CODE LINE 1: example order code shown  T60-E00-HCH-F8H-H6A Range: standard GE serial number format SERIAL NUMBER:...
  • Page 522 6.5 PRODUCT INFORMATION 6 ACTUAL VALUES 6-32 T60 Transformer Protection System GE Multilin...
  • Page 523: Commands And

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin T60 Transformer Protection System...
  • Page 524 The date and time can be entered on the faceplate keypad. The time setting is based on the 24-hour clock. The complete date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the ENTER key is pressed. T60 Transformer Protection System GE Multilin...
  • Page 525: Relay Maintenance

    Various self-checking diagnostics are performed in the background while the T60 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the T60 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances.
  • Page 526: Phasor Measurement Unit One-Shot

    The high-accuracy high-sampling rate record of the two signals captured by the scope can be processed using digital tools to verify the magnitude and phase angle with respect to the time reference signal. As both the time reference and the mea- T60 Transformer Protection System GE Multilin...
  • Page 527: Security

    Operator Logoff: Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session. • Clear Security Data: Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the operands associated with the self-tests. Targets GE Multilin T60 Transformer Protection System...
  • Page 528: Targets Menu

     MESSAGE Each T60 element with a TARGET setting has a target message that when activated by its element is displayed in sequence with any other currently active target messages in the menu. In the example shown, the Phase TOC4 TARGETS and Digital Element 48 target settings are active and so have their targets displayed.
  • Page 529 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the T60 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).
  • Page 530 • What to do: Verify that all the items in the GOOSE data set are supported by the T60. The EnerVista UR Setup soft- ware will list the valid items. An IEC61850 client will also show which nodes are available for the T60.
  • Page 531 What to do: Check that Ethernet cable(s) are properly connected. Check that configuration for the SNTP server corre- sponds to the actual server settings. Check connectivity to the server (ping the server IP address. GE Multilin T60 Transformer Protection System...
  • Page 532 TEMP MONITOR: OVER TEMPERATURE • Latched target message: Yes. • Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. 7-10 T60 Transformer Protection System GE Multilin...
  • Page 533 7 COMMANDS AND TARGETS 7.1 COMMANDS • What to do: Remove the T60 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key • Latched target message: Yes. • Description of problem: Abnormal restart from modules being removed or inserted while the T60 is powered-up, when there is an abnormal DC supply, or as a result of internal relay failure.
  • Page 534 If this message appears, contact the factory and supply the failure code noted in the display. Text in the message identifies the failed module (for example, H81). If operated on a Process Card failure, the Module Fail self-test seals-in (latches) till the UR-series device is restarted. 7-12 T60 Transformer Protection System GE Multilin...
  • Page 535 Brick output failing to respond to an output command can only be detected while the command is active, and so in this case the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended, however the output may still be non-functional. GE Multilin T60 Transformer Protection System 7-13...
  • Page 536 7.1 COMMANDS 7 COMMANDS AND TARGETS 7-14 T60 Transformer Protection System GE Multilin...
  • Page 537: Theory Of Operation

    Figure 8–2: DIRECTIONAL PRINCIPLE OPERATION DURING INTERNAL FAULTS The T60 implementation calculates the maximum angle for the considered currents and compares it against a fixed thresh- old of 90°. The flag indicating whether the directional protection principle is satisfied is available as the FlexLogic operand XFMR PCNT DIFF DIR A/B/C.
  • Page 538 8.1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION T60 Transformer Protection System GE Multilin...
  • Page 539: Commissioning

    CT is the 1 A or 5 A tap, and M[1] is the calculated magnitude compensation factor (see the Transformer section in Chapter 5 for details on calculating the M[1] and M[2] factors). GE Multilin T60 Transformer Protection System...
  • Page 540 2 current as restraint and repeat the steps above by substituting the Breakpoint 2 value in the equations above with the new per-unit restraint current value. The above two tests can be repeated for Phases B and C. (pu) (pu) Figure 9–1: DIFFERENTIAL RESTRAINT CHARACTERISTIC T60 Transformer Protection System GE Multilin...
  • Page 541: Differential Characteristic Test Examples

    This allows the tester to define and confirm various points on the operating characteristic. The spreadsheet can be found at GE Multilin website (look in the support documents for the product).
  • Page 542: Test Example 1

    Not within zone Grounding Within zone Slope 2 Angle WRT 0° Angle WRT 0° Resistance 3Ph 10.000 ohms Resistance 3Ph 10.000 ohms Application of excessive current (> 3 ´ In) for extended periods damages the relay. T60 Transformer Protection System GE Multilin...
  • Page 543 0 A ∠0° 0.15 A ∠0° 0.23 A ∠–180° 0.15 A ∠–180° 0.23 A ∠0° The following differential and restraint current should be read from the T60 actual values menu: PHASE DIFFERENTIAL CURRENT (I PHASE RESTRAINT CURRENT (I 0 ∠0°...
  • Page 544 0 A ∠0° 0.48 A ∠0° 1 A ∠–180° 0.48 A ∠–180° 1 A ∠0° The following differential and restraint current should be read from the T60 actual values menu: PHASE DIFFERENTIAL CURRENT (I PHASE RESTRAINT CURRENT (I 0 ∠0°...
  • Page 545 3.5 pu Due to the mathematical complexity involved in shaping the curve between Breakpoint 1 and Breakpoint 2, an Excel-based simulation tool is available from the GE Multilin website (look in the support documents for the ⁄ ⁄...
  • Page 546 0 A ∠0° 0.5 A ∠0° 9 A ∠–180° 0.5 A ∠–180° 9 A ∠0° The following differential and restraint current should be read from the T60 actual values menu: PHASE DIFFERENTIAL CURRENT (I PHASE RESTRAINT CURRENT (I 0 ∠0°...
  • Page 547: Test Example 2

    0 ∠0° 7.915 ∠0° 8.646 ∠0° Slope 2 0.2 ∠0° 15 ∠–180° 7.918 ∠–180° 8.650 ∠–180° Operate = 95.7% 0 ∠0° 0 ∠0° 0 ∠0° 0 ∠0° 0.2 ∠–180° 0 ∠0° 7.916 ∠0° 8.650 ∠0° GE Multilin T60 Transformer Protection System...
  • Page 548: Test Example 3

    4 ∠0° 0 ∠0° 0 ∠0° 0 ∠0° Slope 2 Block = 93.7% 8 ∠–180° 0.8 ∠0° 11.93 ∠–180° 12.73 ∠0° < Slope 2 = 95% 4 ∠0° 0.8 ∠–180° 11.93 ∠0° 12.73 ∠–180° 9-10 T60 Transformer Protection System GE Multilin...
  • Page 549: Test Example 4

    0 ∠0° 0 ∠0° 0 ∠0° Intermediate Operate Slope 1 & 2 = 68.8% 0.8 ∠–90° 4.63 ∠–270° 3.18 ∠–270° 4.63 ∠–270° > 60% computed 0.8 ∠–270° 4.63 ∠–90° 3.18 ∠–90° 4.63 ∠–90° GE Multilin T60 Transformer Protection System 9-11...
  • Page 550 0 ∠0° 0 ∠0° 0 ∠0° 0 ∠0° Slope 2 Operate = 96% 0.18 ∠–90° 8.33 ∠–270° 8 ∠–270° 8.33 ∠–270° > Slope 2 = 95% 0.18 ∠–270° 8.33 ∠–90° 8 ∠–90° 8.33 ∠–90° 9-12 T60 Transformer Protection System GE Multilin...
  • Page 551: Inrush Inhibit Test Procedure

    Apply a second harmonic to Phase A with a level greater than the set threshold and monitor the operation of the Per- cent Differential element. The element should drop out when the injected second harmonic level becomes three times larger than the set threshold. GE Multilin T60 Transformer Protection System 9-13...
  • Page 552: Overexcitation Inhibit Test Procedure

    9.5% 2 A ∠–180° 2 pu 4 pu Block 2 A ∠0° 4 A ∠–180° 8.5% 2 pu 4 pu Operate 2 A ∠0° 4 A ∠–180° 9.5% 2 pu 4 pu Block 9-14 T60 Transformer Protection System GE Multilin...
  • Page 553: Frequency Element Tests

    Injection to a particular T60 frequency element must be to its configured source and to the channels the source uses for fre- quency measurement.
  • Page 554 1 second from test set time reading of ramp start to relay operation. Note that the T60 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time taken by the frequency responding component to pickup.
  • Page 555: Commissioning Test Tables

    Slope 2 Status: ____________ = _____________ 9.6.2 INRUSH INHIBIT TESTS Table 9–4: INRUSH INHIBIT TEST TABLE PHASE INJECTED DISPLAYED STATUS (BLOCK/ W1 2ND W2 2ND (PU) (PU) OPERATE) CURRENT HARMONIC CURRENT HARMONIC HARMONIC GE Multilin T60 Transformer Protection System 9-17...
  • Page 556: Overexcitation Inhibit Tests

    9.6 COMMISSIONING TEST TABLES 9 COMMISSIONING 9.6.3 OVEREXCITATION INHIBIT TESTS Table 9–5: OVEREXCITATION INHIBIT TEST RESULTS PHASE INJECTED DISPLAYED STATUS W1 5TH W2 5TH (PU) (PU) (BLOCK/ CURRENT HARMONIC CURRENT HARMONIC HARMONIC OPERATE) 9-18 T60 Transformer Protection System GE Multilin...
  • Page 557: Maintenance

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the T60. 842812A1.CDR Figure 10–1: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE)
  • Page 558 The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old CPUs. In the event that there is a mismatch between the CPU and CT/VT module, the relay does not function and error displays. NOTE DSP ERROR HARDWARE MISMATCH 10-2 T60 Transformer Protection System GE Multilin...
  • Page 559: Batteries

    10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit. 11. Power on the unit. 12. Dispose of the old battery as outlined in the next section. GE Multilin T60 Transformer Protection System 10-3...
  • Page 560 22. Reinstall the battery holder and the metal cover, and reinsert the power supply module into the unit. 23. Power on the unit. 24. Dispose of the old battery as outlined in the next section. 10-4 T60 Transformer Protection System GE Multilin...
  • Page 561: Dispose Of Battery

    La batterie est marqué de ce symbole, qui comprennent les indications cadmium (Cd), plomb (Pb), ou mercure (Hg). Pour le recyclage, retourner la batterie à votre fournisseur ou à un point de collecte. Pour plus d'informations, voir: www.recyclethis.info. GE Multilin T60 Transformer Protection System 10-5...
  • Page 562 Baterija je označena s tem simbolom, ki lahko vključuje napise, ki označujejo kadmij (Cd), svinec (Pb) ali živo srebro (Hg). Za ustrezno recikliranje baterijo vrnite dobavitelju ali jo odstranite na določenem zbirališču. Za več informacij obiščite spletno stran: www.recyclethis.info. 10-6 T60 Transformer Protection System GE Multilin...
  • Page 563 North America 905-294-6222 Latin America +55 11 3614 1700 Europe, Middle East, Africa +(34) 94 485 88 00 Asia +86-21-2401-3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574 GE Multilin T60 Transformer Protection System 10-7...
  • Page 564: Uninstall And Clear Files And Data

    Other files can be in standard formats, such as COMTRADE or .csv. You cannot erase directly the flash memory, but all records and settings in that memory can be deleted. Do this using the   command. SETTINGS PRODUCT SETUP CLEAR RELAY RECORDS 10-8 T60 Transformer Protection System GE Multilin...
  • Page 565: Repairs

    Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Grid Solutions service department in Canada at +1 905 927 5098. Use the detailed return procedure outlined at https://www.gegridsolutions.com/multilin/support/ret_proc.htm...
  • Page 566: Storage

    Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range outlined in the Specifications. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. 10-10 T60 Transformer Protection System GE Multilin...
  • Page 567: Disposal

    European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove the modules as outlined earlier, dismantle the unit, and recycle the metal when possible. GE Multilin T60 Transformer Protection System 10-11...
  • Page 568 10.6 DISPOSAL 10 MAINTENANCE 10-12 T60 Transformer Protection System GE Multilin...
  • Page 569: Parameter Lists

    SRC 1 Ib Mag Amps Source 1 phase B current magnitude 6157 SRC 1 Ib Angle Degrees Source 1 phase B current angle 6158 SRC 1 Ic Mag Amps Source 1 phase C current magnitude GE Multilin T60 Transformer Protection System...
  • Page 570 SRC 3 Ib Angle Degrees Source 3 phase B current angle 6286 SRC 3 Ic Mag Amps Source 3 phase C current magnitude 6288 SRC 3 Ic Angle Degrees Source 3 phase C current angle T60 Transformer Protection System GE Multilin...
  • Page 571 SRC 5 Ic Mag Amps Source 5 phase C current magnitude 6416 SRC 5 Ic Angle Degrees Source 5 phase C current angle 6417 SRC 5 In Mag Amps Source 5 neutral current magnitude GE Multilin T60 Transformer Protection System...
  • Page 572 SRC 1 Vab RMS Volts Source 1 phase AB voltage RMS 6673 SRC 1 Vbc RMS Volts Source 1 phase BC voltage RMS 6675 SRC 1 Vca RMS Volts Source 1 phase CA voltage RMS T60 Transformer Protection System GE Multilin...
  • Page 573 SRC 3 Vcg RMS Volts Source 3 phase CG voltage RMS 6790 SRC 3 Vag Mag Volts Source 3 phase AG voltage magnitude 6792 SRC 3 Vag Angle Degrees Source 3 phase AG voltage angle GE Multilin T60 Transformer Protection System...
  • Page 574 Source 4 zero-sequence voltage magnitude 6885 SRC 4 V_0 Angle Degrees Source 4 zero-sequence voltage angle 6886 SRC 4 V_1 Mag Volts Source 4 positive-sequence voltage magnitude 6888 SRC 4 V_1 Angle Degrees Source 4 positive-sequence voltage angle T60 Transformer Protection System GE Multilin...
  • Page 575 SRC 6 Vbc Angle Degrees Source 6 phase BC voltage angle 7003 SRC 6 Vca Mag Volts Source 6 phase CA voltage magnitude 7005 SRC 6 Vca Angle Degrees Source 6 phase CA voltage angle GE Multilin T60 Transformer Protection System...
  • Page 576 Source 3 phase B real power 7238 SRC 3 Pc Watts Source 3 phase C real power 7240 SRC 3 Q Vars Source 3 three-phase reactive power 7242 SRC 3 Qa Vars Source 3 phase A reactive power T60 Transformer Protection System GE Multilin...
  • Page 577 Source 6 phase A real power 7332 SRC 6 Pb Watts Source 6 phase B real power 7334 SRC 6 Pc Watts Source 6 phase C real power 7336 SRC 6 Q Vars Source 6 three-phase reactive power GE Multilin T60 Transformer Protection System...
  • Page 578 Source 1 phase C current demand 7686 SRC 1 Demand Watt Watts Source 1 real power demand 7688 SRC 1 Demand var Vars Source 1 reactive power demand 7690 SRC 1 Demand Va Source 1 apparent power demand A-10 T60 Transformer Protection System GE Multilin...
  • Page 579 Brk 2 Op Time Breaker 2 operating time 8692 Brk 3 Arc Amp A Breaker 3 arcing amp phase A -cyc 8694 Brk 3 Arc Amp B Breaker 3 arcing amp phase B -cyc GE Multilin T60 Transformer Protection System A-11...
  • Page 580 Synchrocheck 1 delta frequency 9219 Synchchk 1 Delta Phs Degrees Synchrocheck 1 delta phase 9220 Synchchk 2 Delta V Volts Synchrocheck 2 delta voltage 9222 Synchchk 2 Delta F Synchrocheck 2 delta frequency A-12 T60 Transformer Protection System GE Multilin...
  • Page 581 SRC 1 Ia Harm[7] Source 1 phase A current seventh harmonic 10247 SRC 1 Ia Harm[8] Source 1 phase A current eighth harmonic 10248 SRC 1 Ia Harm[9] Source 1 phase A current ninth harmonic GE Multilin T60 Transformer Protection System A-13...
  • Page 582 SRC 1 Ic Harm[4] Source 1 phase C current fourth harmonic 10310 SRC 1 Ic Harm[5] Source 1 phase C current fifth harmonic 10311 SRC 1 Ic Harm[6] Source 1 phase C current sixth harmonic A-14 T60 Transformer Protection System GE Multilin...
  • Page 583 SRC 2 Ib THD Source 2 phase B current total harmonic distortion 10373 SRC 2 Ib Harm[2] Source 2 phase B current second harmonic 10374 SRC 2 Ib Harm[3] Source 2 phase B current third harmonic GE Multilin T60 Transformer Protection System A-15...
  • Page 584 SRC 2 Ic Harm[23] Source 2 phase C current twenty-third harmonic 10428 SRC 2 Ic Harm[24] Source 2 phase C current twenty-fourth harmonic 10429 SRC 2 Ic Harm[25] Source 2 phase C current twenty-fifth harmonic A-16 T60 Transformer Protection System GE Multilin...
  • Page 585 SRC 3 Ib Harm[20] Source 3 phase B current twentieth harmonic 10491 SRC 3 Ib Harm[21] Source 3 phase B current twenty-first harmonic 10492 SRC 3 Ib Harm[22] Source 3 phase B current twenty-second harmonic GE Multilin T60 Transformer Protection System A-17...
  • Page 586 SRC 4 Ia Harm[17] Source 4 phase A current seventeenth harmonic 10554 SRC 4 Ia Harm[18] Source 4 phase A current eighteenth harmonic 10555 SRC 4 Ia Harm[19] Source 4 phase A current nineteenth harmonic A-18 T60 Transformer Protection System GE Multilin...
  • Page 587 SRC 4 Ic Harm[14] Source 4 phase C current fourteenth harmonic 10617 SRC 4 Ic Harm[15] Source 4 phase C current fifteenth harmonic 10618 SRC 4 Ic Harm[16] Source 4 phase C current sixteenth harmonic GE Multilin T60 Transformer Protection System A-19...
  • Page 588 SRC 5 Ib Harm[11] Source 5 phase B current eleventh harmonic 10680 SRC 5 Ib Harm[12] Source 5 phase B current twelfth harmonic 10681 SRC 5 Ib Harm[13] Source 5 phase B current thirteenth harmonic A-20 T60 Transformer Protection System GE Multilin...
  • Page 589 SRC 6 Ia Harm[8] Source 6 phase A current eighth harmonic 10743 SRC 6 Ia Harm[9] Source 6 phase A current ninth harmonic 10744 SRC 6 Ia Harm[10] Source 6 phase A current tenth harmonic GE Multilin T60 Transformer Protection System A-21...
  • Page 590 SRC 6 Ic Harm[5] Source 6 phase C current fifth harmonic 10806 SRC 6 Ic Harm[6] Source 6 phase C current sixth harmonic 10807 SRC 6 Ic Harm[7] Source 6 phase C current seventh harmonic A-22 T60 Transformer Protection System GE Multilin...
  • Page 591 RTD Ip 1 RTD input 1 actual value 13553 RTD Ip 2 RTD input 2 actual value 13554 RTD Ip 3 RTD input 3 actual value 13555 RTD Ip 4 RTD input 4 actual value GE Multilin T60 Transformer Protection System A-23...
  • Page 592 RTD input 48 actual value 13600 Ohm Inputs 1 Value Ohms Ohm inputs 1 value 13601 Ohm Inputs 2 Value Ohms Ohm inputs 2 value 14189 PTP–IRIG-B Delta PTP time minus IRIG-B time A-24 T60 Transformer Protection System GE Multilin...
  • Page 593 41134 V0 3rd Harmonic 2 Volts VTFF 2 V0 3rd Harmonic 41136 V0 3rd Harmonic 3 Volts VTFF 3 V0 3rd Harmonic 41138 V0 3rd Harmonic 4 Volts VTFF 4 V0 3rd Harmonic GE Multilin T60 Transformer Protection System A-25...
  • Page 594: Flexinteger Items

    PMU 1 STAT flags 9968 GOOSE UInt Input 1 IEC61850 GOOSE UInteger input 1 9970 GOOSE UInt Input 2 IEC61850 GOOSE UInteger input 2 9972 GOOSE UInt Input 3 IEC61850 GOOSE UInteger input 3 A-26 T60 Transformer Protection System GE Multilin...
  • Page 595 IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 GE Multilin T60 Transformer Protection System A-27...
  • Page 596 A.1 PARAMETER LISTS APPENDIX A A-28 T60 Transformer Protection System GE Multilin...
  • Page 597: Modbus Communications

    (CRC-16) with every packet which is an industry standard method used for error detection. If a Modbus slave device receives a packet in which an error is indicated by the CRC, the slave device does not act upon or respond to the GE Multilin T60 Transformer Protection System...
  • Page 598: Modbus Rtu Crc-16 Algorithm

    This algorithm requires the characteristic polynomial to be reverse bit ordered. The most significant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder. A C programming language implementation of the CRC algorithm will be provided upon request. T60 Transformer Protection System GE Multilin...
  • Page 599 No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC GE Multilin T60 Transformer Protection System...
  • Page 600: Modbus Function Codes

    DATA #1 - low NUMBER OF REGISTERS - low DATA #2 - high CRC - low DATA #2 - low CRC - high DATA #3 - high DATA #3 - low CRC - low CRC - high T60 Transformer Protection System GE Multilin...
  • Page 601: Execute Operation (Function Code 05H

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high GE Multilin T60 Transformer Protection System...
  • Page 602: Store Multiple Settings (Function Code 10H

    PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte T60 Transformer Protection System GE Multilin...
  • Page 603: File Transfers

    Last Cleared Date" to the present date and time. To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT GE Multilin T60 Transformer Protection System...
  • Page 604 EVTnnn.TXT (replace nnn with the desired starting record number) To read from a specific record to another specific record, use the following filename: EVT.TXT xxxxx yyyyy (replace xxxxx with the starting record number and yyyyy with the ending record number) T60 Transformer Protection System GE Multilin...
  • Page 605: Memory Mapping

    0 (Off) 040C Virtual Input 13 State 0 to 1 F108 0 (Off) 040D Virtual Input 14 State 0 to 1 F108 0 (Off) 040E Virtual Input 15 State 0 to 1 F108 0 (Off) GE Multilin T60 Transformer Protection System...
  • Page 606 IEC103 Common ASDU Address 0 to 254 F001 0583 IEC103 Sync Timeout 1 to 1440 F001 IEC 103 Binary Inputs (Read/Write Setting) (96 modules) 0584 IEC103 Binary Input 1 FUN 0 to 255 F001 B-10 T60 Transformer Protection System GE Multilin...
  • Page 607 ...Repeated for Binary Input 48 0644 ...Repeated for Binary Input 49 0648 ...Repeated for Binary Input 50 064C ...Repeated for Binary Input 51 0650 ...Repeated for Binary Input 52 0654 ...Repeated for Binary Input 53 GE Multilin T60 Transformer Protection System B-11...
  • Page 608 IEC103 ASDU 1 Analog Param 2 0 to 65535 F600 070C IEC103 ASDU 1 Analog Factor 2 0 to 65.535 0.001 F001 1000 070D IEC103 ASDU 1 Analog Offset 2 -32768 to 32767 F002 B-12 T60 Transformer Protection System GE Multilin...
  • Page 609 ...Repeated for IEC103 Command 21 07D4 ...Repeated for IEC103 Command 22 07D8 ...Repeated for IEC103 Command 23 07DC ...Repeated for IEC103 Command 24 07E0 ...Repeated for IEC103 Command 25 07E4 ...Repeated for IEC103 Command 26 GE Multilin T60 Transformer Protection System B-13...
  • Page 610 0 to 3 F605 3 (Bad) 1555 Remote Double-Point Status Input 5 State 0 to 3 F605 3 (Bad) Platform Direct Input/Output States (Read Only) 15C0 Direct Input States (6 items) 0 to 65535 F500 B-14 T60 Transformer Protection System GE Multilin...
  • Page 611 ...Repeated for Field RTD 6 16C6 ...Repeated for Field RTD 7 16C7 ...Repeated for Field RTD 8 Field Unit Transducer Actuals (Read Only) (8 modules) 16C8 Field Transducer 1 Value -32.768 to 32.767 0.001 F004 GE Multilin T60 Transformer Protection System B-15...
  • Page 612 Source 1 Phase CG Voltage Magnitude 0 to 999999.999 0.001 F060 1A0E Source 1 Phase CG Voltage Angle -359.9 to 0 degrees F002 1A0F Source 1 Phase AB or AC Voltage RMS 0 to 999999.999 0.001 F060 B-16 T60 Transformer Protection System GE Multilin...
  • Page 613 -0.999 to 1 0.001 F013 1C1C Reserved (4 items) F001 1C20 ...Repeated for Source 2 1C40 ...Repeated for Source 3 1C60 ...Repeated for Source 4 1C80 ...Repeated for Source 5 1CA0 ...Repeated for Source 6 GE Multilin T60 Transformer Protection System B-17...
  • Page 614 ...Repeated for Source 3 1EE0 ...Repeated for Source 4 1F00 ...Repeated for Source 5 1F20 ...Repeated for Source 6 Breaker Flashover (Read/Write Setting) (2 modules) 2196 Breaker Flashover 1 Function 0 to 1 F102 0 (Disabled) B-18 T60 Transformer Protection System GE Multilin...
  • Page 615 Transformer Differential 2nd Harm Iad Magnitude 0 to 999.9 % fo F001 2306 Transformer Differential 2nd Harm Iad Angle -359.9 to 0 degrees F002 2307 Transformer Differential 5th Harm Iad Magnitude 0 to 999.9 % fo F001 GE Multilin T60 Transformer Protection System B-19...
  • Page 616 PMU 1 Auxiliary Voltage Magnitude 0 to 999999.999 0.001 F060 2578 PMU 1 Auxiliary Voltage Angle -180 to 180 ° 0.01 F002 2579 PMU 1 Positive Sequence Voltage Magnitude 0 to 999999.999 0.001 F060 B-20 T60 Transformer Protection System GE Multilin...
  • Page 617 0 to 4294967295 F003 26F8 IEC 61850 Received uinteger 5 0 to 4294967295 F003 26FA IEC 61850 Received uinteger 6 0 to 4294967295 F003 26FC IEC 61850 Received uinteger 7 0 to 4294967295 F003 GE Multilin T60 Transformer Protection System B-21...
  • Page 618 F102 0 (Disabled) 3093 Fault Report 1 Prefault Trigger 0 to 4294967295 F300 3095 Fault Report Analog Channel 1 (32 items) 0 to 65536 F600 30B5 Fault Report 1 Reserved (5 items) F001 B-22 T60 Transformer Protection System GE Multilin...
  • Page 619 0 (Disabled) 3335 Failed Authentication Alarm Enable 0 to 1 F102 1 (Enabled) 3336 Firmware Lock Alarm 0 to 1 F102 1 (Enabled) 3337 Settings Lock Alarm 0 to 1 F102 1 (Enabled) GE Multilin T60 Transformer Protection System B-23...
  • Page 620 -32768 to 32767 °C F002 34F7 RTD Input 8 Value -32768 to 32767 °C F002 34F8 RTD Input 9 Value -32768 to 32767 °C F002 34F9 RTD Input 10 Value -32768 to 32767 °C F002 B-24 T60 Transformer Protection System GE Multilin...
  • Page 621 1812 373D Secondary Accounting Port 0 to 65535 F001 1813 373F RADIUS Authentication Method F619 0 (EAP-TTLS) 3740 RADIUS Vendor ID 1 to 65535 F001 2910 3741 Authentication Timeout 0 to 9999 F001 GE Multilin T60 Transformer Protection System B-25...
  • Page 622 AC Bank Redundancy Type 0 to 2 F261 1 (Dependability Biased) 3895 Remote Phase CT 1 Primary 1 to 65000 F001 3896 Remote Phase CT 1 Secondary 0 to 1 F123 0 (1 A) B-26 T60 Transformer Protection System GE Multilin...
  • Page 623 ...Repeated for Field Contact Input 31 3A55 ...Repeated for Field Contact Input 32 3A60 ...Repeated for Field Contact Input 33 3A6B ...Repeated for Field Contact Input 34 3A76 ...Repeated for Field Contact Input 35 GE Multilin T60 Transformer Protection System B-27...
  • Page 624 Field Shared Output 1 ID 0 to 65535 F205 "SO 1" 3E36 Field Shared Output 1 Operate 0 to 4294967295 F300 3E38 Field Shared Output 1 Unit Dest 1 0 to 8 F256 0 (None) B-28 T60 Transformer Protection System GE Multilin...
  • Page 625 Field Unit 1 Status 0 to 4 F262 0 (Disabled) 3FC1 ...Repeated for Field Unit 2 3FCA ...Repeated for Field Unit 3 3FD3 ...Repeated for Field Unit 4 3FDC ...Repeated for Field Unit 5 GE Multilin T60 Transformer Protection System B-29...
  • Page 626 Port 1 IP Address 0 to 4294967295 F003 2130706433 4089 Port 1 IP Subnet Mask 0 to 4294967295 F003 4278190080 408B Port 1 Gateway IP Address 0 to 4294967295 F003 56554497 408D Network Address NSAP F074 B-30 T60 Transformer Protection System GE Multilin...
  • Page 627 4107 Port 2 IP Subnet Mask 0 to 4294967295 F003 4278190080 4109 Port 2 Gateway IP Address 0 to 4294967295 F003 56554497 410B PRT2 Ethernet Operation Mode 0 to 1 F192 1 (Full-Duplex) GE Multilin T60 Transformer Protection System B-31...
  • Page 628 Daylight Savings Time (DST) Start Day 0 to 6 F238 0 (Sunday) 41AC Daylight Savings Time (DST) Start Day Instance 0 to 4 F239 0 (First) 41AD Daylight Savings Time (DST) Start Hour 0 to 23 F001 B-32 T60 Transformer Protection System GE Multilin...
  • Page 629 ...Repeated for User-Programmable LED 31 431D ...Repeated for User-Programmable LED 32 4320 ...Repeated for User-Programmable LED 33 4323 ...Repeated for User-Programmable LED 34 4326 ...Repeated for User-Programmable LED 35 4329 ...Repeated for User-Programmable LED 36 GE Multilin T60 Transformer Protection System B-33...
  • Page 630 Ground CT 1 Secondary 0 to 1 F123 0 (1 A) 4484 ...Repeated for CT Bank 2 4488 ...Repeated for CT Bank 3 448C ...Repeated for CT Bank 4 4490 ...Repeated for CT Bank 5 B-34 T60 Transformer Protection System GE Multilin...
  • Page 631 Transformer Winding 1 Resistance 0.0001 to 100 ohms 0.0001 F003 100000 4653 ...Repeated for Transformer Winding 2 4666 ...Repeated for Transformer Winding 3 4679 ...Repeated for Transformer Winding 4 468C ...Repeated for Transformer Winding 5 GE Multilin T60 Transformer Protection System B-35...
  • Page 632 ...Repeated for User-Definable Display 4 4C80 ...Repeated for User-Definable Display 5 4CA0 ...Repeated for User-Definable Display 6 4CC0 ...Repeated for User-Definable Display 7 4CE0 ...Repeated for User-Definable Display 8 4D00 ...Repeated for User-Definable Display 9 B-36 T60 Transformer Protection System GE Multilin...
  • Page 633 FlexLogic Entry (512 items) 0 to 4294967295 F300 2097152 RTD Inputs (Read/Write Setting) (48 modules) 5400 RTD Input 1 Function 0 to 1 F102 0 (Disabled) 5401 RTD Input 1 ID F205 “RTD Ip 1“ GE Multilin T60 Transformer Protection System B-37...
  • Page 634 0 to 2 F129 0 (millisecond) 5801 FlexLogic Timer 1 Pickup Delay 0 to 60000 F001 5802 FlexLogic Timer 1 Dropout Delay 0 to 60000 F001 5803 Reserved (5 items) 0 to 65535 F001 B-38 T60 Transformer Protection System GE Multilin...
  • Page 635 Phase Instantaneous Overcurrent 1 Signal Source 0 to 5 F167 0 (SRC 1) 5A02 Phase Instantaneous Overcurrent 1 Pickup 0 to 30 0.001 F001 1000 5A03 Phase Instantaneous Overcurrent 1 Delay 0 to 600 0.01 F001 GE Multilin T60 Transformer Protection System B-39...
  • Page 636 ...Repeated for Neutral Instantaneous Overcurrent 8 5C88 ...Repeated for Neutral Instantaneous Overcurrent 9 5C99 ...Repeated for Neutral Instantaneous Overcurrent 10 5CAA ...Repeated for Neutral Instantaneous Overcurrent 11 5CBB ...Repeated for Neutral Instantaneous Overcurrent 12 B-40 T60 Transformer Protection System GE Multilin...
  • Page 637 CT Fail 1 Events 0 to 1 F102 0 (Disabled) 5E78 ...Repeated for CT Fail 2 5E84 ...Repeated for CT Fail 3 5E90 ...Repeated for CT Fail 4 5E9C ...Repeated for CT Fail 5 GE Multilin T60 Transformer Protection System B-41...
  • Page 638 -60 to 60 °C F002 617C October Average Ambient Temperature -60 to 60 °C F002 617D November Average Ambient Temperature -60 to 60 °C F002 617E December Average Ambient Temperature -60 to 60 °C F002 B-42 T60 Transformer Protection System GE Multilin...
  • Page 639 Power Swing Detect Delay 3 Pickup 0 to 65.535 0.001 F001 65CF Power Swing Detect Delay 4 Pickup 0 to 65.535 0.001 F001 65D0 Power Swing Detect Seal In Delay 0 to 65.535 0.001 F001 GE Multilin T60 Transformer Protection System B-43...
  • Page 640 Phase Overvoltage 1 Block 0 to 4294967295 F300 7047 Phase Overvoltage 1 Target 0 to 2 F109 0 (Self-reset) 7048 Phase Overvoltage 1 Events 0 to 1 F102 0 (Disabled) 7049 ...Repeated for Phase Overvoltage 2 B-44 T60 Transformer Protection System GE Multilin...
  • Page 641 Ground Distance Zone 1 Z0M Z1 Angle -90 to 90 degrees F002 7146 Ground Distance Zone 1 Voltage Level 0 to 5 0.001 F001 7147 Ground Distance Zone 1 Non-Homogeneous Angle -40 to 40 degrees F002 GE Multilin T60 Transformer Protection System B-45...
  • Page 642 Disconnect (Breaker) Switch (Read/Write Setting) (24 modules) 74A0 Disconnect Switch 1 Function 0 to 1 F102 0 (Disabled) 74A1 Disconnect Switch 1 Name F206 “SW 1" 74A4 Disconnect Switch 1 Mode 0 to 1 F157 0 (3-Pole) B-46 T60 Transformer Protection System GE Multilin...
  • Page 643 7797 Repeated for Thermal Protection 2 Ohm Inputs (Read/Write Setting) (2 modules) 77F8 Ohm Inputs 1 Function 0 to 1 F102 0 (Disabled) 77F9 Ohm Inputs 1 ID F205 "Ohm Ip 1 " GE Multilin T60 Transformer Protection System B-47...
  • Page 644 User Programmable Pushbutton 1 Top Line F202 (none) 7B6B User Programmable Pushbutton 1 On Text F202 (none) 7B75 User Programmable Pushbutton 1 Off Text F202 (none) 7B7F User Programmable Pushbutton 1 Drop-Out Time 0 to 60 0.05 F001 B-48 T60 Transformer Protection System GE Multilin...
  • Page 645 CA Loop Impedance Angle -359.9 to 0 degrees F002 7EA9 AG Loop Resistance -2147483647 to F060 2147483647 7EAB AG Loop Reactance -2147483647 to F060 2147483647 7EAD AG Loop Impedance Magnitude 0 to 2147483647 F060 GE Multilin T60 Transformer Protection System B-49...
  • Page 646 0 to 65535 F001 7F71 ...Repeated for Auxiliary Undervoltage 2 7F82 ...Repeated for Auxiliary Undervoltage 3 Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules) 7FA0 Auxiliary Overvoltage 1 Function 0 to 1 F102 0 (Disabled) B-50 T60 Transformer Protection System GE Multilin...
  • Page 647 Breaker Failure 1 Block 0 to 4294967295 F300 8609 Breaker Failure 1 Phase Amp Supv Pickup 0.001 to 30 0.001 F001 1050 860A Breaker Failure 1 Neutral Amp Supv Pickup 0.001 to 30 0.001 F001 1050 GE Multilin T60 Transformer Protection System B-51...
  • Page 648 0 to 1 F102 1 (Enabled) 8A14 Reserved (2 items) F001 8A16 ...Repeated for Digital Element 2 8A2C ...Repeated for Digital Element 3 8A42 ...Repeated for Digital Element 4 8A58 ...Repeated for Digital Element 5 B-52 T60 Transformer Protection System GE Multilin...
  • Page 649 0 to 4294967295 F300 8EF8 Trip Bus 1 Target 0 to 2 F109 0 (Self-reset) 8EF9 Trip Bus 1 Events 0 to 1 F102 0 (Disabled) 8EFA Reserved (8 items) 0 to 1 F001 GE Multilin T60 Transformer Protection System B-53...
  • Page 650 0 to 2 F552 0 (None) 9272 RRTD RTD 1 Target 0 to 2 F109 0 (Self-reset) 9273 RRTD RTD 1 Events 0 to 1 F102 0 (Disabled) 9274 ...Repeated for module number 2 B-54 T60 Transformer Protection System GE Multilin...
  • Page 651 ...Repeated for Direct Input/Output 9 946C ...Repeated for Direct Input/Output 10 9478 ...Repeated for Direct Input/Output 11 9484 ...Repeated for Direct Input/Output 12 9490 ...Repeated for Direct Input/Output 13 949C ...Repeated for Direct Input/Output 14 GE Multilin T60 Transformer Protection System B-55...
  • Page 652 FlexElement 13 Actual -2147483.647 to 2147483.647 0.001 F004 991A FlexElement 14 Actual 0.001 F004 -2147483.647 to 2147483.647 991C FlexElement 15 Actual 0.001 F004 -2147483.647 to 2147483.647 991E FlexElement 16 Actual -2147483.647 to 2147483.647 0.001 F004 B-56 T60 Transformer Protection System GE Multilin...
  • Page 653 VT Fuse Failure 1 V0 3rd Harmonic 0 to 999999.999 0.001 F060 A0AE ...Repeated for module number 2 A0B0 ...Repeated for module number 3 A0B2 ...Repeated for module number 4 A0B4 ...Repeated for module number 5 GE Multilin T60 Transformer Protection System B-57...
  • Page 654 Volts Per Hertz 1 Events 0 to 1 F102 0 (Disabled) A588 Volts Per Hertz 1 Target 0 to 2 F109 0 (Self-reset) A589 Volts Per Hertz 1 T Reset 0 to 1000 F001 B-58 T60 Transformer Protection System GE Multilin...
  • Page 655 Restricted Ground Fault 1 Function 0 to 1 F102 0 (Disabled) A961 Restricted Ground Fault 1 Source 0 to 5 F167 0 (SRC 1) A962 Restricted Ground Fault 1 Pickup 0.005 to 30 0.001 F001 GE Multilin T60 Transformer Protection System B-59...
  • Page 656 Operand for IEC 61850 XCBR Open Interlock 0 to 4294967295 F300 AB07 Operand for IEC 61850 XCBR Close Interlock 0 to 4294967295 F300 AB09 Operand for IEC 61850 XCBR Pos ct1Model 0 to 4 F001 B-60 T60 Transformer Protection System GE Multilin...
  • Page 657 ...Repeated for IEC 61850 GGIO4 Analog Input 18 AF8E ...Repeated for IEC 61850 GGIO4 Analog Input 19 AF95 ...Repeated for IEC 61850 GGIO4 Analog Input 20 AF9C ...Repeated for IEC 61850 GGIO4 Analog Input 21 GE Multilin T60 Transformer Protection System B-61...
  • Page 658 IEC 61850 MMXU W.phsB Deadband 1 0.001 to 100 0.001 F003 10000 B0E2 IEC 61850 MMXU W.phsC Deadband 1 0.001 to 100 0.001 F003 10000 B0E4 IEC 61850 MMXU VAr.phsA Deadband 1 0.001 to 100 0.001 F003 10000 B-62 T60 Transformer Protection System GE Multilin...
  • Page 659 IEC 61850 XSWI Configuration (Read/Write Setting) (24 modules) B370 FlexLogic Operand for IEC 61850 XSWI.ST.Loc Status 0 to 4294967295 F300 B373 ...Repeated for module number 2 B376 ...Repeated for module number 3 B379 ...Repeated for module number 4 GE Multilin T60 Transformer Protection System B-63...
  • Page 660 ...Repeated for module number 3 B960 ...Repeated for module number 4 B980 ...Repeated for module number 5 B9A0 ...Repeated for module number 6 B9C0 ...Repeated for module number 7 B9E0 ...Repeated for module number 8 B-64 T60 Transformer Protection System GE Multilin...
  • Page 661 ...Repeated for Contact Input 38 BC30 ...Repeated for Contact Input 39 BC38 ...Repeated for Contact Input 40 BC40 ...Repeated for Contact Input 41 BC48 ...Repeated for Contact Input 42 BC50 ...Repeated for Contact Input 43 GE Multilin T60 Transformer Protection System B-65...
  • Page 662 ...Repeated for Contact Input 91 BDD8 ...Repeated for Contact Input 92 BDE0 ...Repeated for Contact Input 93 BDE8 ...Repeated for Contact Input 94 BDF0 ...Repeated for Contact Input 95 BDF8 ...Repeated for Contact Input 96 B-66 T60 Transformer Protection System GE Multilin...
  • Page 663 ...Repeated for Virtual Input 42 C028 ...Repeated for Virtual Input 43 C034 ...Repeated for Virtual Input 44 C040 ...Repeated for Virtual Input 45 C04C ...Repeated for Virtual Input 46 C058 ...Repeated for Virtual Input 47 GE Multilin T60 Transformer Protection System B-67...
  • Page 664 ...Repeated for Virtual Output 29 C218 ...Repeated for Virtual Output 30 C220 ...Repeated for Virtual Output 31 C228 ...Repeated for Virtual Output 32 C230 ...Repeated for Virtual Output 33 C238 ...Repeated for Virtual Output 34 B-68 T60 Transformer Protection System GE Multilin...
  • Page 665 ...Repeated for Virtual Output 83 C3C8 ...Repeated for Virtual Output 84 C3D0 ...Repeated for Virtual Output 85 C3D8 ...Repeated for Virtual Output 86 C3E0 ...Repeated for Virtual Output 87 C3E8 ...Repeated for Virtual Output 88 GE Multilin T60 Transformer Protection System B-69...
  • Page 666 ...Repeated for Direct Output 13 C627 ...Repeated for Direct Output 14 C62A ...Repeated for Direct Output 15 C62D ...Repeated for Direct Output 16 C630 ...Repeated for Direct Output 17 C633 ...Repeated for Direct Output 18 B-70 T60 Transformer Protection System GE Multilin...
  • Page 667 ...Repeated for Direct Input 9 C8B4 ...Repeated for Direct Input 10 C8B8 ...Repeated for Direct Input 11 C8BC ...Repeated for Direct Input 12 C8C0 ...Repeated for Direct Input 13 C8C4 ...Repeated for Direct Input 14 GE Multilin T60 Transformer Protection System B-71...
  • Page 668 Remote Device 1 in PMU Scheme 0 to 1 F126 0 (No) CB24 Reserved 0 to 3 F626 0 (None) CB25 ...Repeated for Device 2 CB4A ...Repeated for Device 3 CB6F ...Repeated for Device 4 B-72 T60 Transformer Protection System GE Multilin...
  • Page 669 Remote Output DNA 1 Operand 0 to 4294967295 F300 D222 Remote Output DNA 1 Events 0 to 1 F102 0 (Disabled) D223 Reserved 0 to 1 F001 D224 ...Repeated for Remote Output 2 GE Multilin T60 Transformer Protection System B-73...
  • Page 670 ...Repeated for Remote Output 16 D2E0 ...Repeated for Remote Output 17 D2E4 ...Repeated for Remote Output 18 D2E8 ...Repeated for Remote Output 19 D2EC ...Repeated for Remote Output 20 D2F0 ...Repeated for Remote Output 21 B-74 T60 Transformer Protection System GE Multilin...
  • Page 671 IEC 61850 GGIO2.CF.SPCSO39.ctlModel Value 0 to 2 F001 D347 IEC 61850 GGIO2.CF.SPCSO40.ctlModel Value 0 to 2 F001 D348 IEC 61850 GGIO2.CF.SPCSO41.ctlModel Value 0 to 2 F001 D349 IEC 61850 GGIO2.CF.SPCSO42.ctlModel Value 0 to 2 F001 GE Multilin T60 Transformer Protection System B-75...
  • Page 672 D3EE Reserved F001 D3EF ...Repeated for Contact Output 2 D3FE ...Repeated for Contact Output 3 D40D ...Repeated for Contact Output 4 D41C ...Repeated for Contact Output 5 D42B ...Repeated for Contact Output 6 B-76 T60 Transformer Protection System GE Multilin...
  • Page 673 ...Repeated for Contact Output 55 D719 ...Repeated for Contact Output 56 D728 ...Repeated for Contact Output 57 D737 ...Repeated for Contact Output 58 D746 ...Repeated for Contact Output 59 D755 ...Repeated for Contact Output 60 GE Multilin T60 Transformer Protection System B-77...
  • Page 674 0 to 2 F109 0 (Self-reset) DC7D Synchrocheck 1 Events 0 to 1 F102 0 (Disabled) DC7E Synchrocheck 1 Block 0 to 4294967295 F300 DC80 Synchrocheck 1 Frequency Hysteresis 0 to 0.1 0.01 F001 B-78 T60 Transformer Protection System GE Multilin...
  • Page 675 0 to 2 F001 Phasor Measurement Unit Recording Command (Read/Write Command) EA22 PMU 1 Recording Clear Command 0 to 1 F126 0 (No) EA23 PMU 1 Recording Force Trigger 0 to 1 F126 0 (No) GE Multilin T60 Transformer Protection System B-79...
  • Page 676 PMU 1 Power Trigger Block (3 items) 0 to 4294967295 F300 EB94 PMU 1 Power Trigger Target 0 to 2 F109 0 (Self-reset) EB95 PMU 1 Power Trigger Events 0 to 1 F102 0 (Disabled) B-80 T60 Transformer Protection System GE Multilin...
  • Page 677 0 to 4294967295 F050 Settings File Template (Read/Write Setting) ED09 Template Bitmask (750 items) 0 to 65535 F001 Phasor Measurement Unit Records (Read Only) EFFF PMU Recording Number of Triggers 0 to 65535 F001 GE Multilin T60 Transformer Protection System B-81...
  • Page 678: Data Formats

    0 = 25%, 1 = 50%, 2 = 75%, 3 = 100% UR_UINT32 TIME in SR format (alternate format for F050) First 16 bits are Hours/Minutes (HH:MM:xx.xxx). Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm. Minutes: 0 to 59 in steps of 1. B-82 T60 Transformer Protection System GE Multilin...
  • Page 679 1200 19200 14400 Phase Instantaneous Overcurrent 10 2400 38400 28800 Phase Instantaneous Overcurrent 11 4800 57600 33600 Phase Instantaneous Overcurrent 12 Phase Time Overcurrent 1 Phase Time Overcurrent 2 Phase Time Overcurrent 3 GE Multilin T60 Transformer Protection System B-83...
  • Page 680 Breaker Failure 1 Auxiliary Undervoltage 1 Breaker Failure 2 Auxiliary Undervoltage 2 Breaker Failure 3 Auxiliary Undervoltage 3 Breaker Failure 4 Phase Undervoltage 1 Breaker Failure 5 Phase Undervoltage 2 Breaker Failure 6 B-84 T60 Transformer Protection System GE Multilin...
  • Page 681 Digital Element 25 Non-volatile Latch 1 Digital Element 26 Non-volatile Latch 2 Digital Element 27 Non-volatile Latch 3 Digital Element 28 Non-volatile Latch 4 Digital Element 29 Non-volatile Latch 5 Digital Element 30 GE Multilin T60 Transformer Protection System B-85...
  • Page 682 Disconnect switch 7 RTD Input 19 Disconnect switch 8 RTD Input 20 Disconnect switch 9 RTD Input 21 Disconnect switch 10 RTD Input 22 Disconnect switch 11 RTD Input 23 Disconnect switch 12 B-86 T60 Transformer Protection System GE Multilin...
  • Page 683 0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC System Exception Latching Output Discrepancy F129 Maintenance Alert 01 ENUMERATION: FLEXLOGIC TIMER TYPE SNTP Failure 0 = millisecond, 1 = second, 2 = minute Maintenance Alert Maintenance Alert GE Multilin T60 Transformer Protection System B-87...
  • Page 684 4 = Group 4, 5 = Group 5, 6 = Group 6 F143 UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number) A bit value of 0 = no error, 1 = error B-88 T60 Transformer Protection System GE Multilin...
  • Page 685 4 = SRC 5, 5 = SRC 6 DNA-24 UserSt-27 DNA-25 UserSt-28 DNA-26 UserSt-29 F168 DNA-27 UserSt-30 ENUMERATION: INRUSH INHIBIT FUNCTION DNA-28 UserSt-31 0 = Disabled, 1 = Adapt. 2nd, 2 = Trad. 2nd GE Multilin T60 Transformer Protection System B-89...
  • Page 686 DV1 Xor DV2 ENUMERATION: MEASUREMENT MODE DV1 and DV2 0 = Phase to Ground, 1 = Phase to Phase F189 ENUMERATION: INRUSH INHIBIT MODE 0 = Per Phase, 1 = 2-out-of-3, 2 = Average B-90 T60 Transformer Protection System GE Multilin...
  • Page 687 20 registers, 16 Bits: 1st Char MSB, 2nd Char LSB 0 = Calculated V0, 1 = Measured VX F202 TEXT20: 20-CHARACTER ASCII TEXT 10 registers, 16 Bits: 1st Char MSB, 2nd Char LSB GE Multilin T60 Transformer Protection System B-91...
  • Page 688 MMXU3.MX.TotPF.mag.f MMXU1.MX.W.phsA.cVal.mag.f MMXU3.MX.Hz.mag.f MMXU1.MX.W.phsB.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.mag.f MMXU1.MX.W.phsC.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.ang.f MMXU1.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.mag.f MMXU1.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU1.MX.VAr.phsC.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU1.MX.VA.phsA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU1.MX.VA.phsB.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU1.MX.VA.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU1.MX.PF.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU1.MX.PF.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU1.MX.PF.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU2.MX.TotW.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU2.MX.TotVAr.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU2.MX.TotVA.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU2.MX.TotPF.mag.f MMXU3.MX.A.phsB.cVal.mag.f B-92 T60 Transformer Protection System GE Multilin...
  • Page 689 MMXU5.MX.PF.phsB.cVal.mag.f MMXU4.MX.A.phsB.cVal.ang.f MMXU5.MX.PF.phsC.cVal.mag.f MMXU4.MX.A.phsC.cVal.mag.f MMXU6.MX.TotW.mag.f MMXU4.MX.A.phsC.cVal.ang.f MMXU6.MX.TotVAr.mag.f MMXU4.MX.A.neut.cVal.mag.f MMXU6.MX.TotVA.mag.f MMXU4.MX.A.neut.cVal.ang.f MMXU6.MX.TotPF.mag.f MMXU4.MX.W.phsA.cVal.mag.f MMXU6.MX.Hz.mag.f MMXU4.MX.W.phsB.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f GE Multilin T60 Transformer Protection System B-93...
  • Page 690 IEC 61850 GOOSE Rx dataset GGIO4.MX.AnIn17.mag.f item GGIO4.MX.AnIn18.mag.f None GGIO4.MX.AnIn19.mag.f GGIO3.ST.Ind1.q GGIO4.MX.AnIn20.mag.f GGIO3.ST.Ind1.stVal GGIO4.MX.AnIn21.mag.f GGIO3.ST.Ind2.q GGIO4.MX.AnIn22.mag.f GGIO3.ST.Ind2.stVal GGIO4.MX.AnIn23.mag.f ↓ ↓ GGIO4.MX.AnIn24.mag.f GGIO3.ST.Ind64q GGIO4.MX.AnIn25.mag.f GGIO3.ST.Ind64.stVal GGIO4.MX.AnIn26.mag.f GGIO3.MX.AnIn1.mag.f GGIO4.MX.AnIn27.mag.f GGIO3.MX.AnIn2.mag.f GGIO4.MX.AnIn28.mag.f GGIO3.MX.AnIn3.mag.f GGIO4.MX.AnIn29.mag.f GGIO3.MX.AnIn4.mag.f GGIO4.MX.AnIn30.mag.f GGIO3.MX.AnIn5.mag.f GGIO4.MX.AnIn31.mag.f B-94 T60 Transformer Protection System GE Multilin...
  • Page 691 Wednesday GGIO3.ST.UIntIn4.stVal Thursday GGIO3.ST.UIntIn5.q Friday GGIO3.ST.UIntIn5.stVal Saturday GGIO3.ST.UIntIn6.q GGIO3.ST.UIntIn6.stVal GGIO3.ST.UIntIn7.q F239 GGIO3.ST.UIntIn7.stVal ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS TIME START DAY INSTANCE GGIO3.ST.UIntIn8.q GGIO3.ST.UIntIn8.stVal Value Instance GGIO3.ST.UIntIn9.q First GGIO3.ST.UIntIn9.stVal Second GGIO3.ST.UIntIn10.q Third GGIO3.ST.UIntIn10.stVal GE Multilin T60 Transformer Protection System B-95...
  • Page 692 Description 0...20mA None 4...20mA U1/DC1 potentiometer U1/DC2 tap position U1/DC3 U2/DC1 F247 ENUMERATION: BRICK AC BANK ORIGIN U8/DC3 Value Description None F256 U1/AC1..3 ENUMERATION: BRICK ORIGIN/DESTINATION U1/AC5..7 Value Description U2/AC1..3 None U2/AC5..7 U3/AC1..3 B-96 T60 Transformer Protection System GE Multilin...
  • Page 693 ENUMERATION: ANALOG INPUT MODE [13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64) [14] REMOTE INPUTS (1 to 32) 0 = Default Value, 1 = Last Known [16] DIRECT INPUTS (1 to 96 GE Multilin T60 Transformer Protection System B-97...
  • Page 694 0 = Signed, 1 = Absolute ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION Bitmask Default variation F516 ENUMERATION ELEMENT COMPARE MODE 0 = Level, 1 = Delta F517 ENUMERATION: ELEMENT DIRECTION OPERATION 0 = Over, 1 = Under B-98 T60 Transformer Protection System GE Multilin...
  • Page 695 Corresponds to the Modbus address of the value used when this 4/second 30/second parameter is selected. Only certain values can be used as FlexAn- 5/second 50/second alogs (basically all metering quantities used in protection). 10/second 60/second 12/second 100/second GE Multilin T60 Transformer Protection System B-99...
  • Page 696 Remote RTD 12 PDIF3.ST.Str.general PDIF3.ST.Op.general PDIF4.ST.Str.general F605 PDIF4.ST.Op.general ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT STATUS PDIS1.ST.Str.general PDIS1.ST.Op.general Enumeration Remote DPS input status PDIS2.ST.Str.general Intermediate PDIS2.ST.Op.general PDIS3.ST.Str.general PDIS3.ST.Op.general PDIS4.ST.Str.general PDIS4.ST.Op.general PDIS5.ST.Str.general PDIS5.ST.Op.general PDIS6.ST.Str.general PDIS6.ST.Op.general PDIS7.ST.Str.general PDIS7.ST.Op.general B-100 T60 Transformer Protection System GE Multilin...
  • Page 697 PIOC42.ST.Op.general PIOC16.ST.Op.general PIOC43.ST.Str.general PIOC17.ST.Str.general PIOC43.ST.Op.general PIOC17.ST.Op.general PIOC44.ST.Str.general PIOC18.ST.Str.general PIOC44.ST.Op.general PIOC18.ST.Op.general PIOC45.ST.Str.general PIOC19.ST.Str.general PIOC45.ST.Op.general PIOC19.ST.Op.general PIOC46.ST.Str.general PIOC20.ST.Str.general PIOC46.ST.Op.general PIOC20.ST.Op.general PIOC47.ST.Str.general PIOC21.ST.Str.general PIOC47.ST.Op.general PIOC21.ST.Op.general PIOC48.ST.Str.general PIOC22.ST.Str.general PIOC48.ST.Op.general PIOC22.ST.Op.general PIOC49.ST.Str.general PIOC23.ST.Str.general PIOC49.ST.Op.general PIOC23.ST.Op.general PIOC50.ST.Str.general PIOC24.ST.Str.general PIOC50.ST.Op.general GE Multilin T60 Transformer Protection System B-101...
  • Page 698 PTOC23.ST.Op.general PIOC69.ST.Op.general PTOC24.ST.Str.general PIOC70.ST.Str.general PTOC24.ST.Op.general PIOC70.ST.Op.general PTOV1.ST.Str.general PIOC71.ST.Str.general PTOV1.ST.Op.general PIOC71.ST.Op.general PTOV2.ST.Str.general PIOC72.ST.Str.general PTOV2.ST.Op.general PIOC72.ST.Op.general PTOV3.ST.Str.general PTOC1.ST.Str.general PTOV3.ST.Op.general PTOC1.ST.Op.general PTOV4.ST.Str.general PTOC2.ST.Str.general PTOV4.ST.Op.general PTOC2.ST.Op.general PTOV5.ST.Str.general PTOC3.ST.Str.general PTOV5.ST.Op.general PTOC3.ST.Op.general PTOV6.ST.Str.general PTOC4.ST.Str.general PTOV6.ST.Op.general PTOC4.ST.Op.general PTOV7.ST.Str.general PTOC5.ST.Str.general PTOV7.ST.Op.general B-102 T60 Transformer Protection System GE Multilin...
  • Page 699 RBRF23.ST.OpIn.general PTUV10.ST.Op.general RBRF24.ST.OpEx.general PTUV11.ST.Str.general RBRF24.ST.OpIn.general PTUV11.ST.Op.general RFLO1.MX.FltDiskm.mag.f PTUV12.ST.Str.general RFLO2.MX.FltDiskm.mag.f PTUV12.ST.Op.general RFLO3.MX.FltDiskm.mag.f PTUV13.ST.Str.general RFLO4.MX.FltDiskm.mag.f PTUV13.ST.Op.general RFLO5.MX.FltDiskm.mag.f RBRF1.ST.OpEx.general RPSB1.ST.Str.general RBRF1.ST.OpIn.general RPSB1.ST.Op.general RBRF2.ST.OpEx.general RPSB1.ST.BlkZn.stVal RBRF2.ST.OpIn.general RREC1.ST.Op.general RBRF3.ST.OpEx.general RREC1.ST.AutoRecSt.stVal RBRF3.ST.OpIn.general RREC2.ST.Op.general RBRF4.ST.OpEx.general RREC2.ST.AutoRecSt.stVal RBRF4.ST.OpIn.general RREC3.ST.Op.general RBRF5.ST.OpEx.general RREC3.ST.AutoRecSt.stVal GE Multilin T60 Transformer Protection System B-103...
  • Page 700 GGIO1.ST.Ind24.stVal CSWI16.ST.Pos.stVal GGIO1.ST.Ind25.stVal CSWI17.ST.Loc.stVal GGIO1.ST.Ind26.stVal CSWI17.ST.Pos.stVal GGIO1.ST.Ind27.stVal CSWI18.ST.Loc.stVal GGIO1.ST.Ind28.stVal CSWI18.ST.Pos.stVal GGIO1.ST.Ind29.stVal CSWI19.ST.Loc.stVal GGIO1.ST.Ind30.stVal CSWI19.ST.Pos.stVal GGIO1.ST.Ind31.stVal CSWI20.ST.Loc.stVal GGIO1.ST.Ind32.stVal CSWI20.ST.Pos.stVal GGIO1.ST.Ind33.stVal CSWI21.ST.Loc.stVal GGIO1.ST.Ind34.stVal CSWI21.ST.Pos.stVal GGIO1.ST.Ind35.stVal CSWI22.ST.Loc.stVal GGIO1.ST.Ind36.stVal CSWI22.ST.Pos.stVal GGIO1.ST.Ind37.stVal CSWI23.ST.Loc.stVal GGIO1.ST.Ind38.stVal CSWI23.ST.Pos.stVal GGIO1.ST.Ind39.stVal CSWI24.ST.Loc.stVal GGIO1.ST.Ind40.stVal B-104 T60 Transformer Protection System GE Multilin...
  • Page 701 MMXU1.MX.TotVAr.mag.f GGIO1.ST.Ind78.stVal MMXU1.MX.TotVA.mag.f GGIO1.ST.Ind79.stVal MMXU1.MX.TotPF.mag.f GGIO1.ST.Ind80.stVal MMXU1.MX.Hz.mag.f GGIO1.ST.Ind81.stVal MMXU1.MX.PPV.phsAB.cVal.mag.f GGIO1.ST.Ind82.stVal MMXU1.MX.PPV.phsAB.cVal.ang.f GGIO1.ST.Ind83.stVal MMXU1.MX.PPV.phsBC.cVal.mag.f GGIO1.ST.Ind84.stVal MMXU1.MX.PPV.phsBC.cVal.ang.f GGIO1.ST.Ind85.stVal MMXU1.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind86.stVal MMXU1.MX.PPV.phsCA.cVal.ang.f GGIO1.ST.Ind87.stVal MMXU1.MX.PhV.phsA.cVal.mag.f GGIO1.ST.Ind88.stVal MMXU1.MX.PhV.phsA.cVal.ang.f GGIO1.ST.Ind89.stVal MMXU1.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind90.stVal MMXU1.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind91.stVal MMXU1.MX.PhV.phsC.cVal.mag.f GGIO1.ST.Ind92.stVal MMXU1.MX.PhV.phsC.cVal.ang.f GGIO1.ST.Ind93.stVal MMXU1.MX.A.phsA.cVal.mag.f GE Multilin T60 Transformer Protection System B-105...
  • Page 702 MMXU3.MX.VA.phsC.cVal.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU2.MX.A.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU2.MX.A.phsC.cVal.ang.f MMXU4.MX.TotVAr.mag.f MMXU2.MX.A.neut.cVal.mag.f MMXU4.MX.TotVA.mag.f MMXU2.MX.A.neut.cVal.ang.f MMXU4.MX.TotPF.mag.f MMXU2.MX.W.phsA.cVal.mag.f MMXU4.MX.Hz.mag.f MMXU2.MX.W.phsB.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.W.phsC.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.ang.f MMXU2.MX.VAr.phsA.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.mag.f MMXU2.MX.VAr.phsB.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.ang.f MMXU2.MX.VAr.phsC.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.mag.f MMXU2.MX.VA.phsA.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.ang.f MMXU2.MX.VA.phsB.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.mag.f MMXU2.MX.VA.phsC.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.ang.f B-106 T60 Transformer Protection System GE Multilin...
  • Page 703 MMXU6.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU6.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU6.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU6.MX.VA.phsA.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f MMXU6.MX.VA.phsB.cVal.mag.f MMXU5.MX.A.phsA.cVal.mag.f MMXU6.MX.VA.phsC.cVal.mag.f MMXU5.MX.A.phsA.cVal.ang.f MMXU6.MX.PF.phsA.cVal.mag.f MMXU5.MX.A.phsB.cVal.mag.f MMXU6.MX.PF.phsB.cVal.mag.f MMXU5.MX.A.phsB.cVal.ang.f MMXU6.MX.PF.phsC.cVal.mag.f MMXU5.MX.A.phsC.cVal.mag.f GGIO4.MX.AnIn1.mag.f MMXU5.MX.A.phsC.cVal.ang.f GGIO4.MX.AnIn2.mag.f MMXU5.MX.A.neut.cVal.mag.f GGIO4.MX.AnIn3.mag.f MMXU5.MX.A.neut.cVal.ang.f GGIO4.MX.AnIn4.mag.f MMXU5.MX.W.phsA.cVal.mag.f GGIO4.MX.AnIn5.mag.f MMXU5.MX.W.phsB.cVal.mag.f GGIO4.MX.AnIn6.mag.f MMXU5.MX.W.phsC.cVal.mag.f GGIO4.MX.AnIn7.mag.f MMXU5.MX.VAr.phsA.cVal.mag.f GGIO4.MX.AnIn8.mag.f GE Multilin T60 Transformer Protection System B-107...
  • Page 704 XSWI7.ST.Loc.stVal GGIO1.ST.Ind1.q XSWI7.ST.Pos.stVal GGIO1.ST.Ind1.stVal XSWI8.ST.Loc.stVal GGIO1.ST.Ind2.q XSWI8.ST.Pos.stVal GGIO1.ST.Ind2.stVal XSWI9.ST.Loc.stVal GGIO1.ST.Ind3.q XSWI9.ST.Pos.stVal GGIO1.ST.Ind3.stVal XSWI10.ST.Loc.stVal GGIO1.ST.Ind4.q XSWI10.ST.Pos.stVal GGIO1.ST.Ind4.stVal XSWI11.ST.Loc.stVal GGIO1.ST.Ind5.q XSWI11.ST.Pos.stVal GGIO1.ST.Ind5.stVal XSWI12.ST.Loc.stVal GGIO1.ST.Ind6.q XSWI12.ST.Pos.stVal GGIO1.ST.Ind6.stVal XSWI13.ST.Loc.stVal GGIO1.ST.Ind7.q XSWI13.ST.Pos.stVal GGIO1.ST.Ind7.stVal XSWI14.ST.Loc.stVal GGIO1.ST.Ind8.q XSWI14.ST.Pos.stVal GGIO1.ST.Ind8.stVal XSWI15.ST.Loc.stVal B-108 T60 Transformer Protection System GE Multilin...
  • Page 705 GGIO1.ST.Ind53.stVal GGIO1.ST.Ind27.stVal GGIO1.ST.Ind54.q GGIO1.ST.Ind28.q GGIO1.ST.Ind54.stVal GGIO1.ST.Ind28.stVal GGIO1.ST.Ind55.q GGIO1.ST.Ind29.q GGIO1.ST.Ind55.stVal GGIO1.ST.Ind29.stVal GGIO1.ST.Ind56.q GGIO1.ST.Ind30.q GGIO1.ST.Ind56.stVal GGIO1.ST.Ind30.stVal GGIO1.ST.Ind57.q GGIO1.ST.Ind31.q GGIO1.ST.Ind57.stVal GGIO1.ST.Ind31.stVal GGIO1.ST.Ind58.q GGIO1.ST.Ind32.q GGIO1.ST.Ind58.stVal GGIO1.ST.Ind32.stVal GGIO1.ST.Ind59.q GGIO1.ST.Ind33.q GGIO1.ST.Ind59.stVal GGIO1.ST.Ind33.stVal GGIO1.ST.Ind60.q GGIO1.ST.Ind34.q GGIO1.ST.Ind60.stVal GGIO1.ST.Ind34.stVal GGIO1.ST.Ind61.q GGIO1.ST.Ind35.q GGIO1.ST.Ind61.stVal GE Multilin T60 Transformer Protection System B-109...
  • Page 706 GGIO1.ST.Ind106.stVal GGIO1.ST.Ind80.stVal GGIO1.ST.Ind107.q GGIO1.ST.Ind81.q GGIO1.ST.Ind107.stVal GGIO1.ST.Ind81.stVal GGIO1.ST.Ind108.q GGIO1.ST.Ind82.q GGIO1.ST.Ind108.stVal GGIO1.ST.Ind82.stVal GGIO1.ST.Ind109.q GGIO1.ST.Ind83.q GGIO1.ST.Ind109.stVal GGIO1.ST.Ind83.stVal GGIO1.ST.Ind110.q GGIO1.ST.Ind84.q GGIO1.ST.Ind110.stVal GGIO1.ST.Ind84.stVal GGIO1.ST.Ind111.q GGIO1.ST.Ind85.q GGIO1.ST.Ind111.stVal GGIO1.ST.Ind85.stVal GGIO1.ST.Ind112.q GGIO1.ST.Ind86.q GGIO1.ST.Ind112.stVal GGIO1.ST.Ind86.stVal GGIO1.ST.Ind113.q GGIO1.ST.Ind87.q GGIO1.ST.Ind113.stVal GGIO1.ST.Ind87.stVal GGIO1.ST.Ind114.q GGIO1.ST.Ind88.q GGIO1.ST.Ind114.stVal B-110 T60 Transformer Protection System GE Multilin...
  • Page 707 MMXU2.MX.A.neut.cVal.ang.f MMXU1.MX.PPV.phsCA.cVal.mag.f MMXU2.MX.W.phsA.cVal.mag.f MMXU1.MX.PPV.phsCA.cVal.ang.f MMXU2.MX.W.phsB.cVal.mag.f MMXU1.MX.PhV.phsA.cVal.mag.f MMXU2.MX.W.phsC.cVal.mag.f MMXU1.MX.PhV.phsA.cVal.ang.f MMXU2.MX.VAr.phsA.cVal.mag.f MMXU1.MX.PhV.phsB.cVal.mag.f MMXU2.MX.VAr.phsB.cVal.mag.f MMXU1.MX.PhV.phsB.cVal.ang.f MMXU2.MX.VAr.phsC.cVal.mag.f MMXU1.MX.PhV.phsC.cVal.mag.f MMXU2.MX.VA.phsA.cVal.mag.f MMXU1.MX.PhV.phsC.cVal.ang.f MMXU2.MX.VA.phsB.cVal.mag.f MMXU1.MX.A.phsA.cVal.mag.f MMXU2.MX.VA.phsC.cVal.mag.f MMXU1.MX.A.phsA.cVal.ang.f MMXU2.MX.PF.phsA.cVal.mag.f MMXU1.MX.A.phsB.cVal.mag.f MMXU2.MX.PF.phsB.cVal.mag.f MMXU1.MX.A.phsB.cVal.ang.f MMXU2.MX.PF.phsC.cVal.mag.f MMXU1.MX.A.phsC.cVal.mag.f MMXU3.MX.TotW.mag.f MMXU1.MX.A.phsC.cVal.ang.f MMXU3.MX.TotVAr.mag.f MMXU1.MX.A.neut.cVal.mag.f MMXU3.MX.TotVA.mag.f MMXU1.MX.A.neut.cVal.ang.f MMXU3.MX.TotPF.mag.f GE Multilin T60 Transformer Protection System B-111...
  • Page 708 MMXU5.MX.A.phsB.cVal.mag.f MMXU4.MX.Hz.mag.f MMXU5.MX.A.phsB.cVal.ang.f MMXU4.MX.PPV.phsAB.cVal.mag.f MMXU5.MX.A.phsC.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.ang.f MMXU5.MX.A.phsC.cVal.ang.f MMXU4.MX.PPV.phsBC.cVal.mag.f MMXU5.MX.A.neut.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.ang.f MMXU5.MX.A.neut.cVal.ang.f MMXU4.MX.PPV.phsCA.cVal.mag.f MMXU5.MX.W.phsA.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.ang.f MMXU5.MX.W.phsB.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.mag.f MMXU5.MX.W.phsC.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.ang.f MMXU5.MX.VAr.phsA.cVal.mag.f MMXU4.MX.PhV.phsB.cVal.mag.f MMXU5.MX.VAr.phsB.cVal.mag.f MMXU4.MX.PhV.phsB.cVal.ang.f MMXU5.MX.VAr.phsC.cVal.mag.f MMXU4.MX.PhV.phsC.cVal.mag.f MMXU5.MX.VA.phsA.cVal.mag.f MMXU4.MX.PhV.phsC.cVal.ang.f MMXU5.MX.VA.phsB.cVal.mag.f MMXU4.MX.A.phsA.cVal.mag.f MMXU5.MX.VA.phsC.cVal.mag.f MMXU4.MX.A.phsA.cVal.ang.f MMXU5.MX.PF.phsA.cVal.mag.f MMXU4.MX.A.phsB.cVal.mag.f MMXU5.MX.PF.phsB.cVal.mag.f B-112 T60 Transformer Protection System GE Multilin...
  • Page 709 GGIO5.ST.UIntIn10.stVal MMXU6.MX.PF.phsC.cVal.mag.f GGIO5.ST.UIntIn11.q GGIO4.MX.AnIn1.mag.f GGIO5.ST.UIntIn11.stVal GGIO4.MX.AnIn2.mag.f GGIO5.ST.UIntIn12.q GGIO4.MX.AnIn3.mag.f GGIO5.ST.UIntIn12.stVal GGIO4.MX.AnIn4.mag.f GGIO5.ST.UIntIn13.q GGIO4.MX.AnIn5.mag.f GGIO5.ST.UIntIn13.stVal GGIO4.MX.AnIn6.mag.f GGIO5.ST.UIntIn14.q GGIO4.MX.AnIn7.mag.f GGIO5.ST.UIntIn14.stVal GGIO4.MX.AnIn8.mag.f GGIO5.ST.UIntIn15.q GGIO4.MX.AnIn9.mag.f GGIO5.ST.UIntIn15.stVal GGIO4.MX.AnIn10.mag.f GGIO5.ST.UIntIn16.q GGIO4.MX.AnIn11.mag.f GGIO5.ST.UIntIn16.stVal GGIO4.MX.AnIn12.mag.f PDIF1.ST.Str.general GGIO4.MX.AnIn13.mag.f PDIF1.ST.Op.general GGIO4.MX.AnIn14.mag.f PDIF2.ST.Str.general GGIO4.MX.AnIn15.mag.f PDIF2.ST.Op.general GE Multilin T60 Transformer Protection System B-113...
  • Page 710 PIOC33.ST.Op.general PIOC7.ST.Op.general PIOC34.ST.Str.general PIOC8.ST.Str.general PIOC34.ST.Op.general PIOC8.ST.Op.general PIOC35.ST.Str.general PIOC9.ST.Str.general PIOC35.ST.Op.general PIOC9.ST.Op.general PIOC36.ST.Str.general PIOC10.ST.Str.general PIOC36.ST.Op.general PIOC10.ST.Op.general PIOC37.ST.Str.general PIOC11.ST.Str.general PIOC37.ST.Op.general PIOC11.ST.Op.general PIOC38.ST.Str.general PIOC12.ST.Str.general PIOC38.ST.Op.general PIOC12.ST.Op.general PIOC39.ST.Str.general PIOC13.ST.Str.general PIOC39.ST.Op.general PIOC13.ST.Op.general PIOC40.ST.Str.general PIOC14.ST.Str.general PIOC40.ST.Op.general PIOC14.ST.Op.general PIOC41.ST.Str.general PIOC15.ST.Str.general PIOC41.ST.Op.general B-114 T60 Transformer Protection System GE Multilin...
  • Page 711 PTOC14.ST.Op.general PIOC60.ST.Op.general PTOC15.ST.Str.general PIOC61.ST.Str.general PTOC15.ST.Op.general PIOC61.ST.Op.general PTOC16.ST.Str.general PIOC62.ST.Str.general PTOC16.ST.Op.general PIOC62.ST.Op.general PTOC17.ST.Str.general PIOC63.ST.Str.general PTOC17.ST.Op.general PIOC63.ST.Op.general PTOC18.ST.Str.general PIOC64.ST.Str.general PTOC18.ST.Op.general PIOC64.ST.Op.general PTOC19.ST.Str.general PIOC65.ST.Str.general PTOC19.ST.Op.general PIOC65.ST.Op.general PTOC20.ST.Str.general PIOC66.ST.Str.general PTOC20.ST.Op.general PIOC66.ST.Op.general PTOC21.ST.Str.general PIOC67.ST.Str.general PTOC21.ST.Op.general PIOC67.ST.Op.general PTOC22.ST.Str.general PIOC68.ST.Str.general PTOC22.ST.Op.general GE Multilin T60 Transformer Protection System B-115...
  • Page 712 RBRF14.ST.OpIn.general PTUV1.ST.Op.general RBRF15.ST.OpEx.general PTUV2.ST.Str.general RBRF15.ST.OpIn.general PTUV2.ST.Op.general RBRF16.ST.OpEx.general PTUV3.ST.Str.general RBRF16.ST.OpIn.general PTUV3.ST.Op.general RBRF17.ST.OpEx.general PTUV4.ST.Str.general RBRF17.ST.OpIn.general PTUV4.ST.Op.general RBRF18.ST.OpEx.general PTUV5.ST.Str.general RBRF18.ST.OpIn.general PTUV5.ST.Op.general RBRF19.ST.OpEx.general PTUV6.ST.Str.general RBRF19.ST.OpIn.general PTUV6.ST.Op.general RBRF20.ST.OpEx.general PTUV7.ST.Str.general RBRF20.ST.OpIn.general PTUV7.ST.Op.general RBRF21.ST.OpEx.general PTUV8.ST.Str.general RBRF21.ST.OpIn.general PTUV8.ST.Op.general RBRF22.ST.OpEx.general PTUV9.ST.Str.general RBRF22.ST.OpIn.general B-116 T60 Transformer Protection System GE Multilin...
  • Page 713 XSWI3.ST.Pos.stVal CSWI7.ST.Pos.stVal XSWI4.ST.Loc.stVal CSWI8.ST.Loc.stVal XSWI4.ST.Pos.stVal CSWI8.ST.Pos.stVal XSWI5.ST.Loc.stVal CSWI9.ST.Loc.stVal XSWI5.ST.Pos.stVal CSWI9.ST.Pos.stVal XSWI6.ST.Loc.stVal CSWI10.ST.Loc.stVal XSWI6.ST.Pos.stVal CSWI10.ST.Pos.stVal XSWI7.ST.Loc.stVal CSWI11.ST.Loc.stVal XSWI7.ST.Pos.stVal CSWI11.ST.Pos.stVal XSWI8.ST.Loc.stVal CSWI12.ST.Loc.stVal XSWI8.ST.Pos.stVal CSWI12.ST.Pos.stVal XSWI9.ST.Loc.stVal CSWI13.ST.Loc.stVal XSWI9.ST.Pos.stVal CSWI13.ST.Pos.stVal XSWI10.ST.Loc.stVal CSWI14.ST.Loc.stVal XSWI10.ST.Pos.stVal CSWI14.ST.Pos.stVal XSWI11.ST.Loc.stVal CSWI15.ST.Loc.stVal XSWI11.ST.Pos.stVal GE Multilin T60 Transformer Protection System B-117...
  • Page 714 Port 2 PTP Clock F617 Port 3 PTP Clock ENUMERATION: LOGIN ROLES IRIG-B SNTP Enumeration Role None Administrator F625 ENUMERATION: PTP STATE Supervisor Engineer Enumeration Item Operator Disabled Factory No Signal Calibrating Synchronized Synchronized (No PDelay) B-118 T60 Transformer Protection System GE Multilin...
  • Page 715 Virtual Input 2 Virtual Input 3 ↓ ↓ F628 ENUMERATION: SECURITY BYPASS ACCESS Virtual Input 64 Disables security on local access, remote access, or both. Enumeration Item Disabled Local and Remote Local Remote GE Multilin T60 Transformer Protection System B-119...
  • Page 716 B.4 MEMORY MAPPING APPENDIX B B-120 T60 Transformer Protection System GE Multilin...
  • Page 717: Iec 61850

    LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract ser- vices in IEC 61850-8-1. The T60 relay supports IEC 61850 server services over TCP/IP. The TCP/IP profile requires the T60 to have an IP address to establish communications. These addresses are located in the ...
  • Page 718: File Transfer By Iec 61850

    APPENDIX C C.1.3 FILE TRANSFER BY IEC 61850 The T60 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as an example. In the AX-S4 61850 Explorer window, click the Tools menu and access the SISCO File Transfer Utility.
  • Page 719: Server Data Organization

    C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the T60 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.
  • Page 720: Mmxu: Analog Measured Values

    A limited number of measured analog values are available through the MMXU logical nodes. Each MMXU logical node provides data from a T60 current and voltage source. There is one MMXU available for each con- figurable source (programmed in the ...
  • Page 721 The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the T60 protection elements, these flags take their values from the pickup and operate FlexLogic operands for the corresponding element.
  • Page 722: Server Features And Configuration

    C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the T60. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the settings.
  • Page 723: Logical Node Name Prefixes

    A built-in TCP/IP connection timeout of two minutes is employed by the T60 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the T60. This frees up the con- nection to be used by other clients.
  • Page 724: Generic Substation Event Services: Gsse And Goose

    MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the T60 will use the source Ether- net MAC address as the destination, with the multicast bit set.
  • Page 725 The T60 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 726 REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic equations or other settings. The T60 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
  • Page 727: Ethernet Mac Address For Gsse/Goose

    GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the T60 is configured to use an automated multicast MAC scheme. If the T60 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.
  • Page 728: Iec 61850 Implementation Via Enervista Ur Setup

    An ICD file is generated for the T60 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 729: Configuring Iec 61850 Settings

    Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the T60 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.
  • Page 730: About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
  • Page 731 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. GE Multilin T60 Transformer Protection System C-15...
  • Page 732 RptEnabled Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure C–4: ICD FILE STRUCTURE, IED NODE C-16 T60 Transformer Protection System GE Multilin...
  • Page 733 BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure C–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE GE Multilin T60 Transformer Protection System C-17...
  • Page 734: Creating An Icd File With Enervista Ur Setup

    The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline T60 settings file is typically much quicker than create an ICD file directly from the relay.
  • Page 735 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE GE Multilin T60 Transformer Protection System C-19...
  • Page 736 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. C-20 T60 Transformer Protection System GE Multilin...
  • Page 737: Importing An Scd File With Enervista Ur Setup

    Figure C–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the T60 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
  • Page 738 The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
  • Page 739: Acsi Conformance

    Setting group control REPORTING Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion GE Multilin T60 Transformer Protection System C-23...
  • Page 740: Acsi Services Conformance Statement

    SERVER/ UR FAMILY PUBLISHER SERVER (CLAUSE 7) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 8) Associate Abort Release LOGICAL DEVICE (CLAUSE 9) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 10) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 11) GetDataValues SetDataValues GetDataDirectory GetDataDefinition C-24 T60 Transformer Protection System GE Multilin...
  • Page 741 LOGGING (CLAUSE 17) LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 18, ANNEX C) GOOSE-CONTROL-BLOCK (CLAUSE 18) SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK (ANNEX C) SendGSSEMessage GetReference GetGSSEElementNumber GetGsCBValues GE Multilin T60 Transformer Protection System C-25...
  • Page 742 (QueryLogByTime or QueryLogAfter) c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) NOTE c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) C-26 T60 Transformer Protection System GE Multilin...
  • Page 743: Logical Nodes Table

    GGIO: Generic process I/O GLOG: Generic log GSAL: Generic security application I: LOGICAL NODES FOR INTERFACING AND ARCHIVING IARC: Archiving IHMI: Human machine interface ISAF: Safety alarm function ITCI: Telecontrol interface ITMI: Telemonitoring interface GE Multilin T60 Transformer Protection System C-27...
  • Page 744 PRTR: Rotor protection PSCH: Protection scheme PSDE: Sensitive directional earth fault PTEF: Transient earth fault PTOC: Time overcurrent PTOF: Overfrequency PTOV: Overvoltage PTRC: Protection trip conditioning PTTR: Thermal overload PTUC: Undercurrent PTUF: Underfrequency PTUV: Undervoltage C-28 T60 Transformer Protection System GE Multilin...
  • Page 745 T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TANG: Angle TAXD: Axial displacement TCTR: Current transformer TDST: Distance TFLW: Liquid flow TFRQ: Frequency TGSN: Generic sensor THUM: Humidity TLVL: Media level TMGF: Magnetic field TMVM: Movement sensor GE Multilin T60 Transformer Protection System C-29...
  • Page 746 ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRES: Resistor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZSCR: Semi-conductor controlled rectifier ZSMC: Synchronous machine ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component C-30 T60 Transformer Protection System GE Multilin...
  • Page 747: Iec 60870-5-103

    Xt = (8191/Xmax) * X - 4096 a = 2 * 4096/Xmax b = -4096 To calculate Xmax, one needs to know the rated value for the specific type of measurand. Xmax = 2.4 * Xrated GE Multilin T60 Transformer Protection System...
  • Page 748: Interoperability Document

     <5> Power on Status indications in monitor direction INF Semantics  <16> Auto-recloser active  <17> Teleprotection active  <18> Protection active  <19> LED reset  <20> Monitor direction blocked  <21> Test mode T60 Transformer Protection System GE Multilin...
  • Page 749  <67> Start/pick-up N  <68> General trip  <69> Trip L  <70> Trip L  <71> Trip L  <72> Trip I>> (back-up operation)  <73> Fault location X in ohms  <74> Fault forward/line GE Multilin T60 Transformer Protection System...
  • Page 750  <243> Read directory of a single entry  <244> Read value or attribute of a single entry  <245> End of general interrogation of generic data  <249> Write entry with confirmation  <250> Write entry with execution T60 Transformer Protection System GE Multilin...
  • Page 751  Generic services  Private data Miscellaneous MEASURAND MAX MVAL = TIMES RATED VALUE Current L   Current L   Current L   Voltage L   Voltage L   GE Multilin T60 Transformer Protection System...
  • Page 752 D.1 IEC 60870-5-103 APPENDIX D MEASURAND MAX MVAL = TIMES RATED VALUE Voltage L   Active power P   Reactive power Q   Frequency f   Voltage L   T60 Transformer Protection System GE Multilin...
  • Page 753: Iec 60870-5-104 Protocol

    Balanced Transmission Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin T60 Transformer Protection System...
  • Page 754  <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 T60 Transformer Protection System GE Multilin...
  • Page 755  <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin T60 Transformer Protection System...
  • Page 756 •Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 T60 Transformer Protection System GE Multilin...
  • Page 757 <34> M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin T60 Transformer Protection System...
  • Page 758 <120> F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure T60 Transformer Protection System GE Multilin...
  • Page 759  Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin T60 Transformer Protection System...
  • Page 760 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs T60 Transformer Protection System GE Multilin...
  • Page 761: Point List

    E.1.2 POINT LIST The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. See the Communications section of chapter 5 for details. IEC104 POINT LISTS GE Multilin T60 Transformer Protection System...
  • Page 762 E.1 IEC 60870-5-104 PROTOCOL APPENDIX E E-10 T60 Transformer Protection System GE Multilin...
  • Page 763: Device Profile Document

    2048 Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin T60 Transformer Protection System...
  • Page 764 FlexLogic. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. T60 Transformer Protection System GE Multilin...
  • Page 765  16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin T60 Transformer Protection System...
  • Page 766: F.1.2 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the T60 is not restarted, but the DNP process is restarted. T60 Transformer Protection System GE Multilin...
  • Page 767 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the T60 is not restarted, but the DNP process is restarted. GE Multilin T60 Transformer Protection System...
  • Page 768 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the T60 is not restarted, but the DNP process is restarted. T60 Transformer Protection System GE Multilin...
  • Page 769 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the T60 is not restarted, but the DNP process is restarted. GE Multilin T60 Transformer Protection System...
  • Page 770: Dnp Point Lists

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 T60 Transformer Protection System GE Multilin...
  • Page 771: Binary And Control Relay Output

    Virtual Input 27 Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin T60 Transformer Protection System...
  • Page 772: Counters

    Events Since Last Clear A counter freeze command has no meaning for counters 8 and 9. T60 Digital Counter values are represented as 32-bit inte- gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values.
  • Page 773: Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin T60 Transformer Protection System F-11...
  • Page 774 F.2 DNP POINT LISTS APPENDIX F F-12 T60 Transformer Protection System GE Multilin...
  • Page 775: Radius Server Configuration

    UR device for successful authentication, and the shortname is a short, optional alias that can be used in place of the IP address. client 10.0.0.2/24 { secret = testing123 shortname = private-network-1 In the <Path_to_Radius>\etc\raddb folder, create a file called dictionary.ge and add the following content. # ########################################################## GE VSAs ############################################################ VENDOR...
  • Page 776 Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf file. Restart the relay for the IP address and port changes to take effect.
  • Page 777: Change Notes

    7 December 2007 URX-253 1601-0090-S2 5.5x 22 February 2008 URX-258 1601-0090-S3 5.5x 12 March 2008 URX-260 1601-0090-T1 5.6x 27 June 2008 08-0390 1601-0090-U1 5.7x 29 May 2009 09-0938 1601-0090-U2 5.7x 30 September 2009 09-1165 GE Multilin T60 Transformer Protection System...
  • Page 778: Changes To The T60 Manual

    Deleted EAC logo from title page and deleted EAC certification from Approvals specifications because document not translated into Russian 5-200 5-200 Update Updated Zone 1 and 2 ground distance logic diagrams to include IG Table H–3: MAJOR UPDATES FOR T60 MANUAL REVISION AA3 (Sheet 1 of 2) PAGE PAGE CHANGE DESCRIPTION (AA2)
  • Page 779 APPENDIX H H.1 CHANGE NOTES Table H–3: MAJOR UPDATES FOR T60 MANUAL REVISION AA3 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (AA2) (AA3) 5-159 5-159 Update Updated FlexLogic operands table Update Updated FlexAnalog and FlexInteger tables Update Updated Modbus memory map and F codes Table H–4: MAJOR UPDATES FOR T60 MANUAL REVISION AA2...
  • Page 780 H.1 CHANGE NOTES APPENDIX H Table H–6: MAJOR UPDATES FOR T60 MANUAL REVISION Z1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (Y3) (Z1) Added General Cautions and Warnings to section 1.1.1 Update Revised section 1.3.1 on system requirements, including addition of support for Windows 7 and...
  • Page 781 APPENDIX H H.1 CHANGE NOTES Table H–9: MAJOR UPDATES FOR T60 MANUAL REVISION Y1 (Sheet 2 of 3) PAGE PAGE CHANGE DESCRIPTION (X2) (Y1) 5-18 5-18 Update Updated Networks section 5.2.4d to include all three Ethernet ports 5-18 5-18 Update Added 0 as valid number to section 5.2.4e Modbus Protocol section...
  • Page 782 H.1 CHANGE NOTES APPENDIX H Table H–9: MAJOR UPDATES FOR T60 MANUAL REVISION Y1 (Sheet 3 of 3) PAGE PAGE CHANGE DESCRIPTION (X2) (Y1) Added Security menu and submenu commands and descriptions to the Command menu Added to Minor self-test error message **Bad PTP Signal**...
  • Page 783: Abbreviations

    MRT ....Minimum Response Time MSG....Message F ..... Field MTA ....Maximum Torque Angle FAIL....Failure MTR ....Motor FD ....Fault Detector MVA ....MegaVolt-Ampere (total 3-phase) FDH....Fault Detector high-set MVA_A....MegaVolt-Ampere (phase A) FDL ....Fault Detector low-set GE Multilin T60 Transformer Protection System...
  • Page 784 ..... With Option RST ....Reset WRT....With Respect To RSTR ..... Restrained RTD ....Resistance Temperature Detector X ....Reactance RTU ....Remote Terminal Unit XDUCER..Transducer RX (Rx) ..Receive, Receiver XFMR..... Transformer T60 Transformer Protection System GE Multilin...
  • Page 785 APPENDIX H H.2 ABBREVIATIONS Z ..... Impedance, Zone GE Multilin T60 Transformer Protection System...
  • Page 786: Warranty

    H.3.1 GE MULTILIN WARRANTY For products shipped as of 1 October 2013, GE Grid Solutions warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Grid Solutions Terms and Conditions at https://www.gegridsolutions.com/multilin/warranty.htm...
  • Page 787: Index

    ................5-263 CAUTIONS ................. 1-1 Modbus registers ............B-50 CE APPROVALS .............. 2-36 settings ............... 5-263 CHANGES TO T60 MANUAL..........H-2 specifications ..............2-24 CHANNEL TESTS ............6-11 AUXILIARY VOLTAGE CHANNEL ........3-12 CHANNELS AUXILIARY VOLTAGE METERING ........6-19 banks ...............
  • Page 788 ............... 5-102 actual values ..............6-16 CT FAILURE instantaneous .............. 5-219 FlexLogic operands ............5-160 percent ................ 5-214 logic ................5-305 transformer ....... 5-107, 5-110, 5-117, 5-213, 5-214 settings ............... 5-304 CT INPUTS .............3-12, 5-6, 5-102 T60 Transformer Protection System GE Multilin...
  • Page 789 ..............2-27 FlexLogic™ operands ..........5-163 via EnerVista software ............. 4-2 internal ............... 5-105 EVENTS DNA-1 BIT PAIR ............5-320 syslog ................5-23 EVENTS SETTING ............. 5-5 EXCEPTION RESPONSES ..........B-6 F485 ................1-16 GE Multilin T60 Transformer Protection System...
  • Page 790 Modbus registers ............B-36 G.703 WIRE SIZE .............3-34 FLEXELEMENTS GATEWAY ADDRESS ............5-33 actual values ..............6-23 GE TYPE IAC CURVES ..........5-226 direction ..............5-176 GROUND CURRENT METERING ........6-18 FlexLogic operands ............5-160 GROUND DIRECTIONAL SUPERVISION ......5-200 hysteresis ..............5-176 GROUND DISTANCE Modbus registers ..........B-54, B-56...
  • Page 791 ............10-1 FlexLogic operands ............. 5-165 MAINTENANCE COMMANDS ..........7-3 logic ................5-219 MANUFACTURING DATE ..........6-31 settings ............... 5-219 MAXIMUM CT/VT WIRE SIZE ........... 3-11 specifications ..............2-22 MEMORY MAP DATA FORMATS ........B-82 GE Multilin T60 Transformer Protection System...
  • Page 792 OVERCURRENT CURVE TYPES ........5-223 specifications..............2-24 OVERCURRENT CURVES NEUTRAL INSTANTANEOUS OVERCURRENT definite time ..............5-227 see entry for NEUTRAL IOC FlexCurves ..............5-227 I2T ................5-227 IAC ................5-226 IEC ................5-225 IEEE ................5-223 T60 Transformer Protection System GE Multilin...
  • Page 793 ............... 5-182 actual values ..............6-12 specifications ..............2-22 explained ............... 5-32 PHASE INSTANTANEOUS OVERCURRENT settings ................. 5-31 see entry for PHASE IOC specifications ..............2-32 PU QUANTITY ..............5-4 PUSHBUTTONS, USER-PROGRAMMABLE see USER-PROGRAMMABLE PUSHBUTTONS GE Multilin T60 Transformer Protection System...
  • Page 794 ................4-4 settings ............... 5-245 Modbus registers ............B-81 specifications..............2-23 password protection ............4-5 REVISION HISTORY ............H-1 RF IMMUNITY ..............2-35 removing ................. 4-7 viewing ................4-6 RFI, CONDUCTED ............2-35 viii T60 Transformer Protection System GE Multilin...
  • Page 795 SYSTEM REQUIREMENTS ..........1-5 loss of life ............2-25, 5-221 SYSTEM SETUP ............5-102 metering ................ 6-16 Modbus registers ............B-35 phase relationships ............5-111 phasors ............... 5-112 settings ..........5-108, 5-110, 5-119 thermal inputs .............. 5-119 GE Multilin T60 Transformer Protection System...
  • Page 796 Modbus registers ..........B-37, B-48 WITHDRAWAL FROM OPERATION ........10-8 settings ................. 5-84 specifications..............2-27 USER-PROGRAMMABLE SELF TESTS Modbus registers ............B-34 settings ................. 5-81 ZERO SEQUENCE CORE BALANCE .........3-12 USERST-1 BIT PAIR ............5-320 ZERO-SEQUENCE COMPENSATION ....5-115, 5-116 T60 Transformer Protection System GE Multilin...

Table of Contents