Running the Motor

This chapter takes the new user through all the essential steps to
running a motor for the first time, in each of the possible operating
modes.
Verify 120 Vac control transformer is configured per Table 4-
6. Before applying line voltage to drive system! Otherwise,
damage to control transformer and/or 120 Vac I/O protection
fuse F3 could result.
CAUTION
Ensure that no damage or safety hazard could arise from the
motor starting unexpectedly.
WARNING
The values of the motor parameters affect the protection of
the motor.
The default values in the drive should not be relied upon.
It is essential that the correct value is entered in Pr 5.07
CAUTION
(SE07, 0.28) Motor rated current. This affects the thermal
protection of the motor.
If the keypad mode has been used previously, ensure that
the keypad reference has been set to 0 using the
buttons as if the drive is started using the keypad it will run to
CAUTION
the speed defined by the keypad reference (Pr 1.17).
If the intended maximum speed affects the safety of the
machinery, additional independent over-speed protection
must be used.
WARNING
Table 7-1 Minimum control connection requirements for each
control mode
Drive control method
Terminal mode
Keypad mode
Serial communications
Refer to Figure 4-1 on page 28 for minimum connections to get a motor
running.
72
Electrical
Getting
Basic
Installation
Started
parameters
Requirements
Drive enable
Speed reference
Run forward or run reverse
command
Drive enable
Drive enable
Serial communications link
Running
SMARTCARD
Optimization
the Motor
Operation
www.emersonct.com
Onboard
Advanced
Technical
Diagnostics
PLC
Parameters
Data
Quantum MP User Guide
UL
Information
Issue: A4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents