Running the motor

This section takes a new user through all the essential steps to running a motor for the first time.
Table 7-1 Open Loop and RFC-A
Action
Ensure:
Before power up
The default setting is Open Loop vector mode. For RFC-A mode set
Pr 00.079 to RFC-A, then press the
Power up the drive
the parameters.
Ensure:
Enter:
Enter minimum and
maximum speeds
Enter:
Enter accel and
decel rates
Enter:
Enter motor
nameplate details
Ready to autotune
The drive is able to perform either a stationary or a rotating autotune.
The motor must be at a standstill before an autotune is enabled.
To perform an autotune:
Autotune
Autotune complete
When the autotune has been completed, Pr 00.038 will be set to 0
Tuning of frequency
Depending on the application, the frequency controller gains
controller gains
(Pr 03.010, Pr 03.011 and Pr 03.012) may need to be adjusted.
(RFC-A mode only)
Save parameters
Select 'SAVE' in Pr mm.000 (alternatively enter a value of 1000) and
Save parameters
press the
Ready to run
Run
The drive is now ready to run the motor.
Increasing and
Turning the speed potentiometer will increase and decrease the
decreasing speed
speed of the motor.
To stop the motor under ramp control, open either the run forward or
Stopping
run reverse terminal. If the enable terminal is opened while the motor
is running, the motor will coast to a stop.
32
The drive enable signal is not given, terminal 11 is open
The run signal is not given, terminal 12/13 is open
The motor is connected to the drive
The motor connection is correct for the drive Δ or Y
The correct supply voltage is connected to the drive
The drive displays: Inh
Minimum speed Pr 00.001 (Hz)
Maximum speed Pr 00.002 (Hz)
Acceleration rate Pr 00.003 (s/100 Hz)
Deceleration rate Pr 00.004 (s/100 Hz)
Motor rated current in Pr 00.006 (A)
Motor rated speed in Pr 00.007 (rpm)
Motor rated voltage in Pr 00.008 (V)
Motor rated power factor in Pr 00.009
If the motor is not a standard 50/60 Hz motor, set Pr 00.039
accordingly
Set Pr 00.038 = 1 for a stationary autotune or set Pr 00.038 = 2
for a rotating autotune
Close the drive enable signal (apply +24 V to terminal 11). The
drive will display 'Rdy'.
Close the run signal (apply +24 V to terminal 12 or 13). The
display will flash 'tuning' while the drive is performing the
autotune.
Wait for the drive to display 'Inh' and for the motor to come to a
standstill.
Remove the drive enable and run signal from the drive.
Stop / Reset button to save parameters.
Detail
stop/reset button to save
Unidrive M200-201 Quick Start Guide
Pr 02
Pr 01
t
100Hz
t
Pr 03
Pr 04
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55
I.cl F
°
C 40 s S1
V
Hz min
-1
kW
cosφ
A
230
50 1445 2.20 0.80 8.50
400
4.90
CN = 14.5Nm
240
50 1445 2.20 0.76 8.50
415
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
cos
R
S
σL
S
Issue Number: 5