General

4.16.1
120V User I/O control terminal specifications
C6
Digital input 1
C8
Digital input 2
C10
Digital input 3
C12
Digital input 4
C14
Digital input 5
C4
Digital input 6
Terminal C4 default function
Terminal C6 default function
Terminal C8 default function
Terminal C10 default function
Terminal C12 default function
Terminal C14 default function
Type of input
Maximum input voltage
Nominal input voltage range
Nominal input frequency range
Voltage for ON state
Current for ON state
Voltage for OFF state
Current for OFF state
On fast update time
Off fast update time
C1
120 Vac user output
C3
120 Vac user output
C5
120 Vac user output
C7
120 Vac user output
C9
120 Vac user output
C11
120 Vac user output
C13
120 Vac user output
Supply for user external trip
Terminal C1 Function
(E-Stop) terminal C2
Supply for user external trip (Interlocks)
Terminal C3 Function
terminal C4
Supply for user Not Stop
Terminal C5 Function
terminal C6
Terminal C7 Function
Supply for user Run terminal C8
Terminal C9 Function
Supply for user Jog terminal C10
Supply for user Forward/Reverse
Terminal C11 Function
terminal C12
Supply for user Reset
Terminal C13 Function
terminal C14
Nominal output voltage
120 Vac
Maximum output current
250 mA total for all 120 Vac outputs
Protection
Fuse
C15
120 Vac Relay output neutral
Terminal C15 Function
50
Electrical
Getting
Basic
Installation
Started
parameters
External trip input
Not Stop
Run
Jog
Forward/Reverse
Reset
120 Vac digital logic inputs
132 Vac 50/60 Hz
96 Vac to 132 Vac
(120 Vac, +10% / -20%)
47 Hz to 53 Hz or 
56 Hz to 63 Hz
79 Vac to 132 Vac
2 mA to 3 mA
0 Vac to 20 Vac
0 mA to 1.5 mA
16.5 ms
24.5 ms
120 Vac Neutral connection point for
C16 relay output
Running the
SMARTCARD
Optimization
Motor
Operation
C16
120 Vac relay output
Terminal C16 function
Nominal output voltage
Update time ON
Update time OFF
Maximum output current
Protection
4.16.2
24 Vdc/Analog control terminal specification
1
0V common
Function
2
+24V external input
Function
Nominal voltage
Minimum continuous operating
voltage
Maximum continuous operating
voltage
Minimum start-up voltage
Recommended power supply
Recommended fuse
3
0V common
Function
4
+10V user output
Function
Voltage tolerance
Nominal output current
Protection
www.emersonct.com
Onboard
Advanced
Technical
Diagnostics
PLC
Parameters
Data
Contactor enable (Drive ON)
120 Vac
16.5 ms
24.5 ms
250 mA total for all 120 Vac outputs
Fuse
Common connection for all external
devices
To supply the control circuit
without providing a supply to the
power stage
+24.0 Vdc
+19.2 Vdc
+30.0 Vdc
21.6 Vdc
60W 24 Vdc nominal
3A, 50 Vdc
Common connection for all external
devices
Supply for external analog devices
1%
10 mA
Current limit and trip @12 mA
Quantum MP User Guide