Inputs/Outputs; Contact Inputs - GE L90 Instruction Manual

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
— This setting defines the maximum frequency level required for operation of the element.
FREQ RATE 1 MAX FREQUENCY
The setting can be used to effectively block the feature based on frequency. For example, if the intent is to monitor a
decreasing trend but only if the frequency is already below a certain level (such as for load shedding), set this setting to the
required frequency level.
If the signal source assigned to the frequency rate of change element is only set to auxiliary VT, then the minimum
voltage supervision is 3 V.

5.9 Inputs/outputs

5.9.1 Contact inputs

SETTINGS  INPUTS/OUTPUTS  CONTACT INPUTS
 CONTACT INPUTS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Figure 5-229: Frequency rate of change logic
 CONTACT INPUT H5a
CONTACT INPUT H5a ID:
Cont Ip 1
CONTACT INPUT H5a
DEBNCE TIME: 6.0 ms
CONTACT INPUT H5a
EVENTS: Disabled
 CONTACT INPUT xxx
 CONTACT INPUT
 THRESHOLDS
INPUTS/OUTPUTS
Range: up to 20 alphanumeric
characters
Range: 0.0 to 16.0 ms in steps of 0.5
Range: Disabled, Enabled
5
5-413