PRODUCT SETUP
5.3.12.4 Trip and alarm LEDs
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  TRIP & ALARMS LEDS
 TRIP & ALARM LEDS
The trip and alarm LEDs are in the first LED column (enhanced and graphical front panels) and on LED panel 1 (standard
front panel). Each LED can be programmed to turn on when the selected FlexLogic operand is in the logic 1 state.
5.3.12.5 User-programmable LED 1(48)
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  USER-PROGRAMMABLE LED 1(48)
 USER-PROGRAMMABLE
 LED 1
For the enhanced and standard front panels, there are 48 amber LEDs across the relay LED panels. Each of these
indicators can be programmed to illuminate when the selected FlexLogic operand is in the logic 1 state.
For the standard front panel, the LEDs are located as follows:
LED Panel 2 — User-programmable LEDs 1 through 24
LED Panel 3 — User programmable LEDs 25 through 48
5
For the enhanced front panel, the LEDs are located as follows:
LED column 2 — User-programmable LEDs 1 through 12
LED column 3 — User-programmable LEDs 13 through 24
LED column 4 — User-programmable LEDs 25 through 36
LED column 5 — User-programmable LEDs 37 through 48
See the LED Indicators section in chapter 4 for information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the
Reset" (the default setting), the LED illumination tracks the state of the selected LED operand. If the
"Latched," the LED, once lit, remains so until reset by the front panel
communications channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5-15: Recommended settings for user-programmable LEDs
Setting
LED 1 operand
LED 2 operand
LED 3 operand
LED 4 operand
LED 5 operand
LED 6 operand
LED 7 operand
LED 8 operand
LED 9 operand
LED 10 operand
LED 11 operand
LED 12 operand
5-124
TRIP LED INPUT:
Off
ALARM LED INPUT:
Off
LED 1 OPERAND:
Off
LED 1 TYPE:
Self-Reset
Parameter
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
Off
Off
BREAKER 1 OPEN
BREAKER 1 CLOSED
BREAKER 1 TROUBLE
Off
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched
button, from a remote device via a
RESET
Setting
Parameter
LED 13 operand
Off
LED 14 operand
BREAKER 2 OPEN
LED 15 operand
BREAKER 2 CLOSED
LED 16 operand
BREAKER 2 TROUBLE
LED 17 operand
SYNC 1 SYNC OP
LED 18 operand
SYNC 2 SYNC OP
LED 19 operand
Off
LED 20 operand
Off
LED 21 operand
AR ENABLED
LED 22 operand
AR DISABLED
LED 23 operand
AR RIP
LED 24 operand
AR LO
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
setting is "Self-
LED 1 TYPE
setting is
LED 1 TYPE