S5 INPUTS/OUTPUTS

6.6 S5 Inputs/Outputs

6.6.1 Contact inputs

6–74
Courtesy of NationalSwitchgear.com
S5 INPUTS/OUTPUTS
CONTACT INPUTS
OUTPUT RELAYS
VIRTUAL INPUTS
898768.cdr
The 350 relay is equipped with eight (8) contact inputs, which can be used to provide a
variety of functions such as for circuit breaker control, external trips, blocking of protection
elements, etc. All contact inputs are wet type contacts (refer to the 350 typical wiring
diagram) that require an external DC voltage source. The voltage threshold (17V, 33V, 84V,
166V) is selectable, and it applies for all eight contact inputs.
The contact inputs are either open or closed with a programmable debounce time to
prevent false operation from induced voltage. Because of de-bouncing, momentary
contacts must have a minimum dwell time greater than half power frequency cycle. The
debounce time is adjustable by the user.
PATH:
SETPOINTS > S5 INPUTS/OUTPUTS > CONTACT INPUTS
S5 CONTACT INPUTS
SELECT DC VOLTAGE
52a BKR INPUT 1
52b
BKR INPUT 2
CONTACT INPUT 3
...
CONTACT INPUT 8
S5 OUTPUT RELAYS
RELAY 1 TRIP
RELAY 2 CLOSE
RELAY 3 AUXILIARY
RELAY 4 AUXILIARY
RELAY 5 AUXILIARY
RELAY 6 AUXILIARY
S5 VIRTUAL INPUTS
VIRTUAL INPUT 1
VIRTUAL INPUT 2
VIRTUAL INPUT 3
VIRTUAL INPUT 4
...
VIRTUAL INPUT 32
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS
S5 52a BKR INPUT 1
DEBOUNCE TIME
S5 CONTACT INPUT 8
DEBOUNCE TIME
S5 RELAY 1 TRIP
SEAL-IN TIME
S5 RELAY 2 CLOSE
SEAL-IN TIME
S5 RELAY 6 AUXILIARY
OUTPUT TYPE
S5 VIRTUAL INPUT 1
VI 1 FUNCTION
V INPUT 1 TYPE
S5 VIRTUAL INPUT 32
VI 32 FUNCTION
V INPUT 32 TYPE