GE L90 Instruction Manual page 262

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

PRODUCT SETUP
5
Reset
Range: ON, OFF, any FlexLogic operand
Default: OFF
This setting selects a FlexLogic operand that when activated acknowledges/resets all annunciator windows in the
graphical front panel. This setting is the same as the one defined in Settings > Inputs/Outputs > Resetting > Reset
Annunciator; see the Resetting section in this chapter.
LAYOUT
Range: 3x4, 4x6, 6x8
Default: 3x4
Selects the number of rows and columns to display on the annunciator pages. For example, 3x4 means 12 windows
display per page over eight pages. Up to 96 entries are possible.
To view the layout, click the Preview button.
PAGE NAMES
Range: up to 20 alphanumeric characters
Default: Page 1...Page 8
Up to 20 characters can be input as the name of each annunciator page. The number of pages depends on the Layout.
5-38
Figure 5-11: Annunciator editor with preview shown
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS