GE L90 Instruction Manual page 736

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

PHASE DISTANCE THROUGH POWER TRANSFORMERS
The Zone 1 settings are:
PHS DIST Z1 REACH
: "85"
PHS DIST Z1 RCA
PHS DIST Z1 XMFR VOL CONNECTION
PHS DIST Z1 XMFR CUR CONNECTION
The Zone 4 settings are:
PHS DIST Z4 REACH
: "89"
PHS DIST Z4 RCA
PHS DIST Z4 XMFR VOL CONNECTION
PHS DIST Z4 XMFR CUR CONNECTION
8
8-28
: "0.80"
: "None"
: "Dy1"
: "2.60"
: "Yd11"
: "None"
CHAPTER 8: APPLICATION OF SETTINGS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Eq. 8-20
Eq. 8-21