GE L90 Instruction Manual page 208

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

FLEXLOGIC DESIGN USING ENGINEER
Category
Block or gate
affected
Error
Timer
Error
Input
Warnings
When using the 'Reset OP' operand, a warning can appear indicating that this is a disabled feature. This means that the
Reset Settting's FlexLogic operand is set to OFF. Resetting of the relay can be done by pressing the reset button on the front
panel of the relay or by sending a Reset command through communications.
Table 4-4: Warning messages from compiling
Category
Block or
gate
affected
Minor warning
Input
4
Major warning
Tag-Out
Major warning
All
Minor warning
=VO
Minor warning
Input
Setting warning
Input
Major warning
Input
Major warning
Input
Setting warning
Input
Setting warning
Input
4.4.1.5 Rapidly add logic blocks in sequence
Blocks are added by clicking an element then clicking in the drawing area, or by dragging and dropping the element onto
the canvas. Blocks can be added rapidly in sequence, for example when you have inputs 1 to 10, without having to select
the element each time.
To rapidly add logic blocks:
1.
In Engineer, click File > Preferences. The window opens.
2.
Click the Editor entry.
3.
Enable the Repeat Symbol check box.
4.
Click the Ok button to save and exit from the window.
5.
In the logic diagram, select an element, then click in the drawing area to add it, click again to add a second box, and
so on.
4-72
Message
Timer used more than once
(TIMER_ID, SheetReference)
Unrecognized Parameter
(SYMBOL_ID,Name,SheetRefere
nce)
Message
Input set to unused VO
(SYMBOL_ID,Name,Sheet)
Tag-out not connected
(TAG_ID,Sheet)
Symbol not connected
(SYMBOL_ID,Name,Sheet)
Virtual Output n using default
name (VO_ID,Sheet)
Input using default name
(SYMBOL_ID,Name,Sheet)
Input using disabled feature
(SYMBOL_ID,Name,Sheet)
Input set to OFF
(SYMBOL_ID,Sheet)
Input set to ON
(SYMBOL_ID,Sheet)
Contact Output Operate is OFF
(SYMBOL_ID, Contacts)
Contact Output Seal-In is OFF
(SYMBOL_ID, Contacts)
Description
The same timer is used in more than one place in the editor. This means
either the circuit that the Timer belongs to has been branched, or the
Timer has been duplicated.
An Input symbol is configured to an item that is not recognized by the
current order code and version. Possible cause: The order code and/or
version of the settings file was converted causing the input parameter to
become unavailable.
Description
An Input symbol is using an unassigned Virtual Output
A Tag-Out symbol has no input
A symbol's input and/or output is not connected and is not part of a
VO block. Draw the input and/or output to the block.
The Assigned Virtual Output is using the default name. Change the
name.
An Input symbol is using a Contact Input, Contact Output, Digital
Element, FlexElement, or Digital Counter set to the default name.
Change the name so that it is unique.
An Input symbol is using a disabled Virtual Input, Contact Input, Digital
Element, FlexElement, Digital Counter, Control Pushbutton,
Programmable Pushbutton, Contact Output, or Protection/Monitoring
Element. Enable it and try again.
An Input symbol is set to OFF
An Input symbol is set to ON
The symbol block is using the default setting of OFF
The symbol block is using the default setting of OFF
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL