GE L90 Instruction Manual page 347

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Application example 1
Assume one needs to check if any of the LEDs is "burned" through user-programmable pushbutton 1. Apply the following
settings.
Configure user-programmable pushbutton 1 by making the following entries in the
PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1
PUSHBUTTON 1 FUNCTION
PUSHBTN 1 DROP-OUT TIME
Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the
PRODUCT SETUP  USER-PROGRAMMABLE LEDS  LED TEST
: "Enabled"
LED TEST FUNCTION
:
"PUSHBUTTON 1
LED TEST CONTROL
The test is initiated when the user-programmable pushbutton 1 is pressed. Keep the pushbutton pressed for as long as the
LEDs are being visually inspected. When finished, release the pushbutton. The relay then automatically starts stage 2. At
this point, test can be cancelled by pressing the pushbutton.
Application example 2
Assume one needs to check if any LEDs are "burned" as well as exercise one LED at a time to check for other failures. This
is to be performed via user-programmable pushbutton 1.
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. When
finished, release the pushbutton so that the relay then automatically starts stage 2. When stage 2 is completed, stage 3
starts automatically. The test can be cancelled at any time by pressing the pushbutton.
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Figure 5-52: LED test sequence
menu. (The option does not display when not purchased.)
: "Self-reset"
: "0.10 s"
ON"
SETTINGS  PRODUCT SETUP  USER-
menu:
PRODUCT SETUP
5
SETTINGS 
5-123

Advertisement

Table of Contents
loading