TRANSDUCER INPUTS/OUTPUTS
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel
of a type 5C transducer module installed in the first available slot.
The function of the channel can be either "Enabled" or "Disabled." If "Disabled," there is not an actual value created for the
channel. An alphanumeric ID is assigned to the channel; this ID is included in the channel actual values. It is also used to
reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the type of
RTD connected to the channel configures the channel.
Actions based on RTD overtemperature, such as trips or alarms, are done in conjunction with the FlexElements feature. In
FlexElements, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting the
operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output
contact directly.
See the following table for reference temperature values for each RTD type.
Table 5-44: RTD temperature vs. resistance
Temperature
°C
°F
–50
–58
–40
–40
–30
–22
–20
–4
–10
14
0
32
10
50
5
20
68
30
86
40
104
50
122
60
140
70
158
80
176
90
194
100
212
110
230
120
248
130
266
140
284
150
302
160
320
170
338
180
356
190
374
200
392
210
410
220
428
230
446
240
464
250
482
5-424
Resistance (in ohms)
100 Ω Pt
120 Ω Ni
100 Ω Ni
(DIN 43760)
80.31
86.17
71.81
84.27
92.76
77.30
88.22
99.41
82.84
92.16
106.15
88.45
96.09
113.00
94.17
100.00
120.00
100.00
103.90
127.17
105.97
107.79
134.52
112.10
111.67
142.06
118.38
115.54
149.79
124.82
119.39
157.74
131.45
123.24
165.90
138.25
127.07
174.25
145.20
130.89
182.84
152.37
134.70
191.64
159.70
138.50
200.64
167.20
142.29
209.85
174.87
146.06
219.29
182.75
149.82
228.96
190.80
153.58
238.85
199.04
157.32
248.95
207.45
161.04
259.30
216.08
164.76
269.91
224.92
168.47
280.77
233.97
172.46
291.96
243.30
175.84
303.46
252.88
179.51
315.31
262.76
183.17
327.54
272.94
186.82
340.14
283.45
190.45
353.14
294.28
194.08
366.53
305.44
10 Ω Cu
7.10
7.49
7.88
8.26
8.65
9.04
9.42
9.81
10.19
10.58
10.97
11.35
11.74
12.12
12.51
12.90
13.28
13.67
14.06
14.44
14.83
15.22
15.61
16.00
16.39
16.78
17.17
17.56
17.95
18.34
18.73