Control Elements; Overview - GE L90 Instruction Manual

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

CONTROL ELEMENTS

DIR POWER 1 CALIBRATION
when a small difference in VT and CT angular errors is to be compensated to permit more sensitive settings. This setting
virtually enables calibration of the directional power function in terms of the angular error of applied VTs and CTs. The
element responds to the sum of the
DIR POWER 1 STG1 SMIN
for the stage 1 of the element. The positive values imply a shift towards the operate region along the RCA line; the negative
values imply a shift towards the restrain region along the RCA line. See the Directional Power Sample Applications figure
for details. Together with the RCA, this setting enables a wide range of operating characteristics. This setting applies to
three-phase power and is entered in per-unit (pu) values. The base quantity is 3 x VT pu base x CT pu base.
For example, a setting of 2% for a 200 MW machine is 0.02 × 200 MW = 4 MW. If 13.8kV is line voltage and 10 kA is a
primary CT current, the source pu quantity is 239 MVA, and thus, SMIN needs to be set at 4 MW / 239 MVA = 0.0167 pu ≈
0.017 pu. If the reverse power application is considered, RCA = 180° and SMIN = 0.017 pu.
The element drops out if the magnitude of the positive-sequence current becomes virtually zero, that is, it drops below the
cutoff level.
DIR POWER 1 STG1 DELAY
applications for a synchronous machine, stage 1 is typically applied for alarming and stage 2 for tripping.
5
5.8 Control elements

5.8.1 Overview

Control elements are used for control rather than protection. See the Introduction to Elements section at the beginning of
this chapter for information.
5.8.2 Trip bus
SETTINGS  CONTROL ELEMENTS  TRIP BUS  TRIP BUS 1(6)
 TRIP BUS 1
5-324
— This setting allows the relay characteristic angle to change in steps of 0.05°. This is useful
DIR POWER 1 RCA
— This setting specifies the minimum power as defined along the relay characteristic angle (RCA)
— This setting specifies a time delay for stage 1. For reverse power or low forward power
Figure 5-184: Sensitive directional power logic
TRIP BUS 1
FUNCTION: Disabled
and
DIR POWER 1 CALIBRATION
Range: Enabled, Disabled
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
settings.

Advertisement

Table of Contents
loading

Table of Contents