FLEXLOGIC
Operand type
ELEMENT:
Underfrequency
ELEMENT:
Volts per hertz
ELEMENT:
Wattmetric zero-
sequence directional
FIXED OPERANDS
INPUTS/OUTPUTS:
Contact inputs
INPUTS/OUTPUTS:
Contact outputs,
current
5
(from detector on
form-A output only)
INPUTS/OUTPUTS:
Contact outputs,
voltage
(from detector on
form-A output only)
INPUTS/OUTPUTS:
Direct input
INPUTS/OUTPUTS:
RxGOOSE DPS
INPUTS/OUTPUTS:
RxGOOSE Booleans
INPUTS/OUTPUTS:
Virtual inputs
5-200
Operand syntax
UNDERFREQ 1 PKP
UNDERFREQ 1 OP
UNDERFREQ 1 DPO
UNDERFREQ 2 to 6
VOLT PER HERTZ 1 PKP
VOLT PER HERTZ 1 OP
VOLT PER HERTZ 1 DPO
VOLT PER HERTZ 2
WATTMETRIC 1 PKP
WATTMETRIC 1 OP
WATTMETRIC 2
Off
On
Cont Ip 1 On
Cont Ip 2 On
Cont Ip 1 Off
Cont Ip 2 Off
Cont Ip 120 On
Cont Ip 120 Off
Cont Op 1
IOn
Cont Op 2
IOn
Cont Op 72
IOn
Cont Op 1 VOn
Cont Op 2
VOn
Cont Op 72
VOn
Cont Op 1
VOff
Cont Op 2
VOff
Cont Op 72
VOff
Direct I/P 1-1 On
Direct I/P 1-8 On
Direct I/P 2-1 On
Direct I/P 2-8 On
RxG DPS 1 BAD
RxG DPS 1 INTERM
RxG DPS 1 OFF
RxG DPS 1 ON
RxG DPS 2 to 5
RxG Bool 1 On
RxG Bool 2 On
RxG Bool 3 On
RxG Bool 256 On
Virt Ip 1 On
Virt Ip 2 On
Virt Ip 3 On
Virt Ip 64 On
Operand description
Underfrequency 1 has picked up
Underfrequency 1 has operated
Underfrequency 1 has dropped out
Same set of operands as shown for UNDERFREQ 1
The volts per hertz element 1 has picked up
The volts per hertz element 1 has operated
The volts per hertz element 1 has dropped out
Same set of operands as VOLT PER HERTZ 1
Wattmetric directional element 1 has picked up
Wattmetric directional element 1 has operated
Same set of operands as per WATTMETRIC 1
Logic = 0. Does nothing and can be used as a delimiter in an equation list;
used as 'Disable' by other features.
Logic = 1. Can be used as a test setting.
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(appears only when an inter-relay communications card is used)
(appears only when inter-relay communications card is used)
(appears only when inter-relay communications card is used)
(appears only when inter-relay communications card is used)
Asserted while the RxGOOSE double-point status input is in the bad state
Asserted while the RxGOOSE double-point status input is in the intermediate
state
Asserted while the RxGOOSE double-point status input is off
Asserted while the RxGOOSE double-point status input is on
Same set of operands as per RxG DPS 1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1