CHAPTER 3: INSTALLATION
Flashing yellow — internal mode while receiving a valid data packet
Solid red — (switch to) internal timing mode while not receiving a valid data packet
The link/activity LED status is as follows:
Flashing green — FPGA is receiving a valid data packet
Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit"
Solid red — FPGA is not receiving a valid packet or the packet received is invalid

3.5 Activate relay

The relay is in the default "Not Programmed" state when it leaves the factory. When powered up successfully, the "Trouble"
LED is on and the "In Service" LED is off. The relay in the "Not Programmed" state blocks signaling of any output relay. These
conditions remain until the relay is explicitly put in the "Programmed" state.
RELAY SETTINGS:
Not Programmed
The relay can be activated on the front panel or in the EnerVista software.
To activate the relay using the front panel:
1.
Press the
key until the
MENU
2.
Press the
right arrow until the
MESSAGE
3.
Press the
down arrow until the
MESSAGE
4.
Press the
right arrow until the
MESSAGE
SETTINGS
 SETTINGS
 PRODUCT SETUP
5.
After the
RELAY SETTINGS:
"Programmed."
6.
Press the
key to save the change.
ENTER
RELAY SETTINGS:
Not Programmed
7.
When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the "In Service"
LED turns on.
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
When the relay is powered up, the "Trouble LED" is on, the "In Service" LED is off, and this message
displays, indicating that the relay is in the "Not Programmed" state and is safeguarding (output
relays blocked) against the installation of a relay whose settings have not been entered. This
message remains until the relay is explicitly put in the "Programmed" state.
header flashes momentarily and the
SETTINGS
message displays.
SECURITY
message displays.
INSTALLATION
RELAY SETTINGS:
 SECURITY
 DISPLAY
 PROPERTIES
 INSTALLATION
Not Programmed message displays, press a
RELAY SETTINGS:
Programmed
PRODUCT SETUP
Not Programmed message displays.
RELAY SETTINGS:
Not Programmed
key to change the selection to
VALUE
NEW SETTING
HAS BEEN STORED
ACTIVATE RELAY
message displays.
3-49
3