3.1 General Reference Conditions
Quantity of Influence
Temperature
Relative humidity
Frequency
Supply voltage
Electric field
Magnetic field
■
The intrinsic uncertainty is the error specified for the reference conditions.
■
The operating uncertainty includes the intrinsic uncertainty plus variations of the quantities of influence
(position, supply voltage, temperature, etc.) as defined in standard IEC 61557.
In this section, uncertainties are typically expressed as % of the reading (R) plus number of display counts
(ct).
3.2 Electrical Specifications
3.2.1 Voltage Measurement
Specific reference conditions: Peak factor = 1.414 in AC, sinusoidal signal.
Measurement Range
Resolution
Accuracy
Input impedance
Frequency ranges
3.2.2 Frequency Measurement
Measurement Range
Resolution
Accuracy
28
1.800.561.8187
3. TECHNICAL SPECIFICATIONS
Reference Values
23° ± 3°C (73.4° ± 5.4°F)
45 to 55% RH
DC and 45 to 65Hz
8V ± 0.2V
battery life indication 58% ± 8%
< 40A/m
0.3 to 399.9V
0.1V (AC and DC)
DC and 15.3 at 800Hz
15.3 to 399.9V
0.1Hz
± (1% R + 2 ct)
www.
0V/m
400 to 700V
1V (AC and DC)
± (3% R + 2 ct)
400kΩ
400 to 700V
1Hz
± (1.5% R + 1 ct)
Megohmmeter Model 6526/6532/6534