Statement of Compliance Chauvin Arnoux , Inc. d.b.a. AEMC Instruments ® ® certifies that this instrument has been calibrated using standards and instruments traceable to international standards. We guarantee that at the time of shipping your instrument has met the instrument’s published specifications.
TABLE OF CONTENTS 1. INTRODUCTION ................6 1.1 PRECAUTIONS FOR USE ..........7 1.2 RECEIVING YOUR SHIPMENT ..........7 1.3 ORDERING INFORMATION ............. 8 1.3.1 Accessories ..................8 1.3.2 Replacement Parts................. 8 2. PRODUCT FEATURES ..............9 2.1 DESCRIPTION ................9 2.2 CONTROL FEATURES ............
Example: hardwired equipment in fixed installation and circuit breakers. CAT II: Corresponds to measurements performed on circuits directly connected to the electrical distribution system. Example: measurements on household appliances and portable tools. Megohmmeter Model 6505 - User Manual...
Lead – Replacement 1 ft Jumper Lead ..........Cat. #2151.31 9.6V rechargeable NiMH battery pack..........Cat. #2960.21 Power Cord 115 V US Plug .............. Cat. #5000.14 Order Accessories and Replacement Parts Directly Online Check our Storefront at www.aemc.com/store for availability Megohmmeter Model 6505 - User Manual...
Capacitance of the sample and discharge voltage present at the test leads is displayed at the test’s conclusion. The Model 6505 is designed with the highest level of built-in safety features. This meter incorporates test inhibit capabilities that will not allow test voltages to be generated if a live sample is detected.
AC power plug (direct operation on AC and battery recharge). Back-lit crystal display (see § 2.5). Serial interface male plug (9-pin) for calibration only. Rotary selector switch with 8 positions (see § 2.3). START/STOP button. Two function buttons (see § 2.4). Megohmmeter Model 6505 - User Manual...
Decreases the flashing parameter being displayed. ▼ Used to navigate the list of interval insulation measurements in the R(t) function. NOTE: If you hold down the ▲ or ▼ buttons, the movement speed between parameters will increase Megohmmeter Model 6505 - User Manual...
± 3 V or > 35 V Indicates the duration of the measurement or the time remaining in the case of PI measurement. Indicates the battery is low and must be recharged (§ 5.1). Megohmmeter Model 6505 - User Manual...
START/STOP button will have no effect, and no measurements will be made. Similarly, if an excessively high erroneous voltage (> 0.4 Un) is detected during the measurement, the measurement will automatically stop. Megohmmeter Model 6505 - User Manual...
Connect the blue high-voltage lead between the insulation and the G terminal of the instrument. The guard serves to eliminate the effect of surface leakage currents. Megohmmeter Model 6505 - User Manual...
Page 15
■ Duration of the measurement. After the measurement (5 Presses) ■ Test voltage generated during the measurement. ■ Current that flowed in the resistance measured. Surface leakage current. ■ ■ Capacitance. Megohmmeter Model 6505 - User Manual...
DAR = R 1 min / R 30 s (2 values to be recorded during a measurement lasting 1 min). *For the calculation of the PI, the times of 1 and 10 min can be modified by the user, if required, for a particular application. See § 3.5.1. Megohmmeter Model 6505 - User Manual...
Press and hold the DISPLAY button. Then, turn the rotary switch to the SET Vlock position. You can modify the second PI time using the ▲ and ▼ buttons. ■ ■ To save changes, simply turn the switch. Megohmmeter Model 6505 - User Manual...
It will be displayed for a few seconds when an affected range is selected (e.g. if the maximum voltage is 750 V, it will be applied and displayed on all switch settings from 1000 V up). Megohmmeter Model 6505 - User Manual...
Eliminate the voltage and restart the ■ measurement. Indicates that the protective fuse of ■ the G terminal is defective. ■ Replace the fuse as indicated in § 5.2. Megohmmeter Model 6505 - User Manual...
100 V from (1000 to 5100) V Nominal Current: > 1 mA Short-circuit Current: < 1.6 mA ± 5 % Load Current: 3 mA approx when starting measurement Max. Acceptable Voltage: Upeak = 0.4 Un Megohmmeter Model 6505 - User Manual...
0.2 % Un or 1 ct Accuracy 5 % of Reading ± 3 cts 4.3.3 Calculation of Terms DAR and PI Specified Range 0.02 to 50.00 Resolution 0.01 Accuracy 5 % of Reading ± 1ct Megohmmeter Model 6505 - User Manual...
4.3.4 Typical Change Curve for Test Voltages according to Load Range 500 V MΩ 0.01 Range 1000 V 1200 1000 MΩ Range 2500 V 3000 2500 2000 1500 1000 MΩ Range 5000 V 6000 5000 4000 3000 2000 1000 MΩ Megohmmeter Model 6505 - User Manual...
(14 to 131) °F (-10 to 55) °C during measurement (10 to 80) % RH Storage: (-40 to 158) °F (-40 to 70) °C; (10 to 90) % RH Altitude: < 2000 m Use indoors or outdoors Megohmmeter Model 6505 - User Manual...
(0 to 20) % Vn MΩ 0.1 % R / % Vn on test % Vn ± 5 cts voltage *The terms DAR, PI, DD and the capacity and current leak measurements are included in the quantity “MΩ.” Megohmmeter Model 6505 - User Manual...
5. MAINTENANCE Use only factory specified replacement parts. AEMC Instruments will not be held ® responsible for any accident, incident, or malfunction following a repair completed other than by its service center or by an approved repair center. 5.1 RECHARGING THE BATTERY If the symbol is displayed, the battery needs to be recharged.
Instruments, not by the distributor from whom it was purchased. This ® warranty is void if the unit has been tampered with, abused, or if the defect is related to service not performed by AEMC Instruments. ® Full warranty coverage and product registration is available on our website www.aemc.com/warranty.html...